Creation date November 4, 2021 1:40:31 AM CET Catalogue status 22.10.2021 / We reserve the right to make technical changes. 1 RCMC-5000-AO-P Weidmüller Interface GmbH & Co. KG Klingenbergstraße 26 D-32758 Detmold Germany www.weidmueller.com Product image Rogowski coil A Rogowski coil is a closed air coil without a ferromagnetic core used for floating potential measurement of AC and pulse currents. Measurement with the Ragowski coil is used widely in technology, as it can be retroactively integrated without separating the primary electric circuit in existing systems. Because this method shows no saturation effect, even the smallest currents and high-frequency harmonics can be measured without loss of accuracy. General ordering data Version Measuring transducer, every Rogowski coil, 100…

5000 A, Output : analogue V / mA

Order No. 2593410000 Type RCMC-5000-AO-P GTIN (EAN) 4050118647754 Qty. 1 pc(s).

RCMC-5000-AO-P Weidmüller Interface GmbH & Co. KG Klingenbergstraße 26 D-32758 Detmold Germany www.weidmueller.com Technical data Creation date November 4, 2021 1:40:31 AM CET Catalogue status 22.10.2021 / We reserve the right to make technical changes. 2 Dimensions and weights Depth 78 mm Depth (inches) 3.071 inch Height 100 mm Height (inches) 3.937 inch Width 23.1 mm Width (inches) 0.909 inch Net weight 58 g Temperatures Humidity 5...95 %, no condensation Electrical attributes Frequency band 50...60 Hz Secondary voltage 22,5 mV (@ 50Hz Iprimary = 1 kA) Technical data Pollution severity 2 Protection degree IP20 Voltage supply 24 V DC ± 25 % Technical properties Protection degree IP20 Input Input measurement range 100 A, 200 A, 300 A, 400 A, 500 A, 600 A, 800 A,

1000 A, 1500 A, 2000 A,

4000 A, 5000 A

Output voltage, note 0…5 V DC, 0…10 V DC, 0… 225 mV AC, 0…333 mV AC load impedance voltage ≥ 1 kΩ General data Accuracy < 0.5 % of measuring range Configuration Keys and LED display Current consumption 200 mA typical Linearity ± 0.1 % typ. Standard EN 61010-1: 2010, EN 61010-2-030:2010, EN 61326-1: 2013, EN 61000-6-2:2005, EN 61000-6-3:2007 Temperature coefficient ≤ 0.015 % / °C Type of connection PUSH IN Vibration according to IEC 60721, 3M1 Voltage supply 24 V DC ± 25 %

RCMC-5000-AO-P Weidmüller Interface GmbH & Co. KG Klingenbergstraße 26 D-32758 Detmold Germany www.weidmueller.com Technical data Creation date November 4, 2021 1:40:31 AM CET Catalogue status 22.10.2021 / We reserve the right to make technical changes. 3 Insulation coordination Insulation voltage 1.5 kV AC 1 min. Pollution severity 2 Standard EN 61010-1: 2010, EN 61010-2-030:2010, EN 61326-1: 2013, EN 61000-6-2:2005, EN 61000-6-3:2007 Connection data Type of connection PUSH IN Classifications ETIM 6.0 EC002653 ETIM 7.0 EC002653 ETIM 8.0 EC002653 ECLASS 9.0 27-21-01-20 ECLASS 9.1 27-21-01-20 ECLASS 10.0 27-21-01-20 ECLASS 11.0 27-21-01-20 Important note Product information The RCMC-5000-XX measuring transducer is designed for electronic measurement of AC current. The RCMC-5000-XX measuring transducer may only be used together with a Weidmüller RCMA-B22-DXX Rogowski coil. Functional description The RCMC-5000-XX measuring transducer converts the signal from the Rogowski coil into an analogue output signal with high phase fidelity. The device is configured using two front buttons. LEDs display the operating and configuration status.

Features

  • 12 selectable current measuring ranges
  • USB connection: exclusively for power supply! Approvals Approvals ROHS Conform UL File Number Search E469563 Downloads Approval/Certificate/Document of Conformity Declaration of Conformity User Documentation Instruction sheet Catalogues Catalogues in PDF-format

RCMC-5000-AO-P Weidmüller Interface GmbH & Co. KG Klingenbergstraße 26 D-32758 Detmold Germany www.weidmueller.com Drawings Creation date November 4, 2021 1:40:31 AM CET Catalogue status 22.10.2021 / We reserve the right to make technical changes. 4 Application use with Rogowski coil