AS168XAC1 SCHURTER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 8

Technical content

Thermal-magnetic (TM and AS-line) AS168XAC1www.schurter.com /PG20 Circuit Breakers Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 1 pole

Description

  • Thermal-magnetic circuit breaker - High short circuit performance - Availability of AC and DC in the same frame size - DIN-Rail Mounting Standards - Approval Reference Type: AS168X - IEC 60934 - UL508, UL1077 - CSA C22.2

Applications

  • Industrial appliances Weblinks pdf-datasheet, html-datasheet, General Product Information, Approvals, CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor- Stock-Check, Detailed request for product, Product News Technical Data General data Rated Voltage AC IEC : 240 V; 50/60 Hz ␣ UL/CSA : 277 V; 50/60 Hz Rated Voltage DC 65 V Rated current 0.5 - 52 A , see approbations Conditional short circuit capa- city IEC 60934 Icn: AC 240 V / DC 65 V: 5 kA (no fuse) Conditional short circuit capa- city UL 1077 Inc: AC 277 V: 10 kA (with fuse class H/J, 4x rated current (min. 15 A)) Icn: AC 125 V: 10 kA (no fuse) Icn: AC 277 V: 5 kA (no fuse) Icn: DC 65 V: 2 kA (no fuse) Conditional short circuit capa- city UL 508 Icn: AC 277 V: 5 kA (no fuse) Degree of Protection from front side IP 40 acc. to IEC 60529 Lifetime 1 x Ir : 6000 switching cycles Dielectric Strength 50 Hz: > 2 kV Impulse 1.2/50 μs Vibration Resistance ± 0.75 mm @ 5 - 57 Hz acc. to IEC 60068-2-6, test Fc

10 G @ 57 - 500 Hz

acc. to IEC 60068-2-6, test Fc Insulation Resistance 250/440 VAC > 5 MΩ Shock Resistance 25 G / 10 ms acc. to IEC 60068-2-27, test Ea Ambient temperature -20 °C to 60 °C Weight 100 - 130 g Tripping Type Positively trip free Actuation type Manual ON/OFF Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG Switched neutral Rated Voltage AC 277 V Rated current AC/DC 65 A Function The switched neutral closes with ma- nual closure of the poles and opens automatically with thermal magnetic tripping of the poles. Add-on modules Add-on modules Technical data for the additional module see separate data sheet

Thermal-magnetic (TM and AS-line)AS168XAC1 www.schurter.com /PG20 Circuit Breakers Dimension AS168X 1 pole 1.9 44.4 61.6 68.4 5.1A) 26.6 17.5 A) 35 mm DIN rail EN 50022 B) Max. torque Wire crosssection Max. torque 16 ... 25 mm2 3.1 Nm AS168X 1 pole and switched neutral pole 1.9 44.4 61.6 68.4 5.1 26.6 35A) A) 35 mm DIN rail EN 50022 B) Max. torque Wire crosssection Max. torque 16 ... 25 mm2 3.1 Nm

Thermal-magnetic (TM and AS-line) AS168XAC1www.schurter.com /PG20 Circuit Breakers Diagrams AS168X-CB1... / AS168X-ACBA

Thermal-magnetic (TM and AS-line)AS168XAC1 www.schurter.com /PG20 Circuit Breakers Symbol Standard Rated current Rated voltage AC Conditional short circuit capacity Icn Rated voltage DC Conditional short circuit capacity Icn UL 508 CSA C22.2 no. 14 0.5 - 52 A 277 V 5 kA - - UL 1077 0.5 - 40 A 240 V 10 kA - - CSA C22.2 no. 235 0.5 - 50 A 277 V 125 V 5 kA 10 kA

65 V 2 kA

EN 60934 0.5 - 30 A 240 V 4.5 kA 65 V 4.5 kA GB 17701 - - - - - Effect of ambient temperature AC-breaker are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or higher ambient temperature, use a correction factor from the table below: Ambient temperature [°C] Correction factor AC version Correction factor DC version -20 0.78 0.80 -5 0.82 0.87 0 0.83 0.90 +10 0.87 0.95 +23 0.91 1.00 +30 0.95 1.05 +40 1.00 1.10 +50 1.05 1.20 +60 1.11 1.30 Example DC version: Rated current = 10 A; Environmental temperature = 50 °C; --> Correction factor = 1.2; Resulting current = 12 A

