Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de2102
Description
One, two and three pole thermal-magnetic circuit breakers with trip free mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). Designed for panel or plug-in mounting. Available with auxiliary contacts (1 x N/O, 1 x N/C) for status signalling. Two and three pole models are internally linked to ensure that both/all poles trip in the event of an overload on one pole, even if the actuator is held in the ON position. A choice of characteristic curves further extends the range of applications possibilities for these CBEs. Special auxiliary contact versions for industrial atmosphere and low voltages (e. g. 5 V) available on request. Approved to CBE standard EN 60934 (IEC 60934). Suitable for use in distribution rails – see section Power Distribution Systems. Process control equipment, robotics, machine tool control, communications systems, instrumentation, rail vehicles. Special versions, e.g. for aggressive environmental conditions and low voltages (e. g. 5 V) on request. 2210-S2.. For further details please see: http://www.e-t-a.de/ti_e Voltage rating AC 250 V*; 3 AC 433 V (50-60Hz); DC 65 V (*UL: AC 277/480 V; DC 65 V) Current rating range 0.1...25 A for curves M1, T1 0.1...16 A for curves F1, F2 1...16 A for curves M3 Auxiliary circuit 1 A, AC 240 V/DC 65 V, resistive (min. 10 V / 10 mA) Typical life 10,000 operations at 1 x IN, inductive Insulation co-ordination rated impulse pollution (IEC 60664 and 60664A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V main/aux. circuit AC 1,500 V aux. circuit 11-12/23-24 AC 1,000 V pole/pole AC 1,500 V Insulation resistance > 100 MΩ (DC 500 V) Interrupting capacity Icn 0.1...5 A 400 A 6...25 A 800 A curves F1, F2, M1, T1: 0.1...16 A 2,500A (at DC 32 V) curve M3: 1...2 A AC 200 A DC 400 A Interrupting capacity (UL 1077) Degree of protection operating area IP30 (IEC 60529/DIN 40050) terminal area IP00 Vibration curves F1, F2: 3 g (57-500 Hz), ± 0.23 mm (10-57 Hz) curves M1, M3, T1: 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc 10 frequency cycles/axis Shock curves F1, F2: 25 g (11 ms), directions 1, 2, 3, 4, 5 10 g (11 ms), direction 6 curves M1, M3, T1: 25 g (11 ms), directions 1, 2, 3, 4, 5 20 g (11 ms), direction 6 to IEC 60068-2-27, test Ea Corrosion 96 hours in 5 % salt mist to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Mass approx. 50 g per pole AC 277 V 1-pole 5,000 A 2,000 A AC 277/480 V 2-/3-pole 5,000 A 2,000 A DC 65 V 2,000 A 2,000 A Standard current ratings and typical internal resistance values Current rating (A) Internal resistance (Ω) F1 F2 M1 T1 M3 fast acting for DC only fast acting delay for AC+DC standard for AC+DC delayed low resistance only for AC standard delay 0.1 162 162 92 81 - Preferred types Standard current ratings (A) 1-pole: 1 2 4 6 8 10 16 2210-S211-P1F1-H111- x x x x x 2210-S211-P1M1-H111- x x x x x x x 2210-S211-P1M1-Z111- x x x x x x x 2-pole: 2210-S221-P1M1-H111- x x x x x x x 2210-S221-P1M1-H211- x x x x x x x Preferred types
Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de 2102 Installation drawing Dimensions 0 0 2 A 11 1224 Z 25° 25° OFF ON 10.5 683.5 .268 6x6.8 = 40.8 polarizing tooth 30.5 37.5 12.5 11.5 12.512.5 blade terminals DIN 46244-A6.3-0.8 (QC .250) 5.5 unit III unit II unit I ø11 multipole devices 12 3 .472 .217 .433 .630 1.26 1.97 6x.268 = 1.61 6.8 .394 2.68 .039 .413 .138 .748 1.69 1.48 .984 .492 .453 .492 .492 .709 1.20 mounting thread M3 max. screw length 5.8 mm (.228 in.) tightening torque max. 0.5 Nm 2 A 2 A operating area (reinforced insulation) mounting area (standard insulation) .197 .78711 122412 3 2 Cut-out dimensions ø11.5 12.5 12.5 3-pole 2-pole 1-pole 1.5 ø11.5 s90° recess with panel thickness 36.6 .453 .157 .630 1.26 1.44 .945 .492 .059 .453 This is a metric design and millimeter dimensions take precedence ( mm ) inch
