3076ELS BELDEN | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 3

Technical content

Product: 3076ELS Profibus PA, 1PR #18 Str TC, PO ins, OS, LSNH Jkt, 300V SWA Product Description Profibus PA, 1 Pair AWG 18 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil(s) or Copper Tape(s) shielding, LSZH / FRNC jacket , 300V SWA Technical Specifications Product Overview Suitable Applications: Profibus PA or Foundation FieldBus PA exposure to rodent, crush, or cut through force, harsh environment, outdoors, where multiple cable runs are required, data transmission applications such as Profibus DP or PA, Instrumentation and computer cable, etc. exposure to temperature extremes, humidity/moisture, dust, and oil. Physical Characteristics (Overall) Conductor AWG Stranding Material 18 7x26 TC - Tinned Copper Conductor Count: 2 Total Number of Pairs: 1 Insulation Material Nominal Diameter Diameter +/- Tolerance Nominal Wall Thickness PE - Polyethylene 2.55 mm 0.05 mm 0.67 mm Color Chart Number Color Option .00 with blue inner- and outerjacket White & Black Option .02 with yellow inner- and outerjacket White & Black Option .03 with orange inner- and outerjacket White & Black Option .05 with blue inner- and orange outer jacket White & Black Option .07 with orange inner- and black outer jacket Orange & Blue Inner Shield Type Material Drainwire Material Drainwire AWG Tape Bi-Laminate (Alum+Poly) TC - Tinned Copper AWG20/7 Inner Jacket Material Nominal Diameter Nominal Wall Thickness LSZH - Low Smoke Zero Halogen (Flame Retardant) 7.5 mm 1.15 mm Outer Jacket Material Nominal Diameter Nominal Wall Thickness LSZH - Low Smoke Zero Halogen (Flame Retardant) 13 mm 1.85 mm Construction and Dimensions Armor Type of Armor Material Thickness of Armoring Wires Coverage Percentage Steel Wire Armoring Galvanized steel wire 0.9 mm Min. 95%

Electrical Characteristics

Max. Conductor DCR Max. Outer Shield DCR

20.5 Ohm/km 26 Ohm/km

Max. Capacitance Conductor to Conductor Max. Capacitance Conductor to Shield Max. Capacitance Unbalance 80 pF/m 155 pF/m 4 pF/m Inductance Nominal Inductance 0.62 uH/m Impedance Frequency [MHz] Nominal Characteristic Impedance Nominal Characteristic Tolerance

0.03125 MHz 100 Ohm 5 Ohm

Nominal Velocity of Propagation (VP) [%] 66% High Frequency Frequency [MHz] Max. Insertion Loss (Attenuation) 0.01 MHz 0.2 dB/100m 0.039 MHz 0.3 dB/100m 0.1 MHz 0.6 dB/100m 0.5 MHz 2.8 dB/100m 1 MHz 3.7 dB/100m Voltage Voltage Rating [V] 300 V Temperature Range Installation Temperature Range: -15°C To +80°C Storage Temperature Range: -45°C To +80°C Operating Temp Range (Flexible Install): -15°C To +80°C Operating Temp Range (Fixed Install): -45°C To +80°C Mechanical Characteristics Oil Resistance: IEC 60811-404 Min. Bend Radius During Installation: 260 mm Standards ISO/IEC Compliance: IEC 61158-2 CPR Euroclass: Eca CENELEC Compliance: EN 50290-2-27, EN 50288-7 Applicable Environmental and Other Programs Environmental Space: Indoor/Outdoor - Euroclass Eca Suitability Suitability - Outdoor: Yes Suitability - Sunlight Resistance: Yes Flammability, LS0H, Toxicity Testing IEC Flammability: IEC 60332-1-2, IEC 60332-3-24 IEC 60754-1 - Halogen Amount: Zero

IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity: 2.5 µS/mm IEC 60754-2 - Halogen Acid Gas Amount - Min. pH: 4.3 IEC 61034-2 - Smoke Density Min. Transmittance: 60% Related Part Numbers Variants Item # Color Put-Up Type Length EAN 3076ELS.07500 Black Reel 500 m 8719605180131 3076ELS.00500 Blue Reel 500 m 8719605005397 3076ELS.001000 Blue Reel 1,000 m 8719605005380 3076ELS.03320 Orange Reel 320 m 8719605005441 3076ELS.03500 Orange Reel 500 m 8719605005458 3076ELS.031000 Orange Reel 1,000 m 8719605005434 3076ELS.051000 Orange Reel 1,000 m 8719605005465 3076ELS.031150 Orange Reel 1,150 m 8719605179968 3076ELS.02500 Yellow Reel 500 m 8719605005427 3076ELS.021000 Yellow Reel 1,000 m 8719605005403 3076ELS.021100 Yellow Reel 1,100 m 8719605005410 History Update and Revision: Revision Number: 0.231 Revision Date: 12-22-2023 © 2024 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.