2491B PRO-ELEC | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Page <1> V1.028/01/20 TECHNICAL DATA SHEET Construction Conductor Class 5 flexible plain copper Insulation LSZH (Low Smoke Zero Halogen) Insulation Core Red, Black, Blue, Orange, White, Yellow, Green/Yellow, Grey, Brown, Violet, Pink Sheath Colour See Table Specification Voltage Rating Uo/U H05Z-K - 0.5mm² to 1mm²: 300/500V H07Z-K - 1.5mm² to 240mm²: 450/750V Temperature Rating -25°C to +90°C Minimum Bend Radius Up to 35mm²: 4 x overall diameter 50mm² and above: 6 x overall diameter 2491B / 6701B - H05Z-K / H07Z-K BS EN 50525-3-41 Cable Important Notice : This data sheet and its contents (the “Information”) belong to pro-ELEC. No licence is granted for the use of it other than for information purposes in connection with the products to which it relates. No licence of any intellectual property rights is granted. The Information is subject to change without notice and replaces all data sheets previously supplied. The Information supplied is believed to be accurate but pro-ELEC assumes no responsibility for its accuracy or completeness, any error in or omission from it or for any use made of it. Users of this data sheet should check for themselves the Information and the suitability of the products for their purpose and not make any assumptions based on information included or omitted. Liability for loss or damage resulting from any reliance on the Information or use of it (including liability resulting from negligence or where pro-ELEC was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict pro-ELEC’s liability for death or personal injury resulting from its negligence.
Page <2> V1.028/01/20 TECHNICAL DATA SHEET PART NO CROSS SECTIONAL AREA mm2 (NOMINAL) THICKNESS OF INSULATION mm (NOMINAL) NOMINAL OVERALL DIAMETER mm MINIMUM RESISTANCE OF INSULATION AT 90°C Mohms/km NOMINAL WEIGHT kg/km Lower Limit Upper Limit CB20904 CB20905 CB20906 CB20907 CB20908 CB20909 CB20910 CB20911 CB20912 CB20913 CB20914 CB20915 CB20916 CB20917 CB20918 CB20919 CB20920 CB20921 CB20922 CB20923 CB20924 CB20925 CB20926 CB20927 CB20928 CB20929 CB20930 CB20931 CB20932 CB20933 CB20934 CB20935 CB20936 CB20937 CB20938 CB20939 CB20940 CB20941 CB20942 CB20943 CB20944 CB20945 CB20946 CB20947 CB20948 CB20949 CB20950 CB20951 DIMENSIONS
Page <3> V1.028/01/20 TECHNICAL DATA SHEET PART NO CROSS SECTIONAL AREA mm2 (NOMINAL) THICKNESS OF INSULATION mm (NOMINAL) NOMINAL OVERALL DIAMETER mm MINIMUM RESISTANCE OF INSULATION AT 90°C Mohms/km NOMINAL WEIGHT kg/km Lower Limit Upper Limit CB20952 CB20953 CB20954 CB20955 CB20956 CB20957 CB20958 CB20959 CB20960 CB20961 CB20962 CB20963 CB20964 CB20965 CB20966 CB20967 CB20968 CB20969 CB20970 CB20971 CB20972 CB20975 CB20976 CB20977 CB20978 CB20979 CB20980 CB20981 CB20982 CB20983 CB20984 CB20985 CB20986 CB20987 CB20988 CB20989 CB20990 CB20991 10 1 5.7 7.1 0.0056 108.2 CB20992 CB20993 CB20994 CB20995 CB20996 16 1 6.7 8.4 0.0046 163.4
