IF602SS-198R GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
Features
- One or two Signaling Line Circuits (SLC), up to 396 points
- Velociti protocol 99 detec tors, 99 devices per Loop
- Velociti self-programming logic
- Downloadable or front-panel programmable
- Password protected
- Approved for Supervisory Service
- Fully digital SLC protocol
- SmartLink™ peer-to-peer networkable
- 1000-event history log
- Automatic drift compensation
- Coded signaling capability
- Adjustable sensor sensitivity and temperature settings
- Supervisory service
- Style 6 (Class A) or Style 4 (Class B) SLC
- Four Style Y (Class B), or two Style Z (Class A) notification appliance circuits (NACs)
- Semi-flush mounting (between 16" studs)
- 160-character display
- Optional UDACT
- Built-in strobe and horn synchronization IF602SS g2401ph1.jpg An ISO 9000-2000 Company APPROVED FM SIGNALING S521
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2490 Rev. A3 page 2 of 3 www.gamewell-fci.com Analog Addressable Signaling Line Circuits (Continued) Each SLC loop has a dedicated microprocessor that simul- taneously communicates with connected field devices and the main CPU. The IF602SS uses Velociti ® fully digital communications protocol to improve the s peed and accuracy of event reporting. The communications protocol provides for alarm verification per detector, detector adjustability and compen- sation, adjustable analog heat detector range circuit isola- tion, and priority interrupts. Priority interrupts allow contact- type devices such as manual fire alarm stations to interrupt the polling cycle and transmit their addresses at any time during a polling sequence. The fully digital protocol allows the IF602SS to operate on most types of field wiring, greatly expanding its use in retro- fit applications. Consult the Supplemental SLC Manual or Tech Support for specific wiring requirements. IF602SS Power Supply The IF602SS power supply is a fully regulated 8 amp. sup- ply that furnishes system operating and signaling power. It is equipped with a battery charger which maintains the sec- ondary power source. The power supply is monitored by the main CPU, ensuring that adequate power levels are available. The power supply design allows for high effi- ciency while providing precis e power output. The battery charger maintains batteries up to 26 AH. The supply pow- ers four on-board Notification Appliance Circuits (NACs) (two Class A) with multiple built-in synchronization proto- cols for System Sensor, Cooper-Wheelock and others. Input (I) / Output (O) Devices Addressable control output devices are the interface between analog circuits and building functions. The outputs are controlled with Control By Event (CBE) software within the IF602SS, and can be programmed to respond to any event. The control devices can be used as supervised remote signaling circuits. The IF602SS, with Gamewell-FCI’s complete line of 600 Series devices, provides a foundation for system design. The IF602SS’s RS-232 output expands system monitoring and control capabilities. Remote Display and Control Serial annunciator drivers are available in 16-point incre- ments and are an ideal interface to graphic annunciators. Switches can be used for Acknowledge, Reset, Signal Silence, Drill, etc., to custom ize the remote status control network. Remote Display Network (Continued) An alphanumeric display can also be used for remote sta- tus and control. The alphanumeric display is designed to communicate over the serial communications network. The IF602SS can communicate locally or remotely with a printer to document system activity. See the RAN/SAN data sheet (CS-2025) for complete annunciator details.
Applications
The IF602SS Analog Addressable Control Panel is designed for new or retrofit small- to mid-sized projects that require state-of-the-art life-safety systems. The embedded CPU offers users unrivaled reliability without sacrificing flexibility or value. With compatible analog sensors and addressable input and control interface devices, and its remote status and control capabilities, the IF 602SS provides syst em engineers with all the tools necessary to design effective system solutions for any application. Architectural/Engineering Specifications The control panel furnished and installed shall be capable of supporting 396 addressable devices and two analog loops. The panel shall utilize a fully digital Signaling Line Circuit (SLC) protocol. The panel shall contain four on- board Notification Appliance Ci rcuits (NACs) that support multiple synchronization protocols. The panel shall utilize a 160-character Liquid Crystal Display (LCD) and a 1,000- event history log. The panel shall be a Gamewell-FCI IF602SS with Velociti.
www.gamewell-fci.com CS-2490 Rev. A3 page 3 of 3 Specifications Common Control: Standby Current: 0.125A Alarm Current: 0.171A plus signaling circuit power, plus 0.002A for master box, or plus 0.022A for reverse-polarity Input Power: 120 VAC, 3.0A; or 240 VAC, 1.5A Auxiliary Output: S+/S–, A+/A–, 2.0 A maximum Common Relays: 1.0A @ 30 VDC, or 0.5A @ 250 VAC Notification appliance circuits: Circuits: Four Class B, two Class A. Output: 3.0A maximum@24 VDC per circuit. Maximum 8.0A total for all circuits. Analog SLC: 198 396 Standby Current: 0.045A 0.055A Alarm Current: 0.045A 0.055A Panel Dimensions: Standard Cabinet: 20.0" H x 14.0" W x 4.5" D (50.8 H x 35.6 W x 11.4 D cm) XL Cabinet: 30.0" H x 22.0" W x 5.5" D (76.2 H x 55.9 W x 13.97 D cm) Battery Storage Dimensions: Standard Cabinet: 6.0" H x 9.0" W x 4.5" D (15.24 H x 22.86 x 11.43 D cm) XL Cabinet: 14" H x 22.0" W x 5.5" D (35.56 H x 55.88 W x 13.97 D cm) Relative Humidity: 93% non-condensing Temperature Rating:
Ordering Information
IF602SS-198R IF602SS Analog Addressable System with Velociti consisting of the following:
- IF602SS common control
- 8 amp. main power supply
- One (1) analog circuit module (198 analog addressable points)
- Standard cabinet assembly (CAB-602R) Standard Cabinet: 20.0” H x 14.0” W x 4.5” D (50.8 H x 35.6 W x 11.4 D cm) IF602SS-198XL 198 point/one SLC IF602SS in extra-large housing allowing space for battery storage (Refer to IF602SS-198R model listed above). Extra-large Cabinet: 30.0" H x 22.0" W x 5.5" D (76.2 H x 55.88 W x 13.97 D cm) IF602SS-396R IF602SS analog addressable system with Velociti, consisting of the following:
- IF602SS common control.
- 8 amp main power supply.
- Two (2) analog circuits module (396 analog addressable points).
- Standard cabinet assembly (CAB-602R). Standard Cabinet: 20.0” H x 14.0” W x 4.5” D (50.8 H x 35.56 W x 11.43 D cm) IF602SS-396XL 396 point/two (2) SLC IF602SS (refer to IF602SS-396R above) in extra-large housing, allowing space for battery storage. Extra-large Cabinet: 30.0" H x 22.0" W x 5.5" D (76.2 H x 55.88 W x 13.97 D cm)
52358 IdentiFlex 602SS Analog/Addressable
Fire Alarm Control Panel Installation and Operation Manual
31077 CTM-602, city-tie/remote signaling
module for 602 Series panels.
31078 ISO-232, RS-232 serial-port isolator
module for 602 Series panels.
31079 CLA-602, Class “A” adapter module for
SLC, 602 Series panels.