43DV2 MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 7
Technical content
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 1/7 https://www.m-system.co.jp/ Digital Panel Meters 43 Series DC INPUT DIGITAL PANEL METER (process meter) Functions & Features
- -1999 to +9999 digital panel meter
- Scaling & Hold functions available
- Screwless spring terminal (.94) 48 (1.89) 58 (2.28)* mm (inch) *42 (1.65) for Terminal Block code "S" MODEL: 43DV2–[1][2]–R[3]
ORDERING INFORMATION
- Code number: 43DV2–[1][2]–R[3] Specify a code from below for each of [1] through [3]. (e.g. 43DV2-SAD-R/Q)
- Specify the specification for option code /Q (e.g. /SET) [1] INPUT DC Voltmeter (Without scaled range) V1: ±199.9 mV DC (Conformance range) (Input range: -219 – +219 mV, Input resistance: ≥1 MΩ) V2: ±1.999 V DC (Conformance range) (Input range: -2.19 – +2.19 V, Input resistance: ≥1 MΩ) V3: ±19.99 V DC (Conformance range) (Input range: -21.9 – +21.9 V, Input resistance: ≥1 MΩ) Process Meter S4: 0 – 10 V DC (Conformance range) (Input range: -1 – +11 V, Input resistance: ≥1 MΩ) S5: 0 – 5 V DC (Conformance range) (Input range: -0.5 – +5.5 V, Input resistance: ≥1 MΩ) S6: 1 – 5 V DC (Conformance range) (Input range: 0.6 – 5.4 V, Input resistance: ≥1 MΩ) S0: Specify voltage (See INPUT SPECIFICATIONS) SA: 4 – 20 mA DC (Conformance range) (Input range: 2.4 – 21.6 mA, Input resistance: 20 Ω) SB: 0 – 20 mA DC (Conformance range) (Input range: -2 – +22 mA, Input resistance: 20 Ω) SC: 0 – 10 mA DC (Conformance range) (Input range: -1 – +11 mA, Input resistance: 40.2 Ω) SG: 0 – 1 mA DC (Conformance range) (Input range: -0.1 – +1.1 mA, Input resistance: 402 Ω) SJ: 0 – 5 mA DC (Conformance range) (Input range: -0.5 – +5.5 mA, Input resistance: 80.6 Ω) SZ: Specify current (See INPUT SPECIFICATIONS) [2] TERMINAL BLOCK S: Screwless spring terminal D: Separable screwless spring terminal POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-9422) GENERAL SPECIFICATIONS Construction: Panel flush mounting Connection Terminal block "S": Screwless spring terminal Applicable wire size 1.0 to 1.3 mm2, stripped length 8 mm Terminal block "D": Separable screwless spring terminal Applicable wire size 1.0 to 1.3 mm2, stripped length 8 mm Housing material: Flame-resistant resin (gray) Isolation: Input to power A/D conversion: Σ – Δ Sampling rate: 5 times/sec. (200 msec.) Averaging: None or moving average Setting: (Front button)
- Scaled range (Process meter)
- Calibration (DC Voltmeter)
- Moving average
- Brightness
- Others DISPLAY Display: 4 digits of 10.2 mm (.4”) height, 7-segment, red LED Display range: -1999 to 9999 Zero indication: Higher-digit zeros are suppressed. ■DC Voltmeter Over-range indication: 'S.ERR' blinks when out of the input range.
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 2/7 https://www.m-system.co.jp/ ■Process meter Scaling range for measurement range (conformance range): -1999 to 9999 counts Decimal point position: 10-1, 10-2, 10-3 or none Over-range indication: '-1999' or '9999' blinking for display values out of the display range. 'S.ERR' blinks surpassing the permissible range. Engineering unit indication: Sticker label attached DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min, cm/min, m/min, m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec, m3/min, m3/h, Nm3/h, N·m, N/m2, g, kg, kg/h, N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J, kJ, MJ, rpm, sec, min, pH, %, ppm, etc. INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated Input resistance: 5 - 250 [Ω]* Conformance range: 0 – 50 mA DC Minimum span: 1 mA Operational range: -10 - +110 % of input span * Calculated as follows; Input resistance [Ω] = 250 ÷ Input current at 100 % [mA] ■ DC Voltage Input resistance: ≥ 1 MΩ Input range: 0 – 19.99 V DC Minimum span: 0.1 V Operational range: -10 - +110 % of input span ■ Hold Input: Dry contact input Detecting level: ≤ 0.8 V Sensing: Approx. 2.1V DC, 0.03 mA INSTALLATION Power consumption: Approx. 0.15 W Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Panel flush mounting Weight: 40 g (1.4 oz) PERFORMANCE Accuracy
- DC Voltmeter: ±0.1 % rdg ±1 digit
- Process meter: ±0.1 % rdg ±1 digit × scaling-multiple (When the scaling-multiple is less than 1, rounded up to 1.) Temp. coefficient
- DC Voltmeter: ±(0.01 % rdg + 0.3 digits)/℃
- Process meter: ±(0.01 % rdg + 0.3 digits × scaling-multiple)/℃ (When the scaling-multiple is less than 1, rounded up to 1.) Scaling-multiple = | (Display Scaling Value B - Display Scaling Value A) ÷ (default Display Scaling Value B - default Display Scaling Value A) | Line voltage effect: ±1 digit over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1000 V AC @1 minute (input to power to ground) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 3/7 https://www.m-system.co.jp/ DISPLAY HOLD COMMAND Displayed value is held with an external HOLD command input. Connect the contacts across HOLD to COM. ■WIRING EXAMPLES L HOLD H Twisted pair cable L HOLD H L HOLD H L HOLD H Twisted pair cable Twisted pair cable COM COM (b) Transistor (a) 5V–CMOS, TTL (c) Photo-Coupler (d) Relay Relay Photo-Coupler HOLD Terminals 3 and 4 are NOT isolated from the internal circuit.
