3X0 VERIS | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 2

Technical content

Power Requirements Loop input voltage 9 to 35 Vdc Input Frequency 0.4 Hz to 10 kHz Load Resistance Max 750 Ω @ 24 Vdc Operating Temp Range -29 to 70 °C (-20 to 158 °F) Storage Temp Range -40 to 85 °C (-40 to 185 °F) Accuracy ±0.04% of reading over entire span Linearity 0.1% of full scale WARRANTY Limited Warranty 1 year Power Requirements 12 to 24 Vac 85 mA max.; 12 to 35Vdc, 30 mA max.; reverse and over voltage protected to 40 Vdc Input Frequency 0.4 to 10 kHz Transient Suppression Complies with IEC-801-4 electrical burst, fast transient specification Pulse Output Isolated solid state switch in any standard or custom flow total units; adjustable 50 ms to 1.0 sec pulse output width in 50 ms increments Maximum Sinking Current 100 mA @ 35 Vdc Operating Temp Range -29 to 70 °C (-20 to 158 °F) Storage Temperature Range -40 to 85 °C (-40 to 185 °F) WARRANTY Limited Warranty 1 year Power Requirements 12 to 24 Vdc or 12 to 24 Vac, 70 mA max. Flow Sensor Input Excitation voltage 3-wire sensors: 9.1 Vdc 500Ω source impedance Frequency 4 to 10000 Hz Temp Sensor Input 10k Dale Thermistor (requires two, sold sepa- rately) Operating Temp Range -29 to 70 °C (-20 to 158 °F) Storage Temp Range -40 to 85 °C (-40 to 185 °F) UNITS OF MEASURE Flow Rate gpm, gph, l/sec, l/min, l/hr, ft3/sec, ft3/min, ft3/ hr, m3/sec, m3/min, m3/hr Total Flow gallons, liters, cubic feet, cubic meters Energy Rate kBTU/min, kBTU/hr, kW, MW, hp, tons Total Energy BTU, kBTU, MBTU, kWh, MWh, kJ, MJ WARRANTY Limited Warranty 1 year 3x0 programmable transmitters are capable of converting the frequency signal from any compatible flow sensors to a preferred output type (analog, scaled pulse, protocol). In addition to standard square wave signals, it can also accept a sine wave, making it a versatile transmitter for numerous applications. The 310 and 320 offer analog and scaled pulse output, respectively, while the 340 models offer communication protocols (N2, BACnet/Modbus, or LonWorks), with energy (BTU) measurement (appropriate software and programming cables are required for installation; see Ordering Information). SPECIFICATIONS 310-00 320-00 340-00 Compact Saves space in crowded enclosures Communicating Communication protocols available on the 340 models Programmable Programmable (units of measure, calibration, etc.) using computer with Windows®- based operating system...save installation time in the field by pre-programming the device Input options Accepts sine wave input from a variety of other sources for application flexibility

  • Converting sine/square wave signals to 4 to 20 mA or protocol
  • Increasing wire run length limit for flow sensors
  • Connecting flow sensors to BAS panels

APPLICATIONS

Flow Monitoring | Transmitter: Analog, BTU, Pulse and Protocol Output 3X0 SERIES Converts Flow Signal to a Linear 4 to 20 mA Analog or a Protocol Signal HQ0001785.I 0221

S/ N: 310- 000 00 Sensor Inputs Side 4-20mA Loop(-) 4-20mA Loop(+) Shield Ground Power (4000 only) Model: 310 Programmable Analog Transmitter D.I.C. Comm Port Signal (-) Signal (+) Mattapoisett, MA 02739 ®Data Industrial 1.5” (39 mm) 0.9” (23 mm) 3.25” (83 mm) 1.5” (39 mm) 3.7” (94 mm) 1.75” (45 mm) 2.75” (70 mm) Side1.5” (39 mm) 1.5” (39 mm) 3.7” (94 mm) 1.75” (45 mm) 0.9” (23 mm) 3.25” (83 mm) 2.75” (70 mm) Side 1.6” (40 mm) 0.9” (23 mm) 0.6” (15 mm) 3.7” (94 mm) 3.0” (75 mm) VERIS PART # MANUF. PART # DESCRIPTION BGR-8310-00 8310-001, 2 Flow Transmitter, Analog, Programmable, 4 to 20 mA Output BGR-8340BN/ MB-00 8340BN/MB-00 1, 2 Flow Transmitter, BTU, BN-MB, No Enclosure BGR-8340BN/ MB-03 8340BN/MB-03 1, 2 Flow Transmitter, BTU, BN-MB, Plastic Enclosure BGR-8320-00 8320-001, Flow Transmitter, Programmable, Scaled Pulse Output BGR-8340-00 8340-00 1, 2 Flow Transmitter, Programmable, Frequency Output BGR-8A301-20 8A301-20 Programming Cable with CD for Analog/ Modbus/BACnet/LonWorks Outputs, Serial PC Connector BGR-40134-0002 840134-0002 Programming Cable with CD for Analog/ Modbus/BACnet/LonWorks Outputs, USB PC Connector 1. Software and programming cable are required for analog, Modbus, BACnet transmitter and meter products. 2. 340 Series also requires two 10k T2 thermistors for energy (BTU) measurement. BGR-8310-00 Dimensional Drawing BGR-8340-00 Dimensional Drawing BGR-8320-00 Dimensional Drawing ORDERING INFORMATION ACCESSORIES Veris TI Series immersion temperature sensors with 10K Type 2 thermistor work with the 340 Series transmitters with BTU. Flow Monitoring | 3x0 Series TIGTIH HQ0001785.I 0221