Product: 29505 VFD 300% Gnd, 3C+IG #6 Str TC, XLPO Ins+PVC Gnd, OS+TC Brd, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable Product Description Belden 300% Ground Flexible VFD, 3 Conductor 6AWG (7x19x27) Tinned Copper, XLPO Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable 1000V CSA AWM I/II A/B 600V CIC TC SUN RES DIR BUR Oil Resistant Technical Specifications Product Overview Suitable Applications: AC Motor drives, VFD, Variable Frequency drives Physical Characteristics (Overall) Conductor Element AWG Stranding Material No. of Conductors 6 7x19x27 TC - Tinned Copper 3 Ground Wire 6 7x19x27 TC - Tinned Copper 1 Conductor Count: 4 Insulation Material Nominal Wall Thickness XLPE - Cross Linked Polyethylene 0.062 in PVC - Polyvinyl Chloride 0.062 in Color Chart Number Color
1 Black and Numbered 1
2 Black and Numbered 2
3 Black and Numbered 3
4 Green/Yellow
Type Layer Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D Tape 1 Aluminum/Polyester Duofoil® 100 % TC - Tinned Copper 12 (4x) 65x30 mm Braid 2 TC - Tinned Copper 85 % Outer Jacket Material Material Nominal Diameter Nominal Wall Thickness PVC - Polyvinyl Chloride 1.002 in 0.095 in
Electrical Characteristics
0.41 Ohm/1000ft
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield
0.171 µH/ft Impedance Nominal Characteristic Impedance
56 Ohm
Max. Recommended Current [A]
75 Amps per conductor @ 30°C
Description UL Voltage Rating CSA AWM I/II A/B 1000 V RMS
600 V RMS (Type TC)
UL Temp Rating: 90°C Dry, 90°C Wet Operating Temp Range: -40°C To +90°C Wet Temp Range: -40°C To +90 °C Dry Temp Range: -40°C To +90 °C Mechanical Characteristics Oil Resistance: Yes Bulk Cable Weight: 811 lbs/1000ft Max Recommended Pulling Tension: 1220 lbs Min Bend Radius/Minor Axis: 8.25 in Standards NEC Articles: 336 - ER NEC/(UL) Specification: TC-ER, RHW-2, WTTC CEC/C(UL) Specification: CIC, TC CSA AWM Specification: AWM I/II A/B PMSHA Specification: P-07-KA070003 Other Specification: 1000V UL Flexible Motor Supply Cable Applicable Environmental and Other Programs EU Directive 2000/53/EC (ELV): Yes EU Directive 2003/96/EC (BFR): Yes EU Directive 2011/65/EU (ROHS II): Yes EU Directive 2012/19/EU (WEEE): Yes EU Directive 2015/863/EU: Yes EU Directive Compliance: EU Directive 2003/11/EC (BFR) EU CE Mark: Yes EU RoHS Compliance Date (yyyy-mm-dd): 2005-10-13 CA Prop 65 (CJ for Wire & Cable): Yes MII Order #39 (China RoHS): Yes Suitability Suitability - Burial: Yes Suitability - Indoor: Yes Suitability - Oil Resistance: Yes Suitability - Outdoor: Yes Suitability - Sunlight Resistance: Yes Flammability, LS0H, Toxicity Testing UL Flammability: UL1685 UL Loading
CSA Flammability: FT4 IEEE Flammability: 1202, 383 UL voltage rating: 1000 V RMS (Flexible Motor Supply Cable) Part Number Variants Item # Color UPC Length Footnote 29505 0101000 Black 612825137139 1,000 ft C Z 29505 010250 Black 612825137177 250 ft C Z 29505 0103500 Black 612825137184 3,500 ft C Z Footnote: C - CRATE REEL PUT-UP. Footnote: Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN. History Update and Revision: Revision Number: 0.325 Revision Date: 09-10-2019 © 2019 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.