Page <4> V1.028/01/20 TECHNICAL DATA SHEET NOMINAL CROSS SECTIONAL AREA mm2 MAXIMUM DIAMETER OF WIRES IN CONDUCTOR mm MAXIMUM RESISTANCE OF CONDUCTOR AT 20°C ohms/km (Plain Wires) 0.5 0.21 39 0.75 0.21 26 1 0.21 19.5 1.5 0.26 13.3 2.5 0.26 7.98 4 0.31 4.95 6 0.31 3.3 10 0.41 1.91 16 0.41 1.21 25 0.41 0.780 35 0.41 0.554 50 0.41 0.386 70 0.51 0.272 95 0.51 0.206 120 0.51 0.161 150 0.51 0.129 185 0.51 0.106 240 0.51 0.0801 CONDUCTORS Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Page <5> V1.028/01/20 TECHNICAL DATA SHEET NOMINAL CROSS SECTIONAL AREA mm2 REFERENCE METHOD A (ENCLOSED IN CONDUIT IN THERMALLY INSULATING WALL ETC) Amps REFERENCE METHOD B (ENCLOSED IN CONDUIT ON A WALL OR IN A TRUNKING ETC) Amps REFERENCE METHOD C (CLIPPED DIRECT) Amps REFERENCE METHOD F (IN FREE AIR OR ON A PERFORATED CABLE TRAY ETC HORIZONTAL OR VERTICAL ETC) TOUCHING Amps REFERENCE METHOD G (IN FREE AIR) SPACED BY ONE CABLE DIAMETER Amps
2 Cables Single-Phase
3 Cables Three-Phase
2 Cables
1 14 13 17 15 19 17.5 - - - - - 1.5 19 17 23 20 25 23 - - - - - 2.5 26 23 31 28 34 31 - - - - - 4 35 31 42 37 46 41 - - - - - 6 45 40 54 48 59 54 - - - - - 10 61 54 75 66 81 74 - - - - - 16 81 73 100 88 109 99 - - - - - 25 106 95 133 117 143 130 161 141 135 182 161 35 131 117 164 144 176 161 200 176 169 226 201 50 158 141 198 175 228 209 242 216 207 275 246 70 200 179 253 222 293 268 310 279 268 353 318 95 241 216 306 269 355 326 377 342 328 430 389 120 278 249 354 312 413 379 437 400 383 500 454 150 318 285 393 342 476 436 504 464 444 577 527 185 362 324 449 384 545 500 575 533 510 661 605 240 424 380 528 450 644 590 679 634 607 781 719
ELECTRICAL CHARACTERISTICS
Current Carrying Capacity and Voltage Drop Ambient temperature: 30ºC Conductor operating temperature: 90ºC 1. Where a conductor operates at a temperature exceeding 70ºC it must be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see also Regulation 512.1.2). 2. Where cables in this table are connected to equipment or accessories designed to operate at a temperature not exceeding 70ºC, the current ratings given in the equivalent table for 70ºC thermoplastic insulated cables (Table 4D1A) must be used (see Regulation 523.1). The above table is in accordance with Table 4E1A of the 17th Edition of IEE Wiring Regulations.
Page <6> V1.028/01/20 TECHNICAL DATA SHEET NOMINAL CROSS SECTIONAL AREA mm2
2 CABLES DC
2 CABLES SINGLE-PHASE AC
3 OR 4 CABLES THREE-PHASE AC
(enclosed in conduit or trunking) Reference Methods C, F and G (clipped direct, on tray or in free air) Reference Methods A and B (enclosed in conduit or trunking) Reference Methods C, F and G (clipped direct, on tray or in free air) Cable Touching Cable Spaced Cable Touching Trefoil Cable Touching Flat Cable Spaced* Flat 1 46 46 46 46 40 40 40 40 1.5 31 31 31 31 27 27 27 27 2.5 19 19 19 19 16 16 16 16 4 12 12 12 12 10 10 10 10 10 4.7 4.7 4.7 4.7 4 4 4 4 r x z r x z r x z r x z r x z r x z r x z VOLTAGE DROP DERATING FACTORS Conductor operating temperature: 90ºC r = Resistive Component x = Reactive Component z = Impedance Value * Spacings larger than one cable diameter will result in a larger voltage drop. The above table is in accordance with Table 4E1B of the 17th Edition of IEE Wiring Regulations. For cables having conductors of 16mm2 or less cross-sectional area their inductances can be ignored and (mV/A/m)r values only are tabulated. For cables having conductors greater than 16mm2, cross-sectional area the impedance values are given as (mV/A/m)z, together with the resistive component (mV/A/m)r and the reactive component (mV/A/m)x. The above paragraph is extracted from Appendix 4 of the 17th Edition of IEE Wiring Regulations. AMBIENT TEMPERATURE 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC 65ºC 70ºC 85ºC 90ºC 95ºC