3130-F110-P7T1-W14QR3-5A E-T-A | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 7

Technical content

3130 Thermal Overcurrent Circuit Breaker

www.e-t-a.de2613

Description

Single, two and three pole rocker switch/thermal trip free circuit breakers (S-type TO CBE to EN 60934) of compact design for snap-in panel mounting. Available either with protection on one/ both/all poles or, in the case of the double pole version, protection on one pole only. Illumination is optional and there is a choice of rocker colours. Approved to CBE standard EN 60934 (IEC 60934). Motors, protection of transformers (e.g. for illumination), solenoids, household and office machines, electrical tools, mobile homes, boats, construction vehicles, medical equipment to EN 60601. Features and benefits l Single pole, double pole or three-pole thermal circuit brea- ker/switch combination l Voltage ratings AC 240 V; 3 AC 415 V; DC 50 V l Current ratings: 0.1...20 A l Rating UL1077/AC 277 V, Use Group EA for industrial applications l Can be combined with X3120 Power Entry Module. Please refer to the respective section in this document. Your benefits l Maximum equipment availability is ensured by overload protection perfectly matched with the loads (prevention of nuisance tripping) and quick resettability l Reduced mounting and wiring time l Less space requirement l Less disposition and storage costs l Enhanced overall reliability The current data sheet is available on our website: www.e-t-a.de/d001 Information onlineCompliances 3130-F110 1-pole X3130-FA.A 2-pole, with power entry module 3130-F130 3-pole 3130-F112 1-pole 3130-F114 1-pole Approvals Authority Standard Rated voltage Current ratings Approval logos VDE IEC/EN 60934 AC 240 V AC 240 V

3 AC 415 V

0.1 A...20 A (1-pole) 0.1A...16 A (2-pole) 0.1A...16 A (3-pole) 0.1A...16 A (1-, 2-pole)

0.1 A…20 A (1-pole)

CQC(1) GB/T 17701 AC 240 V AC 240 V 0.1 A...20 A (1-pole) 0.1A...16 A (2-pole) 0.1A...16 A (3-pole) 0.1A...16 A (1-, 2-pole) (1) not for frame mounting 2/3/4/5 Authority Standard Rated voltage Current ratings UL-categories Approval logos UG TC OL UL/CSA UL 1077, CSA C22.2 No.235 AC 277 V AC 250 V AC 250 V DC 50 V 0.1...16 A (a) 0.1...16 A (b) 0.1...12 A (c) 0.1...16 A (d) EA D D D 1(a), 2 1(a), 2 (a) 1- and 2-pole, all poles protected (b) 1- and 2-pole (c) 3-pole (d) 1-, 2- and 3-pole

www.e-t-a.de 2613 Technical data Technical data For further details please see: www.e-t-a.de/ti_e Voltage rating AC 240 V; 3 AC 415 V; DC 50 V (UL: AC 250 V; 3 AC 250 V; DC 50 V) Current ratings 0.1...20 A 1-pole 0.1...16 A 2- and 3-pole Typical life 1-pole (IEC/EN 60934) AC 240 V: 0.1...20 A 30,000 operations at 1 x IN, inductive DC 50 V: 0.1...4 A 30,000 operations at 1 x IN, inductive 4.5...16 A 30,000 operations at 1 x IN, resistive DC 28 V: 0.1...20 A 30,000 operations at 1 x IN, inductive Typical life 2-pole (IEC/EN 60934) AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive Typical life 3-pole (IEC/EN 60934) 3 AC 415 V: 0.1...16 A 30,000 operations at 1 x IN, inductive Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V current path/current path AC 1,500 V Insulation resistance > 100 MΩ (DC 500 V) Degree of protection operating area IP40 (IEC 60529/DIN 40050) terminal area IP00 Vibration 5 g (57-500 Hz) ± 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis Shock 1-pole: 25 g (11 ms) 2 + 3-pole: 20 g (11 ms) to IEC 60068-2-27, test Ea Corrosion 96 hours at 5 % salt mist, to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH, to IEC 60068-2-78, test Cab Mass approx. 45 g (three pole) approx. 31 g (double pole) approx. 17 g (single pole) Interrupting capacity ICN (EN 60934) IN UN ICN 1, 2, 3-pole 0.1...2 A AC 240 V/3 AC 415 V 10 x IN 1 pole 2.5…20 A AC 240 V 200 A 2 pole 2.5…16 A AC 240 V 300 A 3 pole 2.5…12 A 3 AC 415 V 150 A 3 pole 14…16 A 3 AC 415 V 130 A Rupture capacity INC (UL1077) IN UN Inc 1, 2-pole 0.1...16 A AC 250 V 3 500 A, C, 1 3-pole 0.1...12 A 3 AC 250 V 5 000 A, C, 1 1, 2-pole 0.1…16 A AC 277 V 2 000 A, C, 1 1,2-pole 0.1...16 A DC 50 V 2 000 A, C, 1

www.e-t-a.de2613 Ordering information - 1-pole Type No. 3130 single pole thermal circuit breaker Mounting F Snap-in frame Frame 1 Standard, panel cut-out 14.6 x 34 mm 3 Panel cut-out 18.0 x 35-37 mm Number of poles 1 single pole, thermally protected Frame mounting For Frame 1, snap-in, panel thickness 1.0-2.5 mm, color 0 black 2 white 4 grey For Frame 3, snap-in, panel thickness 1.5-3.2 mm, color 1 black 3 white 5 grey Terminal design P 7 blade terminals 6.3 x 0.8 mm H7 for terminals 1.1, 2.1 3.1 terminal screws M 3.5 Characteristic curve T 1 thermal Actuator style W rocker switch with marking „I“ and „O“ moulded in Actuator colour Rocker opaque without illumination