4 HOLD
4 HOLD 3
(1) Front Cover (2) 4-digit Display (6) UP Button (5) SF Button (3) DI Button (4) SC Button ■ COMPONENT IDENTIFICATION No. COMPONENT FUNCTION (1) Front Cover Removed at con/f_iguration. (2) 4-digit Display 4-digit LED display. Range: -1999 to 9999 (not including decimal point) (3) DI Button Used to move on to the display setting mode; or to shift through setting items in each setting mode. (4) SC Button Used to move on to the scaling setting or calibration mode; or to shift through setting items in each setting mode. (5) SF Button Used to move on to the setting standby status and shift through display digits in each setting item. (6) UP Button Used to select setting value.
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 4/7 https://www.m-system.co.jp/ PARAMETER LIST ■ SCALING SETTING MODE (Process meter, applicable to input code Sx only) ... ... PARAMETER S0 *2 SA SB SC SG SJ SZ SA SB SC SG SJ SZ SA SB SC SG SJ SZ Display Scaling Value A Display Scaling Value B Decimal Point Position *1 . 0% input and 100% input mean the default values according to the input code. *2. Specified value 10 -1 through 10-3 or none Decimal point position Display value for 100% input *1 Display value for 0% input *1 To distinguish from B, the first decimal point is blinking. FUNCTION DEFAULT VALUE MEASURING RANGE DISPLAY A 0% 100% 0% 100% B Display Input Display Scaling B A Display Input Display Scaling
- Normal Scaling The display value increases when the input signal increases.
- Inverted Scaling The display value decreases when the input signal increases. The decimal point position can be set to any digit. Set it according to the 100% value.
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 5/7 https://www.m-system.co.jp/ ■ CALIBRATION MODE (Only for DC Voltmeter, applicable to input code V1, V2, V3) PARAMETER 0% Calibration 100% Calibration Calibrates 100% input 50% Calibration Calibrates 50% input Calibrates 0% input FUNCTION DEFAULT VALUE Factory Calibration DISPLAY ■ DISPLAY SETTING MODE PARAMETER Moving Average Brightness Initialization Non-initialization Brightness level 1 (dark) Moving average with 2 samples Brightness level 4 Brightness level 5 (bright) Brightness level 3 Brightness level 2 No moving averaging FUNCTION DEFAULT VALUE DISPLAY Initialize settings (change to factory settings) *1 Version Indication Version number, indication only – – Moving average with 4 samples Moving average with 8 samples Moving average with 16 samples *1 . While “ ” is shown, pressing DI button or SC button initializes settings. If “Initialization” is done once, all current parameters will be deleted and overwritten with factory default values. Notice that after this, Ex-factory settings with “/SET” option will be irrecoverable.
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 6/7 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 22 (.87) 35 (1 .38) 17 (.67) for Separable terminal5.5 (.22) 45 (1 .77) 48 (1 .89) 24 (.94) 50.5 (1 .99)
- Separable terminal • One block terminal
- Separable terminal • One block terminal Separable screwless spring terminal Screwless spring terminal 1 .5 (.06) for One block terminal ■ FRONT VIEW ■ SIDE VIEW ■ REAR VIEW ■ TOP VIEW
MODEL: 43DV2 43DV2 SPECIFICATIONS ES-9422 Rev.11 Page 7/7 https://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm + 0.6 – 0 22.2 + 0.3 – 0 min. 65 min. 35 Panel thickness: 0.8 to 3.5 mm ■ PANEL CUTOUT unit: mm MOUNTING Just insert the meter body (snap-in method) SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM COM HOLD Digital Computation A/D Converter POWER INPUT Display / Setting * + *Input shunt resistor attached for current input. Specifications are subject to change without notice.