98-3100 MACOM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Features
- 3-pole contactors.
- Industry-standard mounting plate.
- Optional interlock/auxiliary switches available.
- Manual test button is standard.
- Coil dust cover helps keep dust and dirt away from magnet and coil area.
- Double E magnet system provides optimal performance. Coil Data Nominal Coil Voltage 24 120 208/240 277 480 Maximum Pickup Volts 18 88 177 220 384 Drop-Out Volts Range 6 -15 20 - 70 40 - 140 65 - 185 150 - 270 Nominal Inrush VA @ 50 Hz 60 60 60 60 65 Nominal Inrush VA @ 60 Hz 53 53 53 53 53 Nominal Sealed VA @ 60 Hz 5 5 5 5 5 Nominal DC Resistance - Ohms 7 180 720 950 3100 Users should thoroughly review the technical data before selecting a product part number. It is recommended that users also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application. Full Number Line Locked Resistive Maximum Horsepower Load of Voltage Rotor Amps Voltage Single Three Amps Poles Amps Rating Phase Phase 240/277 120 30 110/120 1.5 - 20 3 480 100 30 200/240 3 7.5 600 80 30 480/600 - 7.5 110/120 2 - 240/277 150 35 200/208 - 7.5 25 3 480 125 35 240/277 5 10 600 100 35 480 - 15 600 - 20 110/120 2 - 240/277 180 40 200/208 - 10 30 3 480 150 40 240/277 5 10 600 120 40 480 - 15 600 - 20 110/120 3 - 240/277 240 50 200/208 - 10 40 3 480 200 50 240/277 7.5 10 600 160 50 480 - 20 600 - 25 Contact Data @ 25°C Arrangements: 3 Form X (3PST -NO-DM). Maximum Ratings: See Contact Ratings Table. Material: Silver Cadmium Oxide. Coil Data @ 25°C Voltage: 24 - 480 VAC, 50/60 Hz. See Coil Data Table below. Insulation Class: UL Class B (130°C). Duty Cycle: Continuous. Environmental Data T emperature Range:Storage and Operating: -40°C – +65°C. Flammability: UL 94-HB housing. Mechanical Data Contact T ermination: 20, 25, 30 FLA Models T ype:#10-32 Screw with quad 0.250” (6.35 mm) quick connects. Wire Size: 16-8 AWG (Stranding must be split for 8 AWG wire.) Tightening T orque:25 in.-lbs.
40 FLA Models
T ype:Box Lug with dual 0.250” (6.35 mm) quick connects. Wire Size: 14-4 Cu/Al AWG Tightening T orque:40 in.-lbs. Coil T ermination:Dual 0.250” (6.35 mm) quick connects, standard. A 0.250” quick connect and a #6-32 screw, optional. Arc Cover: Optional on 20-30 FLA models, standard on 40 FLA models. Weight: 16 oz. (455 g) approximately Model 98 - 3100 series Definite Purpose Contactor 3-pole, 20-40 FLA AC Coil File E75492 File EN60947-4-1:1991 IEC 947-4-1
reference purposes only. Dimensions are in inches over (millimeters) unless otherwise specified. Catalog 1308242 Issued 3-03 (PDF Rev. 3-04) Specifications and availability subject to change. www.tycoelectronics.com Technical support: Refer to inside back cover. 3100-30Q9999CY 3100-30T9999CY 3100-30U9999CY 3100-30Q10999CG 3100-30T10999CG 3100-30U10999CG Standard part numbers listed below are more likely to be available from stock.
Ordering Information
ORDERING NOTE: “Standard” terminals need not be specified in the “Ordering Information” chart above. “Special” terminals are offered on a special order basis. Special order items may be subject to extended leadtimes and significant minimum order quantities. Y our Tyco Electronics sales engineer must consult with the factory before providing price and availability information regarding items with these options. T ypical Part No. B 3100 - 30 Q 9 999 1. Series: 3100 = 3-pole, 20-40 FLA contactor 2.Packaging: Y = Individual Pack - = Bulk Pack A-ZZZ = Customer specific information (assigned by factory) 3.Pole Configuration: 30 = 3 Form X (3PST -NO-DM) 4.Coil Voltage (50/60 Hz.): Q = 24VAC U = 208/240VAC H = 480VAC J = 120VAC, molded M = 277VAC, molded T = 120VAC V = 277VAC I = 24VAC, molded K = 208/240VAC, molded W = 480VAC, molded 5.Contact Ratings (Inductive): 7 = 20 FLA 8 = 25 FLA 9 = 30 FLA 10 = 40 FLA 6.Customer ID Suffix: 999 = Standard Model 000-998 = Factory assigned customer ID 7 . Option Code: Leave Blank = No customer-specific options A - ZZ = Factory assigned customer-specific options. 2.0 MAX. (50.8) 3.00 (76.2) 3.39 (86.1) 2.97 (75.44)1.19 (30.23) 1.78 (45.21) 2.00 (50.8).250 TYP . (6.35) .203 TYP . (5.156) .455 DIA. (11.56) .203 TYP . (5.156) 2.375 TYP . (60.325) .125 (3.175) 3.25 (82.55) 3.75 (95.25) Outline Dimensions T ermination Options Standard on 20, 25, 30, 35 FLA #10-32 Combination Phillips, Slotted & 5/16 Hex Head #12 Washer Special on 20, 25, 30, 35 FLA #10-32 Sems Screw with Pressure Plate Standard on 40 FLA Lug accepts 14-4 Cu/Al AWG .253 (6.43) Factory Modifications Field Added Kits Description Contact Config. Kit Catalog Number of NO NC Number Kits Required Single unit interlock 1 0 98220-303 1 configurations listed. 0 1 98220-331 1 Maximum of two. 1 1 98220-332 1 (One on each side.) 2 0 98220-303 2 0 2 98220-331 2 See footnote (1) for ratings. 2 2 98220-332 2 SPDT Circuit 1 1 98220-337 1 (Either one or two 2 2 98220-338 1 switches per side.) 2 2 98220-337 2 See footnote (2) for ratings. 4 4 98220-338 2 SPDT Dry Circuit 1 1 98220-341 1 0.1 amp max. 2 2 98220-340 1 Gold Flashed Contacts 4 4 98220-340 2 Factory Modifications Field Added Kits Description Contact Config. Kit Catalog Number of NO NC Number Kits Required Single unit interlock 1 0 98220-303 1 configurations listed. 0 1 98220-331 1 Maximum of two. 1 1 98220-332 1 (One on each side.) 2 0 98220-303 2 0 2 98220-331 2 See footnote (1) for ratings. 2 2 98220-332 2 Auxiliary Switches Various interlock / auxiliary switches are available for the Model 98 contactor. All auxiliary switches for the Model 98 are snap-on design, no tools required. Footnotes: Ratings of Auxiliary Interlocks / Switches (1) Contact Rating Single Circuit NO or NC and two circuit NO/NC: 120V 240V 480V 600V Amperes - Break 3.0 1.5 0.75 0.6 Amperes - Make 30 15 7.5 6 Amperes - Continuous 10 10 10 10 (2) Contact Rating SPDT (337): 10A, 1/3 HP , 125 or 250 VAC 1/2A, 125 VDC; 1/4A, 250 VDC: 4A 120 VAC on Lamp Load
1 N/O / 1 N/C
Equipped with 0.250” (6.35) Quick Connect Terminals Equipped with #6-32 Screw Terminals & Saddle Clamps Shown with Optional Auxiliary Switches TWO SPDT SWITCHES PER SIDE ONE SPDT SWITCH PER SIDE