4420.0163 SCHURTER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
Thermal-magnetic (TM and AS-line) AS168X Add-on moduleshttps://www.schurter.com /PG20 Circuit Breakers Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic Auxiliary contact Signal contact Relay trip module See below: Approvals and Compliances
Description
- DIN-Rail Mounting - Auxiliary contact module Each auxiliary contact module contains one contact, either normally open or normally closed - Signal contact module Signal contact modules are linked internally with the protected poles but not linked at the handles. Contacts are actuated by a fault condi- tion at the protected poles, not by manual operation of the CBE - Relay trip module The relay trip module can be used for remote tripping of the adjacent poles by applying a voltage to the module's terminal
Applications
- Industrial appliances References Last order possibility: 31.08.2018 Last delivery date: 30.09.2018 Weblinks pdf datasheet, html-datasheet, General Product Information, Distributor- Stock-Check, Detailed request for product, Product News Technical Data Ratings AC 277 V / 6 A (50/60 Hz) ␣ DC 125 V / 1 A ␣ DC 50 V / 6 A Conditional short circuit ca- pacity IEC: Inc, PC1, AC 277 V: 1 kA Dielectric Strength 50 Hz: > 2 kV Impulse 1.2/50 μs Insulation Resistance > 5 MΩ Endurance typical mechanical: 50000 switching cycles ␣ IEC 60947-5-1 AC : 10 x Ir , p.f. = 0.3 : DC : 1 x Ir , L/R = 0.3 s : 6050 switching cycles 6000 switching cycles Overload AC: min. 10 trips ␣ DC: min. 50 trips @ 1.1 x Ir, L/R = 0.3 s Ambient temperature -20 °C to 60 °C Vibration Resistance ± 0.75 mm @ 10 - 60 Hz acc. to IEC 60068-2-6, test Fc
10 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc Shock Resistance 30 G / 18 ms acc. to IEC 60068-2-27, test Ea Degree of Protection from front side IP 20 acc. to IEC 60529 Weight 22 - 49 g Approvals and Compliances Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals Approvals The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products. Approval Reference Type: AS168X Approval Logo Certificates Certification Body Description VDE Approvals VDE VDE Certificate Number: 40021845 UL Approvals UL UL File Number: E216629 / E71572 UL Approvals UL UL File Number: E216629 / E71572
Thermal-magnetic (TM and AS-line)AS168X Add-on modules https://www.schurter.com /PG20 Circuit Breakers Product standards Product standards that are referenced Organization Design Standard Description Designed according to IEC 60947-5-1 Circuit-breakers for equipment (CBE) Designed according to UL 508 Standard for Supplementary Protectors for Use in Electrical Equipment Designed according to UL 508 Standard for Industrial Control Equipment Designed according to CSA C22.2 Supplementary Protectors Application standards Application standards where the product can be used Organization Design Standard Description Designed for applications acc. IEC/UL 60950 IEC 60950-1 includes the basic requirements for the safety of information technologyequipment. Compliances The product complies with following Guide Lines Identification Details Initiator Description CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. RoHS SCHURTER AG EU Directive RoHS 2011/65/EU China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. Dimension [mm] AS168X-ACBH. AS168X-ACBS. AS168X-ACBA. 17.5 17.5 +0.5 -0.0 17.5 +0.5 -0.0 +0.5 -0.0
Thermal-magnetic (TM and AS-line) AS168X Add-on moduleshttps://www.schurter.com /PG20 Circuit Breakers 35.7 75.6 44.4 61.6 68.4 5.1A) 26.4 37.1 8.75 +0.5 -0.0 AS168X-Auxiliary contact A) 35 mm DIN rail EN 50022 Diagrams PHASE-OUT
Thermal-magnetic (TM and AS-line)AS168X Add-on modules https://www.schurter.com /PG20 Circuit Breakers Approvals Relay trip module Symbol Standard Rated voltage AC Rated voltage DC UL 508 CSA C22.2 no. 14 - - UL 1077 up to 277 V up to 240 V CSA C22.2 no. 235 - - EN 60934 - - GB 17701 - - Approvals Auxiliary contact Symbol Standard Rated current AC Rated voltage AC Rated current DC Rated voltage DC UL 508 CSA C22.2 no. 14
6 A 277 V 1 A
CSA C22.2 no. 235 - - - - EN 60934 6 A (Ac-15) 277 V 1 A (DC-12)
0.5 A (DC-13)
6 A (DC-12)
Symbol Standard Rated current AC Rated voltage AC Rated current DC Rated voltage DC UL 508 CSA C22.2 no. 14 CSA C22.2 no. 235 - - - - EN 60934 6 A (AC-15) 277 V 1 A (DC-12) Functional auxiliary contact Type H1 assumes the same contact position Type H2 assumes the opposite position Actuation of the contact is determined by the condition of the handle position of the adjacent poles. Functional signal contact Type S1 assumes the same contact position Type S2 assumes the opposite position The signal contact operates due to a thermal magnetic tripping and must be reset by hand. Function of relay trip module Type Voltage range AC/DC 5 - 12 V 10 - 24 V 20 - 48 V 40 - 110 V 90 - 240 V Impedance at 50 Hz 1.1 Ω 4.7 Ω 16 Ω 63 Ω 395 Ω When voltage is applied across the terminals, remote tripping takes place by a self interrupting magnetic system. Trip delay time 8 - 16 ms. Maximum Pole combination The maximum allowed number of poles/modules is 6, but in any combination, only 1 or 2 add-on modules are permitted 1 or 2 add-on modules only 1 add-on module 1 or 2 add-on modules + 1 or 2 or 3 pole + 4 pole + 4 pole + switched neutral + switched neutral The time-current-curves are not relevant for the add-on modules.
Thermal-magnetic (TM and AS-line) AS168X Add-on moduleshttps://www.schurter.com /PG20 Circuit Breakers Config. Code The characters are placeholders for the correspondingly keys of selections from the key tables. AS168X-ACB| H1 |S2|A3|LOA| = Auxiliary contact Auxiliary contact Configuration key Auxiliary contact synchronized H1 Auxiliary contact opposited H2 AS168X-ACB|H1| S2 |A3|LOA| = Signal contact Signal contact Configuration key Signal contact synchronized S1 Signal contact opposited S2 AS168X-ACB |H1|S2| A3 |LOA| = Relay trip module Relay trip module Configuration key Relay trip module AC/DC 5 -12 V A1 Relay trip module AC/DC 10 -24 V A2 Relay trip module AC/DC 20 - 48 V A3 Relay trip module AC/DC 40 -110 V A4 Relay trip module AC/DC 90 -240 V A5 AS168X-ACB |H1|S2|A3| LOA | = Relay trip module Accessories Configuration key Lockout attachment LOA Variants Auxiliary contact Signal contact Relay trip module Accessories Config. Code Order Number Auxiliary contact synchronized AS168X-ACBH1 4420.0163 Auxiliary contact opposited AS168X-ACBH2 4420.0176 Relay trip module AC/DC 20 - 48 V AS168X-ACBA3 4420.0189 Relay trip module AC/DC 10 -24 V AS168X-ACBA2 4420.0340 Signal contact synchronized AS168X-ACBS1 4420.0414 Signal contact opposited AS168X-ACBS2 4420.0415 Lockout attachment AS168X-ACBLOA 4420.0799 Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER Packaging Unit 1 Pcs The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 19.02.2018 PHASE-OUT