01 Q black

02 Q white

04 Q red

Rocker translucent white, with LED illumination

12 Q G green

12 Q R red

12 Q Y yellow

Rocker translucent color, with LED illumination

14 Q R red

15 Q Y orange

19 Q G green

Illumination voltage range (1) 2 10 - 14 V DC 3 20 - 28 V DC 6 90 - 140 V AC 7 185 - 275 V AC 9 225 – 330 V AC Current ratings 0.1...20 A 3130 - F 1 1 0 - P7 T1 - W 14 Q R 3 - 5 A ordering example Ordering information - multipole Type No. 3130 multipole thermal circuit breaker Mounting F Snap-in frame Frame 1 Standard, panel cut-out size depending on no. of poles A version for X3130 Number of poles 2 2-pole thermally protected 3 3-pole thermally protected 5 2-pole, 1-pole thermally protected Frame mounting

0 Snap-in frame, black, panel thickness

1.0-2.5 mm for frame size 1 A 2-pole, version for X3130 Terminal design P 7 blade terminals 6.3 x 0.8 mm (characteristic curve T1) H7 for terminals 1.1, 2.1 3.1 terminal screws M 3.5 Characteristic curve T 1 thermal Actuator style W rocker switch with marking „I“ and „O“ moulded in Actuator colour Rocker opaque without illumination Rocker translucent color, with LED illumination

16 Q T blue

Illumination voltage range(1) 2 10 - 14 V DC 3 20 - 28 V DC 6 90 - 140 V AC 7 185 - 275 V AC 8 320 - 450 V AC 9 225 – 330 V AC(2) Current ratings 0.1...16 A 3130 - F 1 3 0 - P7 T1 - W 14 Q R 7 - 5 A ordering example Please observe our minimum ordering quantities (1) N/A for non-illuminated version (2) for 2-pole variant only Custom designed versions Looking for a version you cannot find in our order numbering key? Please get in touch. We will be pleased to find a solution for you.

www.e-t-a.de 2613 Dimensions 3130-F110-... Dimensions 3130-F120-... terminal for illumination conductor size 0.14 mm2 (AWG26), length 180 mm (7.09 in.) +0.3 +.012 blade terminals 6.3 x 0.8 mm 9.5OFF ON 5.85 233 14.5 34+0.2 14.6+0.2 min. 1.5 < R0.5 ±0.1 panel thickness 1-2.5 mm (.039-.098 in.) panel cut-out I.2 LINE I.II.3 -0.4 -0.2 .230 .079 .374 .571 ±.004 < .020 -.016 -.008 min .059 .709 1.42 1.34+.008 .575+.008 .394 1.30 .079 .787 1.34 optional illumination R3.118 Edge of working parts: ISO13715 Flat head screw M3.5, tightening torque max. 0.8 Nm +0.3 +.012 26.1+0.2 29.5 optional illumination 2 I blade terminals 6.3 x 0.8 mm OFF 5.85 233 34+0.2 min. 1.5 < R0.5±0.1 panel thickness 1-2.5 mm (.039-.098 in.) panel cut-out I.2 LINE I.II.3 Edges of working parts: ISO13715 .230 .079 .827 1.02 ±.004 < .020 min .059 1.16 1.42 1.34+.008 1.03+.008 .394 1.30 .079 .787 1.34 unit .118 Flat head screw M3.5, tightening torque max. 0.8 Nm Standard current ratings and typical internal resistance values Dimensions 3130-F311-... OFF ON 18.5 9.5 12.4 5.8 5.8 233100.8 1.5 39.5 19.5 19.5 -0.2 -0.4 ±0.1 A min. 1.5 max. R0.5 +0.3 B 18.1±0.1 A 1,50 35.1 ± 0.1 2,35 36.1 ± 0.1 3,20 37.1 ± 0.1 B Terminal for illumination conductor size 0.14 mm², length 180 mm Blade terminals 6.3 mm x 0.8 mm Flat head screw M3.5, tightening torque max. 0.8 Nm Panel cut-out Current rating (A) Internal resistance per pole (Ω) Current rating (A) Internal resistance per pole (Ω) 0.1 94 4 0.0435 0.2 24 5 0.0325 0.3 12 6 0.0215 0.4 5.30 7 0.0165 0.5 4.20 7,5 0.0165 0.8 1.50 8 0.0165 1 0.9 10 < 0.02 1.2 0.80 12 < 0.02 1.5 0.45 14 < 0.02 1.75 0.36 15 < 0.02 2 0.27 16 < 0.02 2.5 0.0785 18 < 0.02 3 0.0595 20 < 0.02 3.5 0.0565

