3076F BELDEN | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
Part Number: 3076F Fieldbus, 1 Pr #18 Str TC, PO Ins, OS, PVC Jkt, Flexible SUN RES OIL RES Product Description Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PO Insulation, Overall Beldfoil® Shield, Orange PVC Outer Jacket, Flexible SUN RES OIL RES Technical Specifications Physical Characteristics (Overall) Conductor AWG Stranding Material Nominal Diameter No. of Pairs 18 7x26 TC - Tinned Copper 0.045 in 1 Conductor Count: 2 Insulation Material PO - Polyolefin Outer Shield Material Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D Tape Aluminum/Polyester Beldfoil® 100 % TC - Tinned Copper 20 7x28 mm Outer Jacket Material Material Nominal Diameter PVC - Polyvinyl Chloride 0.28 in Construction and Dimensions Cabling Twists Filler 5.3 twist/ft Polypropylene
Electrical Characteristics
Nominal Conductor DCR Nominal Outer Shield DCR 5.86 Ohm/1000ft 7.5 Ohm/1000ft Capacitance Max. Capacitance Unbalance Nom. Capacitance Conductor to Shield Nom.Mutual Capacitance 1.2 pF/ft 45 pF/ft 24 pF/ft Inductance Nominal Inductance 0.19 µH/ft Impedance Nominal Characteristic Impedance
100 Ohm
High Frequency (Nominal/Typical) Nom. Insertion Loss 0.08 dB/100ft Delay Nominal Velocity of Propagation (VP) [%] 66 % High Freq Frequency [MHz] Max. Insertion Loss (Attenuation) Max./Min. Input Impedance (unFitted) 0.031 MHz 0.091 dB/100ft 100 Ohm Current Element Max. Recommended Current [A] Per Conductor 5.2 Amps Voltage UL Voltage Rating
300 V RMS
Electrical Characteristics Notes: Max Propagation Delay Change From 7.812 kHz to 39.06 kHz: 518 pS/ft Other Electrical Characteristic 2: 31.25 KBits/sec Temperature Range UL Temp Rating: 105°C Operating Temp Range: -40°C To +105°C Mechanical Characteristics Oil Resistance: Yes UV Resistance: Yes Bulk Cable Weight: 38 lbs/1000ft Max Recommended Pulling Tension: 60 lbs Min Bend Radius/Minor Axis: 2.5 in Standards NEC Articles: 725, 727, 800 NEC/(UL) Specification: CMR, ITC-ER, PLTC-ER CEC/C(UL) Specification: CMG CPR Euroclass: Eca IEEE Specification: 1202, IEEE 383 Vertical Tray Flame Test (70,000 BTU) Applicable Environmental and Other Programs EU Directive 2000/53/EC (ELV): Yes EU Directive 2003/96/EC (BFR): Yes EU Directive 2011/65/EU (ROHS II): Yes EU Directive 2012/19/EU (WEEE): Yes EU Directive 2015/863/EU: Yes EU Directive Compliance: EU Directive 2003/11/EC (BFR) EU CE Mark: Yes EU RoHS Compliance Date (yyyy-mm-dd): 2004-01-01 CA Prop 65 (CJ for Wire & Cable): Yes MII Order #39 (China RoHS): Yes Suitability Suitability - Burial: Yes - UL Suitability - Indoor: Yes Suitability - Oil Resistance: Yes Suitability - Outdoor: Yes Suitability - Sunlight Resistance: Yes
Flammability, LS0H, Toxicity Testing C(UL) Flammability: FT4 UL Flammability: UL1666 Riser ISO/IEC Flammability: IEC 60332-1-2 IEEE Flammability: 1202 UL voltage rating: 300 V RMS Plenum/Non-Plenum Plenum (Y/N): No Part Number Variants Item # Color UPC Length Footnote 3076F 0061000 Blue, Light 612825140269 1,000 ft C 3076F 0031000 Orange 612825140207 1,000 ft C 3076F 003250 Orange 612825140221 250 ft C 3076F 0032500 Orange 612825140238 2,500 ft C 3076F 003500 Orange 612825140245 500 ft C 3076F 0035000 Orange 612825140252 5,000 ft C N 3076F 00310000 Orange 612825140214 C N Footnote: C - CRATE REEL PUT-UP. Footnote: N - FINAL PUT-UP LENGTH MAY VARY -0% TO +10% FROM LENGTH SHOWN. Product Notes Notes: Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010 History Update and Revision: Revision Number: 0.322 Revision Date: 08-22-2019 © 2019 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.