3RHP CRYDOM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
3 Phase RHP - Hybrid Solid State Contactors
/Control Voltage D5: 5 VDC D12: 12 VDC D24: 24 VDC E: 24 VAC F: 120 VAC G: 220 VAC Operating Voltage VAC 50/60 Hz 12: 120 V 1-phase 24: 240 V 3-phase or 1-phase 28: 280 V 3-phase 60: 600 V 3-phase Three Phase Device Load Current 40: 40 Amps 50: 50 Amps SERIES Derating Curves 3RHPXX40XX 25 35 45 55 65 75 Ambient Temperature, °C Load Current, Amps rms AWG # 6 AWG # 8 Power lead size 3RHPXX50XX 25 35 45 55 65 75 Ambient Temperature, °C Load Current, Amps rms AWG # 6 AWG # 8 Power lead size Safe Operating Area Safe Operating Area
3 Phase Contactor
Combined SSR and EMR advantages Lifetime >2 million operations @ full load No heat sink required DC logic compatible input Input status LED indicator Wire, lug or quick connect termination DP contactor footprint CE compliant & UL/cUL recognized Combined SSR and EMR advantages Lifetime >2 million operations @ full load No heat sink required Input status LED indicator Wire, lug or quick connect termination DP contactor footprint CE compliant & UL/cUL recognized CONTROL SPECIFICATIONS Coil Voltage Range Coil Power Consumption, Inrush Coil Power Consumption, Sealed Control Voltage Suffix Voltage suffix Operating Voltage (50/60Hz) Maximum Off-State Leakage Current per channel Load Current suffix Maximum Load Current per Phase @ 40°C Power terminals / wire range 24 - 280 VAC 0.05 mA @ 240 VAC
40 A Resistive
Dual quick connect and Binder head screws / AWG#14 - AWG#8 Input to Output Dielectric Isolation. Input/Output to Ground Dielectric Isolation. Contacts (Double Break ) Ambient Operating Temperature Range Ambient Storage Temperature Range Maximum Number of Operations per Minute Lifetime @ Rated Load Current, 40°C ambient temp, 30 operations/min, Rated Vcontrol Weight (typical) See Derating Curves for additional operational conditions. The RHP includes a Solid-State Relay. Therefore, the output is never completely open. The RHP includes an overtemperature protection for the Solid-State Module. GENERAL SPECIFICATIONS 540 grs (1.19 lb)
2500 VAC
-20°C to 75°C
4000 VAC
2 Million operations -40°C to 100°C OUTPUT SPECIFICATIONS Dual quick connect and Box lugs / AWG#14 - AWG#6 Screw torque requirements 18 in lbs (2.1 Nm) 25 in lbs (2.9 Nm) 48 - 600 VAC 0.06 mA @ 480 VAC
50 A Resistive
Specificationts @ 25°C unless otherwise noted.1 Min. Turn-On Voltage Min. Turn-Off Voltage E 20 - 26 VAC, 50/60 Hz
56 VA @ 24 VAC
6.6 VA @ 24 VAC
20 VAC
12 VAC
F 100 - 130 VAC, 50/60 Hz
56 VA @ 120 VAC
6.6 VA @ 120 VAC
100 VAC
24 VAC
G 208 - 240 VAC, 50/60 Hz
56 VA @ 220 VAC
6.6 VA @ 220 VAC
208 VAC
48 VAC
Max. Turn-On Time Max. Turn-Off Time 16.6 mS @ 60 Hz / 20 mS @ 50 Hz 32 mS @ 60 Hz / 40 mS @ 50 Hz CONTROL SPECIFICATIONS Control Voltage Range Control Voltage Suffix Max. Reverse Voltage Min. Turn-On Voltage Min. Turn-Off Voltage Input Current 4.5 - 5.5 VDC -5.5 VDC
4.5 VDC
1 VDC
12mA @ 5 VDC D12 10 - 15 VDC -15.5 VDC
9.5 VDC
2 VDC
12mA @ 12 VDC D24 22 - 27 VDC -27.5 VDC 12mA @ 24 VDC Voltage suffix Operating Voltage (50/60Hz) Maximum Off-State Leakage Current per channel Load Current suffix Maximum Load Current per Phase @ 40°C Power terminals / wire range Input to Output Dielectric Isolation Input/Output to Ground Dielectric Isolation Contacts (Double Break) Ambient Operating Temperature Range Ambient Storage Temperature Range Maximum Number of Operations per Minute Lifetime @ Rated Load Current, 40°C ambient temp, 30 operations/min, Rated Vcontrol Weight (typical) OUTPUT SPECIFICATIONS 100 - 120 VAC Dual quick connect and Binder head screws / AWG#14 - AWG#8 0.05 mA @ 120 VAC Three Normally Open 30 operations per min > 2 Million operations -40°C to 100°C 0.06 mA @ 240 VAC Dual quick connect and Box lugs / AWG#14 - AWG#6 540 grs (1.19 lb) -20°C to 75°C Max. Turn-On Time Max. Turn-Off Time 16.6 mS @ 60 Hz / 20 mS @ 50 Hz 32 mS @ 60 Hz / 40 mS @ 50 Hz Screw torque requirements 18 in lbs (2.1 Nm) 25 in lbs (2.9 Nm) See Derating Curves for additional operational conditions. The RHP includes a Solid-State Relay. Therefore, the output is never completely open. The RHP includes an overtemperature protection for the Solid-State Module. Specificationts @ 25°C unless otherwise noted.1 PATENT PENDIN G PATENT PENDIN G
Typical Electrical Connection for 3 Phase Applications Optional Electrical Connections for Single Phase Applications HYBRID SOLID STATE CONTACTOR 120/240 VAC Single Phase Operating Voltage IL 1 1L1 3L2 5L3=NC IL1 ≤ Rated current 6T3=NC Line Neutral DC Input/Control Voltage (D5, D12, D24 input versions) - + HYBRID SOLID STATE CONTACTOR 120/240 VAC Single Phase Operating Voltage IL2 ≤ Rated current IL3 ≤ Rated current IL2 + IL3 > Rated current IL 3 IL 2 NC Line Neutral 1L1 3L2 5L3 DC Input/Control Voltage (D5, D12, D24 input versions) - + HYBRID SOLID STATE CONTACTOR - +120/240 VAC Single Phase Operating Voltage IL1 = (IL2 + IL3) ≤ Rated current IL 3 IL 1 IL 2 1L1 3L2 5L3 DC Input/Control Voltage (D5, D12, D24 input versions) Line Neutral HYBRID SOLID STATE CONTACTOR ~~~ - + VLL IL 1 IL 3 DC Input/Control Voltage (D5, D12, D24 input versions) Load IL 1 5L3 3L2 1L1 6T3 4T2 2T1
3 Phase AC
(E, F, G input versions) AC Input/Control Voltage (E, F, G input versions) AC Input/Control Voltage (E, F, G input versions) AC Input/Control Voltage (E, F, G input versions) The single phase supply voltage must be wired to terminal 1L1 and 3L2 for proper single phase operation. In applications switching two single phase loads (R1 and R2) where the combined load current exceeds the contactor’s rating (40 or 50 Amps) the return/neutral lead must not be wired through the contactor (see above drawing). Match VLL to voltage suffixes 28 & 60 for options E, F & G and 12 & 24 for options DX.5 (For output voltage options 24, 28, 60) (For output voltage options 12, 24, 28, 60) DO NOT apply any AC voltage to contactor coil connections, for DC versions only.