3103A BELDEN | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 2
Technical content
Product: 3103A Inst, 1 Pr #12 Str BC, PVC-NYL Ins E1, OS, Blk PVC Jkt, 600V TC 150V NPLF THHN OR THWN Product Description UL Instrumentation, 1 Pair 12AWG (7x20) Bare Copper, PVC-NYL Insulation E1 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC 150V NPLF THHN OR THWN 90C Dry 75C Wet SUN RES DIR BUR Technical Specifications Construction Details Conductor Element No. of Elements Size Stranding Material Conductor(s) 2 12 AWG 7x20 BC - Bare Copper Insulation Element Material Nom. Thickness Nom. Insulation Diameter Color Code Conductor(s) PVC/Nylon - Polyvinyl Chloride + Nylon 0.019 in (0.48 mm) 0.131 in (3.33 mm) Black, White Outer Shield Shield Type Material Coverage Tape Bi-Laminate (Alum+Poly) 100% Outer Jacket Material Nom. Thickness Nom. Diameter Ripcord PVC - Polyvinyl Chloride 0.047 in (1.2 mm) 0.364 in Yes Overall Cable Diameter (Nominal): 0.364 in
Electrical Characteristics
Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Shield Max. Current
1.65 Ohm/1000ft 56 pF/ft (180 pF/m) 106 pF/ft (348 pF/m) 31 Amps per Conductor at 30ºC
600 V (TC-ER), 150 V (NPLF)
Mechanical Characteristics Temperature UL Temperature Operating 90°C Dry/Wet -25°C to +90°C Bend Radius Stationary Min. Installation Min. 4.368 in (110.9 mm) 4.368 in Max. Pull Tension: 228 lbs (103 kg) Bulk Cable Weight: 91 lbs/1000ft
Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial Flammability / Reaction to Fire: UL1685 UL Loading, T-29-520, IEEE 1202 FT4 NEC / UL Compliance: Article 336, Article 760 European Directive Compliance: EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) APAC Compliance: China RoHS II (GB/T 26572-2011) Product Notes Notes: Alternate color coding available upon request. History Update and Revision: Revision Number: 0.267 Revision Date: 12-20-2022 © 2023 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.