Technical content
Features
- Three (411) or four (411UD) monitoring channels (inputs).
- Inputs may be individually programmed to monitor the host control panel for: Fire alarm, fire trouble, fire supervisory, process monitoring, AC power loss, security alarm and other (fire and non-fire events).
- Fully supervised trigger inputs require a contact closure for activation.
- 12- or 24-VDC operation, jumper-selectable.
- Industry-first, UL recognized," dialer-run- away" prevention feature.
- Dual-line rotary- or Touch-Tone®-dial DACT interfaces to public switched telephone network (leased phone lines are not required).
- Includes 15 reporting formats, including the popular ADEMCO Contact ID format.
- Capable of transmitting the following DACT information, in addition to vital system status of the host control panel: DACT troubles, telephone line 1 and 2 voltage fault, primary or secondary Central Station communication fault, system off- normal, 24-hour normal test and 24-hour abnormal test.
- New long-distance Carrier Access Code (CAC) compliant, accepting up to 20-digit Central Station telephone numbers.
- Fully programmable transmittal codes for fire, security, process monitoring, and others.
- Field-programmable utilizing PRO-411 hand- held programmer.
- Programmable from remote site with optional PK-CD programming software (model 411UD only). Features continued on page 2. 411/411UD Slave Digital Alarm Communicator Transmitter Listings Listings and approvals below apply to the basic 411/411UD communicator/ transmitter. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: file S2424.
- CSFM approved: file 7300-0075:174.
- MEA approved: file 328-94-E Vol. III Vol. VI (411UDAC). g2508ph1.jpg
411/411UD CS-2508 APage 2 of 4 Diagnostic LEDs Communication Fail (visible with front cover in place). DACT Trouble (visible with front cover in place) (411UD). Channel Active (visible with front cover in place) (411UD). Primary Phone Line Active (411UD). Secondary Phone Line Active (411UD). Modem Active (411UD).
Ordering Information
411 Three-channel, dual-line, slave Digital Alarm Communica-
tor Transmitter. Includes housing, operating and pro- gramming instructions. Requires PRO-411 hand-held DACT programmer for local programming. 411UD Same as above with four input channels, Form-C pro- grammable relay, silence switch and remote upload/ download capability. Requires PRO-411 hand-held DACT programmer for local programming or PK-CD Windows- based programming software for remote programming and real-time diagnostics. PRO-411 Hand-held programmer for local programming of 411 Series DACTs. PK-CD Remote upload/download, Windows ® compatible pro- gramming software kit (for use with PK-Series only). MCBL-7 DACT phone cord, seven feet long (two required). Windows® is a registered trademark of Microsoft Corporation.
- View 411 Series status offsite in real time, with optional PK-CD programming software, without ever compromising monitoring protection at the protected premises (model 411UD only).
- Integral piezo sounder (both models) with local silence switch (model 411UD only).
- One Form-C relay, fully programmable (model 411UD only).
- Complies with NFPA 72 — 1996 edition (Central Station and Remote Station [DACT only— not polarity reversal] Fire Alarm Systems).
- Surface Mount Technology (SMT).
- Extremely compact enclosure, measuring only 6.75" (17.145 cm) W x 4.40" (11.176 cm) H x 1.05" (2.667 cm) D. Specifications: 411UD Listings and Approvals: NFPA 72 Central Station Fire Alarm Systems, NFPA 72 Remote Station Fire Alarm Systems. UL Standard 1635 Digital Alarm Communicator/Transmitters, UL Standard 864 Control Units for Fire Alarm Systems. FCC Registration: OAAUSA-25431-AL-E. Ringer Equivalence: 0.5 B. For Canadian Applications: IC Certificate Number: 2132 9028 A. Ringer Equiva- lence Number (REN): 0.2. Programming: A digital programming unit with a keypad, model PRO-411. is available for programming the 411 Series. Operating Power: The 411UD circuit board operates on filtered 12 VDC. The configura- tion of Jumper J4 determines whether 12 VDC power is to be supplied directly to the circuit board, or 24 VDC power is to be supplied and then internally regulated down to 12 VDC. DC Power:
- J4 Jumper REMOVED: Filtered, nonresettable and power-limited 24 VDC (nominal) power must be supplied at TB1 Terminals 7(+) and 8(–). Current require- ments are 100 mA in standby and 170 mA* while communicating.
