29504F BELDEN | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 3

Technical content

Product: 29504F VFD 300% Gnd, 3C+IG #8 Str TC, XLPO Ins+PVC Gnd, OS+TC Brd, Blk TPE Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable Product Description Belden 300% Ground Extra Flexible VFD, 3 Conductor 8AWG (7x24x30) Tinned Copper, XLPO Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield, Black TPE Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable 1000V WTTC 600V CIC TC SUN RES OIL RES I&II DIR BUR Technical Specifications Product Overview Suitable Applications: AC Motor drives, VFD, Variable Frequency drives Physical Characteristics (Overall) Conductor Element AWG Stranding Material No. of Conductors 8 7x24x30 TC - Tinned Copper 3 Ground Wire 8 7x24x30 TC - Tinned Copper Conductor Count: 3 Insulation Material Nominal Wall Thickness PVC - Polyvinyl Chloride 0.062 in XLP - Cross Linked Polyolefin 0.062 in Color Chart Number Color

1 Black and Numbered 1

2 Black and Numbered 2

3 Black and Numbered 3

4 Green/Yellow

Type Layer Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Tape 1 Aluminum/Polyester Duofoil® 100 % TC - Tinned Copper 12 Braid 2 TC - Tinned Copper 85 % Outer Jacket Material Material Nominal Diameter Nominal Wall Thickness TPE - Thermoplastic Elastomer 0.933 in 0.095 in

Electrical Characteristics

0.64 Ohm/1000ft

Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield

0.181 µH/ft Impedance Nominal Characteristic Impedance

62 Ohm

Max. Recommended Current [A]

55 Amps per conductor @ 30°C (per NEC)

1000 V RMS (Flexible Motor Supply Cable)

UL Temp Rating: 90°C Dry, 90°C Wet Operating Temp Range: -40C To +90C Wet/Dry Wet Temp Range: -40°C To +90 °C Mechanical Characteristics Bulk Cable Weight: 636 lbs/1000ft Max Recommended Pulling Tension: 768 lbs Min Bend Radius (Continuous Flexing): 7 in Min Bend Radius/Minor Axis: 4.7 in Standards NEC Articles: 336 - ER NEC/(UL) Specification: TC-ER, WTTC, XHHW-2 CEC/C(UL) Specification: 600V Type CIC TC Other Specification: 1000V UL Flexible Motor Supply Applicable Environmental and Other Programs EU Directive 2000/53/EC (ELV): Yes EU Directive 2003/96/EC (BFR): Yes EU Directive 2011/65/EU (ROHS II): Yes EU Directive 2012/19/EU (WEEE): Yes EU Directive 2015/863/EU: Yes EU Directive Compliance: EU Directive 2003/11/EC (BFR) EU CE Mark: Yes EU RoHS Compliance Date (yyyy-mm-dd): 2005-10-13 CA Prop 65 (CJ for Wire & Cable): Yes Suitability Suitability - Indoor: Yes Suitability - Outdoor: Yes Suitability - Sunlight Resistance: Yes Flammability, LS0H, Toxicity Testing UL Flammability: UL1685 UL Loading CSA Flammability: FT4 IEEE Flammability: 1202, 383 Vertical Tray Flame Test (70,000 BTU) UL voltage rating: 1000 V RMS (Flexible Motor Supply Cable) Part Number Variants Item # Color UPC Length

29504F 0101000 Black 612825367284 1,000 ft 29504F 0105000 Black 612825367277 5,000 ft History Update and Revision: Revision Number: 0.118 Revision Date: 09-10-2019 © 2019 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.