Product: 3076ENH Profibus PA, 1PR #18 Str TC, PO ins, OS, LSNH Jkt, 300 V Product Description Profibus PA, 1 Pair AWG 18 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil(s) or Copper Tape(s) shielding, LSZH / FRNC jacket , 300 V Technical Specifications Product Overview Suitable Applications: harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. Physical Characteristics (Overall) Conductor AWG Stranding Material No. of Pairs 18 7x26 TC - Tinned Copper 1 Conductor Count: 2 Total Number of Pairs: 1 Insulation Material Nominal Diameter Diameter +/- Tolerance Nominal Wall Thickness PE - Polyethylene 2.55 mm 0.05 mm 0.67 mm Color Chart Number Color Pair 1 White & Black Outer Shield Type Material Thickness of Foil Drainwire Material Drainwire AWG Tape Bi-Laminate (Alum+Poly) 9 / 23 µm TC - Tinned Copper AWG20/7 Outer Jacket Material Nominal Diameter Nominal Wall Thickness LSZH - Low Smoke Zero Halogen (Flame Retardant) 7.5 mm 1.15 mm
Electrical Characteristics
Max. Conductor DCR Max. Outer Shield DCR
20.5 Ohm/km 26 Ohm/km
Max. Capacitance Conductor to Conductor Max. Capacitance Conductor to Shield 80 pF/m 155 pF/m Inductance Nominal Inductance 0.62 uH/m
Frequency [MHz] Nominal Characteristic Impedance Nominal Characteristic Tolerance
0.03125 MHz 100 Ohm 5 Ohm
Nominal Velocity of Propagation (VP) [%] 66% High Frequency Frequency [MHz] Max. Insertion Loss (Attenuation) 0.01 MHz 0.2 dB/100m 0.039 MHz 0.3 dB/100m 0.1 MHz 0.6 dB/100m 0.5 MHz 2.8 dB/100m 1 MHz 3.7 dB/100m Voltage Voltage Rating [V] 300 V Temperature Range Installation Temperature Range: -15°C To +80°C Storage Temperature Range: -45°C To +80°C Operating Temp Range (Flexible Install): -15°C To +80°C Operating Temp Range (Fixed Install): -45°C To +80°C Mechanical Characteristics Oil Resistance: IEC 60811-404 Max. Pull Tension: 50 N Min. Bend Radius During Installation: 100 mm Standards ISO/IEC Compliance: IEC 61158-2 CPR Euroclass: Eca CENELEC Compliance: EN 50290-2-20 Applicable Environmental and Other Programs Environmental Space: Indoor - Euroclass Eca Suitability Suitability - Sunlight Resistance: Yes Flammability, LS0H, Toxicity Testing IEC Flammability: IEC 60332-1-2, IEC 60332-3-24 IEC 60754-1 - Halogen Amount: Zero IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity: 2.5 µS/mm IEC 60754-2 - Halogen Acid Gas Amount - Min. pH: 4.3 IEC 61034-2 - Smoke Density Min. Transmittance: 60% Related Part Numbers Variants Item # Color Put-Up Type Length EAN 3076ENH.00500 Blue Reel 500 m 8719605005519 3076ENH.001000 Blue Reel 1,000 m 8719605005502 3076ENH.041000 Blue Reel 1,000 m 8719605005557 3076ENH.01500 Orange Reel 500 m 8719605005540 3076ENH.011000 Orange Reel 1,000 m 8719605005526
3076ENH.012050 Orange Reel 2,050 m 8719605005533 History Update and Revision: Revision Number: 0.232 Revision Date: 12-22-2023 © 2024 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.