Ordering information
Type No. 2210 single or multipole thermal-magnetic circuit breaker Mounting S socket or panel mounting Actuator design 2 toggle Number of poles 1 1-pole protected 2 2-pole protected 3 3-pole protected Panel mounting 1 with M3 thread Terminal design (main contacts) P1 blade terminals 6.3-0.8 (QC .250) Characteristic curve F1 fast acting: therm.1.01-1.4xIN;magn.2-4xIN DC (DC only) F2 fast acting: therm.1.01-1.4xIN; M1 standard delay: therm. 1.01-1.4xIN; magn. 6-12xIN AC;7.8-15.6xIN DC T1 delayed: therm. 1.01-1.4xIN; magn. 10-20xIN AC M3 standard delay, low resistance: therm.1.4-1.8xIN; magn. 6-12xIN AC; 7.8-15.6xIN DC Intermediate position H without intermediate position (standard) Z with intermediate position Auxiliary contacts 1 with auxiliary contacts in all poles 2 with auxiliary contacts in pole 1 (only multipole devices) not suitable for Module 17plus Auxiliary contact function (see diagram) 1 one each N/C and N/O (standard) 4 one N/O contact, closed in the intermediate and ON position (-Z only) Auxiliary contact - terminal design 1 same as main terminals Current ratings 0.1...25 A 2210 - S 2 1 1 - P1 F1 - H 1 1 1 - 10 A ordering example Please be informed that we have minimum ordering quantities to be observed. Approvals Authority Standard Rated voltage Current ratings VDE IEC/EN 60934
3 AC 433 V
0.1 A…25 A
CSA C22.2 No 235 AC 277/480 V AC 277 V DC 65 V DNV GL IEC60934, CG 0339
Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de2102 Thermal-Magnetic Circuit Breaker 2210-S2... Multipole devices: all poles symmetrically loaded. With single pole overload, thermal tripping will be at max. 1.7 x I N with curves F1, F2 and M1 at max. 2.2 x IN with curve M3. The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient °F temp. °C -22 -30 -20 +14 -10 +32 +73.4 +23 +86 +30 +104 +40 +122 +50 +140 +60 Trip time in seconds Trip time in seconds Trip time in seconds -F1 0.1…16 A DC only 0.001 12 46 81 02 0 40 10000 1000 100 0.1 0.01 6080100 -F2 8…16 A AC/ DC 1) 10000 0.001 0.001 12 46 81 0 20 40 1000 100 0.1 0.01 6080100 12 46 81 02 0 40 10000 1000 100 0.1 0.01 6080100 -F2 0.1…7.5 A AC/ DC 1) -30 °C -22 °F +23 °C +73.4 °F +60 °C +140 °F … times rated current … times rated current … times rated current 1) Magnetic tripping currents are increased by 30 % on DC supplies. Internal connection diagrams Typical time/current characteristics OFF position Intermediate position ON position line line line line line line I >I > 0 I (Z) 11 1 23 12 24 (Z) 11 12 3 12 24 (Z) 11 1 OFF position Intermediate position ON position I > 0I(Z) 12 3 0I(Z) 12 3
0 I(Z) 12 3
I >I > I > with auxiliary contact function 1 (one each N/O and N/C) with auxiliary contact function 4 (1 N/O, leading) Toggle positions OFF position intermediate positionO N position Shock directions current rating
Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de 2102 The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Multi pole devices: all poles symmetrically loaded. With single pole overload, thermal tripping will be at max. 1.7 x I N with curves F1, F2 and M1 at max. 2.2 x IN with curve M3. 1) Magnetic tripping currents are increased by 30% on DC supplies (curves F2, M1, M3). Ambient °F temp. °C -22 -30 -20 +14 -10 +32 +73.4 +23 +86 +30 +104 +40 +122 +50 +140 +60 -T1 8…25 A AC only 100 0.1 0.01
0.001 Trip time in seconds
… times rated current 100 0.1 0.01 … times rated current 100 0.1 0.01 … times rated current -M1 0.1…6 A AC/DC 1) -T1 0.1…6 A AC only-M1 8…25 A AC/DC 1) -M3 1…5 A AC/DC 1) -M3 6…16 A AC/DC 1) 100 0.1 0.01 … times rated current 100 0.1 0.01 … times rated current 100 0.1 0.01 … times rated current Typical time/current characteristics
Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de2102 Thermal-Magnetic Circuit Breaker 2210-S2... Accessories insulation to DIN 4102-B2 translucent Outer dimensions of female connectors to 6.3-1 DIN 46247 Ms-gal Sn max. 16 A 71 ± 1.5 33.2 blade terminal DIN 46244 A6.3-0.8 (QC .250), max. 25 A25 12.5 .315 1.31 2.79 ± .060 .984 .492 busbar max. 50 A 6 x 6.8 = 40.8 6 x .268 = 1.61 retaining clip 22.2 max. 30 3.5 6.8 4.4 7.4 12.56.25 12.5 polarized blade terminals DIN 46244-A6.3-0.8 (QC .250) .291 .173 .394 .827 .874 .079 .236 max. 1.18 2.52 .492 1.97 2.95 501.972.26 57.4 .268 .138 .492.246 slot for fitting labels from Phoenix, Weidmüller, Wieland slot for busbar module right-side terminal block left-side terminal block .4132.641.67 1.85 2.48 4.53 2.24 .984.236 .984 1.46 Module 17plus For technical data see section Power Distribution Systems 2-way mounting socket 6-way mounting socket 23-P10-Si 63-P10-Si (up to 16 A max. load) (retaining clip Y 302 974 01 available on request) Bus bar 50 A, 6-way, for type 63-P10-Si socket X 221 760 11 17 plus symmetrical rail EN 50022-35x7.5 G-profile EN 50035-G32 115 42.5 68 10.5 6 25 25 12 12
1 Line 1 Line
7.4 4.4 57.4 12.5polarized recess .173 .291 2.521.972.26 .492 .984 5.4 125 .669 .213 .354 4.92 cylinder head screw washer M4x4 ISO1207 nickel plated A 4.3 DIN 125 nickel plated female connector Phoenix terminal AKG 35 max.cross section 35 mm2 (AWG 2) 12.87 154.8 pressure-relief joint (1.1 mm (.043 in.) thick constriction) Cu rail, tin-plated .394 .079 .504.276 6.09 insulation to DIN 4102-B2 translucent Outer dimensions of female connectors to 6.3-1 DIN 46247 Ms-gal Sn max. 16 A blade terminal DIN 46244 A6.3-0.8 (QC .250), max. 25 A25 12.5 busbar max. 50 A .315 .984 .492 blade terminal DIN 46244 part 2 C profile (2xA2.8-0.8) (QC 2x.110) depth 10 mm (.394 in.) adapter X20040901 symmetrical rail EN 50022-35x7.5 polarization recess G-profile EN 50035-G32 8.525.86.5 33.3 1.4 12.5 41.3 45.8 retaining clip 2(k) 2(i) 2(k) 2(i) 1.801.6 .335 .256 1.02 3.15 1.31 .055 .1 .492 .394 polarized blade terminal DIN 46244-A6.3-0.8 (QC .250) slot for fitting labels from Phoenix, Weidmüller 6.3 -P10 2.8 -P70 .394 .248 .394 .110 Single mounting sockets (up to 16 A max. load) (with adapter) 17-P10-Si 17-P10-Si-20025 17-P70-Si 17-P70-Si-20025 (retaining clip Y 302 974 21 available on request) Bus bar (10-way) (supplied as a complete package) for type 17 socket (for max. 100 A continuous load), more positions available on request X 211 157 01 with terminal X 211 157 02 without terminal Bus bar 50 A (6-way) for type 17-P10-Si socket X 221 760 01 Insulating sleeving for bus bar (10-way) Y 303 824 01 71 ± 1.5 2.79 ± .060 33.2 1.31 This is a metric design and millimeter dimensions take precedence ( mm ) inch
Thermal-Magnetic Circuit Breaker 2210-S2... www.e-t-a.de 2102 Accessories .787 .039 3.6 32 ø3.5 9.5 2.5 R12 24R15 5.5 .217 .098 .591 .472 .945 .866 1.26 1.50 .142 .472 .138 .374 Toggle guard for 1-pole units, black X 221 617 01 Connector bus links -P10 X 210 588 01/ 1.5 mm2, (AWG 16), brown (up to 13 A max. load)2 X 210 588 02/ 2.5 mm2, (AWG 14), black (up to 20 A max. load) X 210 588 03/ 2.5 mm2, (AWG 14), red (up to 20 A max. load) X 210 588 04/ 2.5 mm2, (AWG 14), blue (up to 20 A max. load) ~70 100 quick-connect tabs 6.3 (.250) DIN 46247 tinned brass, insulated For front panel mounting. ~2.76 This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. 2.09 32±0.1 2pole 12.6±0.1 3pole 25.2±0.1 mounting holefixing plate Splash cover (transparent) with fixing plate and screws (IP54) for type 2210-S211-… (1-pole) X 211 117 02 Splash cover (transparent) with fixing plate and screws (IP54) for type 2210-S221-… (2-pole) and type 2210-S231-… (3-pole) X 211 118 01 max. 4 1.2 24.5 1.2 21 ø16.8 max. 2 fixing plate 53 25+0.340 mounting dimensions: M3 - hole dia. 3.5 mm/.138 in. mounting holes ø17+0,2 1.22 max .079 .661 .827.047 1.54 .748 1.26 .669+.008 1.26 1.50 max .157 .827.047 .965 1.26±.004 1.69 .984+.012 1.57 .496±.004 3pole .992±.004 Retaining clip for 2210-S to module 18plus Part no. Y30297431