38N4 MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
P. / 2ES-456-4 DCS Input/Output Relay Card Series OUTPUT RELAY CARD MODEL 38N-4 Specifications are subject to change without notice. MODEL & SUFFIX CODE SELECTION 38N–4 MODEL OUTPUT CARD 4 : Manual ON / Auto OFF
ORDERING INFORMATION
Specify code number. (e.g. 38N-4)
RELATED PRODUCTS
- Standard rack (model: 38N-BY1, -BH1) GENERAL SPECIFICATIONS Construction: Rack mounted; terminal access via screw terminals at the front and via card-edge con- nector at the rear Connection: M3.5 screw terminals and card-edge connec - tor Screw terminal material: Nickel-plated steel (torque 0.8 N·m) Power input: Supplied via card-edge connector Fuse for voltage output: 0.5A incorporated Alarm: Dry contact output at the rack terminal when the fuse is blown. Isolation: DCS output or external contact or power to power for voltage output or fuse alarm output Indicator LED: Orange light turns on with the output ON INPUT ■ DCS OUTPUT: Open collector Coil rating: 24V DC @10mA (approx.) ■ EXTERNAL CONTACT (EM valve control SW): Dry contact Coil rating: 24V DC @20mA (approx.) OUTPUT ■ VOLTAGE CONTACT OUTPUT Rated load: 100V AC @0.5A (cosø=1) 30V DC @0.5A (resistive load) Electrical life 10 5 cycles (rate 30/min.) Maximum switching voltage: 125V AC or 30V DC Maximum switching power: 50VA or 15W Minimum load: 5V DC @10mA Mechanical life: 5 × 107 cycles External protection: Contact protection and noise quench- ing recommended when driving an inductive load (coil, etc.) ■ FUSE ALARM OUTPUT: Dry contact Rated load: 50V AC @0.5A (cosø=1) 30V DC @0.5A (resistive load) Electrical life 10 5 cycles (rate 30/min.) Maximum switching voltage: 50V AC or 30V DC Maximum switching power: 25VA or 15W Minimum load: 5V DC @10mA Mechanical life: 5 × 107 cycles External protection: Contact protection and noise quench- ing recommended when driving an inductive load (coil, etc.) INSTALLATION Power input: Operational voltage range 24V DC ±10%, ripple 10% p-p max., approx. 40mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90% RH (non-condensing) Dimensions: W23×H149×D102 mm (0.91”×5.87”×4.02”) Weight: 150 g (0.33 lbs) PERFORMANCE Insulation resistance: ≥100MΩ with 500V DC (DCS output or external contact or power to power for voltage output to fuse alarm output) Dielectric strength: 1000V AC @1 minute (DCS output or external contact or power to power for volt- age output to fuse alarm output) DESCRIPTIONS The 38N-4 is a DCS-front-end use relay card installed in a dedicated 19-inch rack, used to manually turn on/off a volt- age contact output to directly drive devices such like elec- tromagnetic valve, and to automatically turn it off by an external status contact from the DCS.
- Voltage output (LED turns on at output)
- Test switch useful for the DCS test running
- 0.5A fuse for the voltage output
P. 2 / 2ES-456-4 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM FRONT VIEW 5 6 7 8 LED (orange)AUTO OFF ON SW TAG NAME 8–M3.5 SCREWS 149 (5.87) 23 (.91) 1 2 3 4 X2X3 X1 POWER PANEL ON SW PANEL OFF SW FIELD OFF SW FIELD ON SW EXTERNAL CONTACT (EM valve control SW) VOLTAGE CONTACT OUTPUT NO NC COM OFF AUTO ON CONNECTOR DCS OUTPUT FUSE ALARM FOR VOLTAGE OUTPUT POWER FOR VOLTAGE OUTPUT