T9-211_V02 SCHURTER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Thermal (T- and TA-Line) T9-211https://www.schurter.com /PG17_18_19 Circuit Breakers Circuit Breaker for Equipment thermal, Threaded-neck type, 1 pole See below: Approvals and Compliances
Description
- Threaded neck type - Thermal circuit breaker - 1-pole - On request available with elevaled glow-wire ratings - Quick connect terminals 6.3 x 0.8 mm Unique Selling Proposition - Reset type - Cycling trip-free release - Compact design - Different mounting possibilities
Applications
- Power supplies - Uninterruptible power supply - Power tools - Industrial appliances - HVAC - Household appliances Weblinks pdf data sheet, html datasheet, General Product Information, Distributor- Stock-Check, Detailed request for product, Product News Technical Data Rated Voltage AC 240 VAC Rated Voltage DC 48/32 VDC Rated current 3-16 A, see approbations Conditional short circuit capa- city Inc IEC 60934: PC1, AC 240 V: 2 kA UL / CSA: SC, AC 240 V DC 48 / 32 V: 2 kA, C1 Degree of protection front side IP40 Endurance minimum IEC: 200% Ir, cos φ 0.6: min. 50 swit- ching cycles Endurance typical 3-8 A: 150% Ir, cos φ 0.9: 2500 switching cycles ␣ 10-16 A: 150% Ir, cos φ 0.9: 6000 switching cycles Dielectric Strength 1500 VAC Insulation Resistance 500 VDC > 1000 MΩ Allowable Operation Temp. 3 A: -5 °C to 60 °C
4 A: -5°C to 50 °C
5-16 A: -5 °C to 60 °C Weight 9 - 13 g Approvals and Compliances Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF 16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree- ments by SCHURTER. Approvals The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products. Approval Reference Type: T9 Approval Logo Certificates Certification Body Description VDE Approvals VDE VDE Certificate Number: 40038016 UL Approvals UL UR File Number: E71572 CCC Approvals CCC CCC Certificate Number: 2020970307003348
Thermal (T- and TA-Line)T9-211 https://www.schurter.com /PG17_18_19 Circuit Breakers Product standards Product standards that are referenced Organization Design Standard Description Designed according to IEC 60934 Circuit-breakers for equipment (CBE) Designed according to UL 1077 Standard for Supplementary Protectors for Use in Electrical Equipment Designed according to CSA C22.2 No. 235 Supplementary Protectors Designed according to GB 17701 Circuit-breaker for equipment Application standards Application standards where the product can be used Organization Design Standard Description Suitable for applications acc. IEC/UL 62368-1 Audio/video, information and communication technology equipment - Part 1: Safety requirements Compliances The product complies with following Guide Lines Identification Details Initiator Description CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. UKCA declaration of conformity SCHURTER AG The UKCA marking declares that the product complies with the applicable requirements laid down in the British Amendment of Regulation (EC) 765/2008. RoHS SCHURTER AG Directive RoHS 2011/65/EU, Amendment (EU) 2015/863 China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. Dimension [mm] T9-211/311 36.110.4ø 15.4 10 19 58 3/8" -27UNS6.3x0.8 ±0.2 ±0.213.6 8.6 SW14 Pannel thickness 0.8 - 5.5 mm 1) max. torque: 0.6Nm 8.909.6 9.6 +0.10 0.00 Hexagonal nut TZZ12 / TZZ51 3/8" -27UNS 2.5 SW 14 Cover TZZ31für IP65 optional, see accessory 13.6
Thermal (T- and TA-Line) T9-211https://www.schurter.com /PG17_18_19 Circuit Breakers Approval Rated current Rated Voltage AC Rated Voltage DC UL 1077 3 - 12 A 14 - 16 A 240 V 240 V 48 V 32 V CSA 22.2 235 3 - 12 A 14 - 16 A 240 V 240 V 48 V 32 V IEC 60934 3 - 12 A 14 - 16 A 240 V 240 V 48 V 32 V GB 17701 3 - 12 A 14 - 16 A 240 V 240 V 48 V 32 V Typical internal resistance per pole Rated Current [A] Internal Resistance [mΩ] 3 65.0 4 21.6 5 23.6 6 16.3 7 15.3 8 12.9 10 7.3 12 7.0 14 4.8 15 4.3 16 3.9 Time-Current-CurvesTime in Seconds 23 4516 78 10 [min] [sec] 10'000 1'000 100 0.1
5 A -16 A (TC-1)
4 A (TC-2)
1.05 1.35 1.45 Multiple of Rated Current In Ambient temperature +23° Time in Seconds 23 4516 78 10 [min] [sec] 10'000 1'000 100 0.1
3 A (TC-2)
1.05 1.5 Multiple of Rated Current In Ambient temperature +23°
Thermal (T- and TA-Line)T9-211 https://www.schurter.com /PG17_18_19 Circuit Breakers Effect of ambient temperature The units are calibrated for an ambient temperature of +23°C. To determine the rated cur- rent for a lower or higher ambient temperature, use a correction factor (typical value) from the table below: Ambient Temperature [°C] Correction factor -5 0,85 +10 0,95 +23 1,00 +40 1,08 +60 1,21 Example: Rated current = 10 A, Environmental temperature = 60 °C, --> Correction factor = 1.21, Resulting current = 12.1 A --> Round to next higher rated current: 13 A Accessories Part Number Type Resources / Description
4404.0039 TZZ31 Protection cover for IP65
4400.0420 TZZ11 Knurled nut nickel-plated
4400.0559 TZZ11-414 Knurled nut black
4400.0425 TZZ12 Additional hexagonal nut nickel-plated
4404.0072 TZZ51 Additional hexagonal nut PA 66
Mounting Front printing Rated current Order Number Threaded neck short Rated current not printed on front 3.0 A 4404.0084 Threaded neck short Rated current not printed on front 4.0 A 4404.0083 Threaded neck short Rated current not printed on front 5.0 A 4404.0082 Threaded neck short Rated current not printed on front 6.0 4404.0081 Threaded neck short Rated current not printed on front 7.0 A 4404.0080 Threaded neck short Rated current not printed on front 8.0 A 4404.0079 Threaded neck short Rated current not printed on front 10.0 A 4404.0078 Threaded neck short Rated current not printed on front 12.0 A 4404.0077 Threaded neck short Rated current not printed on front 14.0 A 4404.0076 Threaded neck short Rated current not printed on front 15.0 A 4404.0075 Threaded neck short Rated current not printed on front 16.0 A 4404.0074 Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER Packaging Unit 100 Pcs The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 08.06.2022