- J4 Jumper INSTALLED: Filtered, nonresettable and power-limited 12 VDC (nominal) power must be supplied at TB1 Terminals 7(+) and 8(–). Current require- ments are 100 mA in standby and 170 mA* while communicating. *NOTE: A maximum of 300 mA is possible with all channels active, the 411UD communicating, the PRO-411 connected, and Lamp Test active . Features continued... Specifications continued on page 4.
411/41UD CS-2508 A Page 3 of 4 Compatible UL-Listed Receivers The chart below shows UL-listed receivers compatible with 411 Series products: KEY: (1) With 685-8 Line Card with Rev 4.4d software. (2) With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A software. (3) Rev. 4.0 software. (4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a memory card with Rev 3.8 software. (5) Model 6500 with Rev 600 software. (6) Model 6000 with Rev 204 software. (7) With Rev B control card at Rev 1.4 software and Rev C line card at Rev 1.5 software. (8) Model 2 only. (9) Version 1.62 software. Format # (addresses 16 & 42) Ademco 685 (1) Silent Knight 9000 ITI CS4000 (3) FBI CP220FB Osborne Hoffman Models 1 & 2 Radionics (5) Sescoa 3000R (7) SurGuard MLR-2 (9) 0 4+1 Ademco Express 1 4+2 Ademco Express (8) E Ademco Contact ID 51735rec.tbl
411/411UD CS-2508 APage 4 of 4 Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2009 Gamewell-FCI Channels/Inputs:**
- Programmable Channels 1 through 4.
- Power-limited circuitry.
- Fully supervised.
- Operation: All channels NFPA Style B (Class B). Requires Normally Open contact to trigger.
- Normal operating voltage: 12 VDC.
- Alarm current: 3.34 mA.
- End-of-line resistor: 2.2K ohms.
- Short-circuit current: 3.8 mA per channel/ input. **NOTE: Channels/inputs do NOT support two-wire smoke detectors. Form-C Relay:
- Contact rating: 2.0 amps @ 30 VDC (resistive). Specifications: 411 FCC Registration: OAAUSA-25431-AL-E. Ringer Equivalence: 0.5 B. For Canadian Applications: IC Certificate Number: 2132 9028 A. Ringer Equivalence Number (REN): 0.2. Programming: A digital programming unit with a keypad, model PRO-411, is available for programming the 411 Series. Operating Power: The 411 may be powered from UL-listed control panels that output nonresettable and power-limited 12 or 24 VDC power. The configuration of Jumper J4 determines whether 12 VDC power is to be supplied directly to the 411 circuit board, or
24 VDC power is to be supplied and then
internally regulated down to 12 VDC. DC Power: TB1 Terminals 1(+) and 2(–); Terminal 3 is Earth Ground.
- J4 Jumper removed: nonresettable, and power-limited 24 VDC (nominal) power must be supplied at TB1 Terminals 1(+) and 2(–). Operating voltage provided must be within 21.3 to 24.0 VDC (UL tested range: –15%, +10%). Current requirements are 78 mA in standby and 126 mA* while communicating.
- J4 Jumper installed: Filtered, nonresettable, and power-limited 12 VDC (nominal) power must be supplied at TB1 Terminals 1(+) and 2(–). Operating voltage must be within 11.2 to 12.4 VDC (UL tested range: –15%, +10%). Current requirements are 78 mA in standby and 126 mA* while communicating. *NOTE: A maximum of 240 mA is possible with all input channels active, the 411 communicating, the Programmer connected, and Lamp Test active. Channels/Inputs** — TB2 Terminals 1 through 6:
- Programmable Channels 1 through 3.
- Power-limited circuitry.
- Fully supervised.
- Operation: All channels NFPA Style B (Class B). Requires Normally Open contact to trigger.
- Normal operating voltage: 12 VDC.
- Maximum line resistance: 100 ohms per channel.
- Alarm current: 3.34 mA.
- End-of-line resistor: 2.2K ohms, 1/2 watt (P/N 27070).
- Short circuit current: 3.8 mA per channel/ input. **NOTE: Channels/inputs do NOT support two-wire smoke detectors. Specifications: 411 continued...