02/09/2016 066167 - HPL-ED2016 V19.0 EN 1 / 5 Thermistor￿overload￿relay￿for￿machine￿protection,￿24-240V50/60HZ/DC Part￿no. EMT6-DB Article￿no. 066167 Catalog￿No. EMT6-DB Delivery￿programme Product range EMT6 thermistor overload relay for machine protection Function Selector switch with/without manual reset For manual or remote resetting Test button Mains and fault LED display Rated￿operational￿current AC-15

240 V Ie A 3

300 V Ie A 3

400 V Ie A 3

Value applies starting with release 001. conventional thermal current Ith A 6 Rated control voltage Us V 24 - 240 V 50 - 400 Hz 24 - 240 V DC Notes Observe manual MN03407006Z-DE/EN. Can be snap fitted on a top-hat rail to IEC/EN 60715. Technical￿data General Standards IEC/EN 60947, VDE 0660, EN 55011 Climatic proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open °C -25 - +60 Enclosed °C - 25 - 45 Storage °C - 45 - 85 Mounting position As required Weight kg 0.15 Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 10 Degree of Protection IP20 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Safe isolation to EN 61140 between the contacts V AC 250 between contacts and power supply V AC 250 Auxiliary￿and￿control￿circuits Rated impulse withstand voltage Uimp V AC 4000 Rated impulse withstand voltage Uimp V AC 6000 Value applies starting with release 001. Overvoltage category/pollution degree III/3 Terminal capacities Auxiliary and control circuits Solid mm2 1 x (0.5 - 2.5) 2 x (0.5 - 1.5) Flexible with ferrule mm2 1 x (0.5 - 2.5) 2 x (0.5 - 1.5) Solid or stranded AWG 20 - 14 Terminal screw M3.5 Tightening torque Nm 1.2

02/09/2016 066167 - HPL-ED2016 V19.0 EN 2 / 5 Tools Pozidriv screwdriver Size 2 Standard screwdriver mm 1 x 6 Auxiliary￿power￿circuit Rated insulation voltage Ui V 300 Rated insulation voltage Ui V 400 Value applies starting with release 001. Rated operational current Ie A AC--14 Make contact

380 V 400 V 415 V Ie A 3

Value applies starting with release 001. Break contact Value applies starting with release 001. AC-15 Make contact

220 V 230 V 240 V Ie A 3

300 V Ie A 1

380 V 400 V 415 V Ie A 1

Value applies starting with release 001. Break contact Value applies starting with release 001. Max. short-circuit protective device Fuse gG/gL A 6 Control￿circuit Rated insulation voltage Ui V 240 Rated operational voltage Ue V 240 Pick-up and drop-out values x Ue 0.85 - 1.1 Power consumption AC VA 3.5 DC W 2 Trip at approx. Ω 3600 Recovery at approx. Ω 1600 Electromagnetic￿compatibility￿(EMC) Electrostatic discharge (ESD) applied standard IEC/EN 61000-4-2 Air discharge kV 8 Contact discharge kV 6 Electromagnetic fields (RFI) applied standard IEC/EN 61000-4-3 V/m 80 - 1000 MHz: 10 1.4 - 2 GHz: 3 2.0 - 2.7 GHz: 1 Radio interference suppression EN 55011 Class B Burst kV Supply cables: 2 Signal cables: 1 according to IEC/EN 61000-4-4 power pulses (Surge) 2 kV (symmetrical) 4 kV (asymmetrical) according to IEC/EN 61000-4-5 Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10

02/09/2016 066167 - HPL-ED2016 V19.0 EN 3 / 5 Design￿verification￿as￿per￿IEC/EN￿61439 Technical data for design verification Operating ambient temperature min. °C -25 Operating ambient temperature max. °C 60 Technical￿data￿ETIM￿6.0 Relays (EG000019) / Temperature monitoring relay (EC001446) Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Temperature monitoring equipment Type of electric connection Screw connection Rated control supply voltage Us at AC 50HZ V 24 - 240 Rated control supply voltage Us at AC 60HZ V 24 - 240 Rated control supply voltage Us at DC V 24 - 240 Voltage type for actuating AC/DC With detachable clamps No Number of measuring circuits 1 Error registration possible No External reset possible Yes Number of contacts as normally closed contact 1 Number of contacts as normally open contact 1 Number of contacts as change-over contact 0 Width mm 23 Height mm 84 Depth mm 104 Approvals Product Standards UL 508; CSA-C22.2 No. 14; IEC/EN 60947-8; CE marking UL File No. E29184 UL Category Control No. NKCR CSA File No. 12528 CSA Class No. 3211-03 North America Certification UL listed, CSA certified Specially designed for North America No Max. Voltage Rating 600 V AC Degree of Protection IEC: IP20, UL/CSA Type: -

02/09/2016 066167 - HPL-ED2016 V19.0 EN 4 / 5 Characteristics

02/09/2016 Eaton Industries GmbH http://www.eaton.eu © 02/2016 by Eaton Industries GmbH 066167 - HPL-ED2016 V19.0 EN Dimensions Applies to release 001 and higher Additional￿product￿information￿(links) IL03407100Z￿(AWA2327-1454)￿thermistor￿overload￿relay￿for￿machine￿protection IL03407100Z (AWA2327-1454) thermistor overload relay for machine protection ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407100Z2014_11.pdf MN03407006Z￿(AWB2327-1446)￿EMT6￿machine￿protection￿relays￿-￿overload￿monitoring￿for￿machines￿in￿Ex￿e￿areas MN03407006Z (AWB2327-1446) EMT6 machine protection relays - overload monitoring for machines in Ex e areas - English ftp://ftp.moeller.net/DOCUMENTATION/AWB_MANUALS/MN03407006Z_DEEN.pdf terminal markings and sensor circuit http://de.ecat.moeller.net/flip-cat/?edition=HPLTEv1&startpage=6.21