Thermal-magnetic (TM and AS-line) AS168XAC1www.schurter.com /PG20 Circuit Breakers Horsepower (FLA & LRC Ratings Apply where no HP Rating is given) Nominal Circuit Voltage, VACAS168X-CB Motor Nameplate 110- 120 2002 08 220- 240 265 277 380- 415 440- 480 Rated Current (See Note #1) FLA Rating Starting/ LRC Rating 2 pole1 pole 0.5A 0.5A 1A 1A 1.5A 1.5A 2A 2A 3A 3A 4A 4A 5A 5A 6A 6A 7A 7A 8A 8A 9A 9A 10A 10A 12A 12A 13A 13A 15A 15A 16A 16A 18A 18A 20A 20A 23A 23A 25A 25A 27A 27A 30A 30A AS168X-CB Nominal Circuit Voltage, VAC 110-120 2002 08 220-240 380-415 440-480 Rated Current (See Note #1) Note #1: For AC motor circuit nameplate FLA loads, AC general-use loades, AC resistance loads FLA Starting/ 3 pole 0.5A 0.5A 1A 1A 1.5A 1.5A 1/2 2A 2A 3/4 3A 3A 1 1/2 4A 4A 2 5A 5A 3 6A 6A 3 7A 7A 3 8A 8A 5 9A 9A 5 10A 10A 5 12A 12A 7 1/2 13A 13A 7 1/2 15A 15A 10 16A 16A 10 18A 18A 10 20A 20A 10 23A 23A 15 25A 25A 15 27A 27A 20 30A 30A 20 Motor Nameplate Horsepower (FLA & LRC Ratings Apply where no HP Rating is given) Rating LRC Rating 10A 1/2 12.5A 3/4 20A 1/2 1/2 1/2 1 25A 3/4 3/4 3/4 1 1/2 32A 1/2 1 1 1 2 32A 1/2 1 1 1/2 2 32A 3/4 1/2 1/2 2 3 46A 3/4 2 2 2 3 46A 1 2 2 2 3 46A 1 2 2 3 5 63.5A 1 1/2 3 3 3 5 63.5A 1 1/2 3 3 3 5 81A 2 3 3 3 7 1/2 81A 2 3 3 5 7 1/2 81A 2 5 5 5 10 81A 3 5 5 5 10 116A 3 5 5 7 1/2 10 116A 3 5 7 1/2 7 1/2 10 145A 3 7 1/2 7 1/2 7 1/2 15 145A 3 7 1/2 7 1/2 10 15 6° 1/10 9° 1/10 1/10 1/10 1/6 12A 1/8 1/6 1/6 1/4 18A 1/10 1/6 1/6 1/4 1/4 1/3 1/3 1/2 24A 1/8 1/4 1/3 1/3 1/3 1/3 1/2 1 30A 1/6 1/3 1/3 1/2 1/2 1/2 3/4 1 1/2 36A 1/4 1/2 1/2 1/2 3/4 3/4 1 2 42A 1/4 1/2 1/2 3/4 1 1 1 1/2 2 48A 1/3 3/4 3/4 1 1 1 2 2 54A 1/3 3/4 1 1 1 1 1/2 2 3 60A 1/2 1 1 1 1/2 1 1/2 2 2 3 72A 1/2 1 1/2 1 1/2 2 2 2 3 3 78A 1/2 1 1/2 1 1/2 2 2 2 3 3 90A 3/4 2 2 2 3 3 3 5 96A 1 2 2 2 3 3 3 5 108A 1 2 2 3 3 3 5 5 120A 1 1/2 3 3 3 3 3 5 5 138A 1 1/2 3 3 3 3 3 5 7 1/2 150A 2 3 3 3 5 5 5 7 1/2 162A 2 3 3 3 5 5 7 1/2 10 180A 2 3 3 5 5 5 7 1/2 10

Thermal-magnetic (TM and AS-line)AS168XAC1 www.schurter.com /PG20 Circuit Breakers Time-Current-Curves Version F / Magnetic 3-5 xln Time in Seconds 11 0 100 1000 x In 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Multiple of Rated Current In Reference Temperature +23° Version G / Magnetic 6-10 xln Time in Seconds 11 0 100 1000 x In 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Multiple of Rated Current In Reference Temperature +23° Version H / Magnetic 12-20 xln Time in Seconds 11 0 100 1000 x In 0,1ms 1ms 10ms 0,1s 10s 100s 1000s 1hr Multiple of Rated Current In Reference Temperature +23° Config. Code The characters are placeholders for the correspondingly keys of selections from the key tables. AS168X-CB| 1 |DG|200|N| = Number of Poles Number of Poles Configuration key 1-pole 1

Thermal-magnetic (TM and AS-line) AS168XAC1www.schurter.com /PG20 Circuit Breakers AS168X-CB|1| DG |200|N| = Tripping characteristics Tripping characteristics Configuration key 1.0-1.25xIn / 3-5xIn / 0.5-52 A F 1.0-1.25xIn / 6-10xIn / 0.5-52 A G 1.0-1.25xIn / 12-20xIn / 0.5-52 A H AS168X-CB|1|DG| 200 |N| = Rated current Rated current Configuration key

0.05 A 005

1.0 A 010

1.5 A 015

2.0 A 020

3.0 A 030

4.0 A 040

5.0 A 050

6.0 A 060

7.0 A 070

8.0 A 080

9.0 A 090

10.0 A 100

Other rated currents on request Rated current Configuration key

12.0 A 120

15.0 A 150

16.0 A 160

18.0 A 180

20.0 A 200

23.0 A 230

25.0 A 250

27.0 A 270

30.0 A 300

32.0 A 320

35.0 A 350

40.0 A 400

45.0 A 450

50.0 A 500

52.0 A 520

Other rated currents on request AS168X-CB |1|DG|200| N | = Switched neutral Switched neutral Configuration key Switched neutral pole N Variants Tripping characteristics Rated current Switched neutral Config. Code Order Number

Thermal-magnetic (TM and AS-line)AS168XAC1 www.schurter.com /PG20 Circuit Breakers Tripping characteristics Rated current Switched neutral Config. Code Order Number █ Most Popular. Availability for all products can be searched real-time:http://www.schurter.com/Stock-Check/Stock-Check-SCHURTER Packaging Unit 1 Pcs The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 13.10.2016