www.e-t-a.de2613 Dimensions 3130-F130-... -0.4 -0.2 +0.3 +.012 2 unitI3 37.6+0.2 optional illumination 37.5 32.5 blade terminals 6.3 x 0.8 mm OFF 5.85 233 34+0.2 min. 1.5 < R0.5 ±0.1 panel thickness 1-2.5 mm (.039-.098 in.) panel cut-out I.2 LINE I.II.3 Edges of working parts: ISO 13715 .230 .079 1.28 1.48 ±.004 < .020 min .059 1.61 1.42 1.34+.008 1.48+.008 .394 1.30 .079 .787 1.34 .118 -.016 -.008 Panel cut-outFlat head screw M3.5, tightening torque max. 0.8 Nm Internal connection diagrams 1.2 line 1.1 1-pole lamp 3.1 3.2 2.1 2.21.2 line 1.1 3-pole load load load load 2-pole 2.1 2.21.2 line 1.1 load load Installation drawing 3130-F1... mounting area When installing the circuit breaker apply pressure on bezel only. I.2 LINE I.II.3 1032 58 7 operating area .984 1.26 .276.276.315 .787 .197 .394 Note: Terminal drawings 6,3 2,8 6,3 ALT / OLD t=0,8 NEU / NEW t=0,8 Note: The flat terminals are changed from slotted to unslotted from June 2026 onwards. This will not affect their shape, fit or function (the electromechanical specifications will remain the same). The order number remains the same as well. However, it will no longer be possible to attach receptacles for 2.8 x 0.8 mm. In some illustrations in this data sheet, the old version of the flat plug is still visible.

www.e-t-a.de 2613 All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. This is a metric design and millimeter dimensions take precedence ( mm ) inch The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient °F temperature °C -22 -30 -20 +14 -10 +32 +73.4 +23 +104 +40 +122 +50 +140 +60 Trip time in seconds +23 °C +73.4 °F +60 °C +140 °F -30 °C -22 °F … times rated current Trip time in seconds +23 °C +73.4 °F +60 °C +140 °F -30 °C -22 °F 12 46 81 02 04 0 10000 1000 100 0.1 0.1…2 A 2.5…20 A 1-pole 2.5…16 A 2- and 3-pole Multipole types: all poles symmetrically loaded. With single pole overload, thermal tripping will be at approx. 1.54 x IN with 2-pole devices and at approx. 1.68 x IN with 3-pole devices. 12 46 81 02 04 0 10000 1000 100 0.1 … times rated current 1,4 1,4 Typical time/current characteristicsAccessories 3130-F130-... ø4.4 .173 36.5 1.44 41.5 1.63 1.97 .197 .472 .315 1.97 .433 2.17 ø11 Splash cover, transparent, for 3-pole version X 221 258 01 (IP54), comprising bezel Y 306 109 01 and transparent cover Y 306 108 01

Power Entry Module for 3130-FA.A 2-pole circuit breaker www.e-t-a.de2613 This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. Dimensions Mounting hole X3130 40.236.5 Circuit breaker 3130 (2-pole) ø 3.3 I.2 LINE I.I I.3 The space-saving X3130 Power Entry Module with double pole circuit breaker 3130-FA.A combines three functions within a single component: A C14 appliance inlet and rocker switch with resettable overcurrent protection; screw mounting from the front or the rear. Electrical medical apparatus, laboratory equipment, professional audio equipment and office machines.

Ordering information

Type No. X3130 Power Entry Module for circuit breaker type 3130-FA.A Module A appliance inlet C14 Design 04 screw-type mounting Accessories 00 without Version 0 1 not wired; mounting position 3130: 0 to connector 11 wired; mounting position 3130: 0 to connector Delivery condition M module supplied with circuit breaker FA.A Technical data Rated voltage AC 250 V Rated current 10 A (IEC)

15 A (UL/CSA)

Ambient temperature -25 °C ... 70 °C Number of poles L, N + ground Cable cross section max. 1.5 mm2 Degree of protection Class I Mounting method screw-type mounting (front or rear) Terminal design blade terminals 6.3 x 0.8 mm Housing material thermoplastics, black UL94V-0 Appliance inlet C14 according to IEC/EN 60320-1 Switch circuit breaker type 3130, 2-pole Approvals X3130-A – C14-appliance inlet Authority Standard Rated voltage Current ratings ENEC IEC/EN 60320-1 AC 240 V 10 A UL/CSA UL 60320-1, CSA C22.2 no. 60320-1 AC 250 V 15 A CQC CCC AC 250 V 10 A Please note: the current rating of the circuit breaker must not exceed the max. current of the appliance inlet, depending on approval. Complete module X3130-A also available with approval according to UL 60320-1 at max. current of 15 A. 72 ± 0.2 M3/Ø 3.3 31.6 ± 0.1 63.6 ± 0.15 2.50 2.83 Ø.130 1.24