M22-LED-W EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 3
Technical content
07/26/2016 216557 - HPL-ED2016 V24.0 EN 1 / 3 LEDelement,white,frontmount,12-30VAC/DC Partno. M22-LED-W Articleno. 216557 CatalogNo. M22-LED-WQ Deliveryprogramme Product range RMQ-Titan (drilling dimensions 22.5 mm) Basic function LED elements Single unit/Complete unit Single unit Fixing Front fixing Connection technique Screw terminals Rated operational voltage Ue V 12 - 30 V AC/DC, 50/60 Hz Ratedoperationalcurrent Ie mA 8 - 15 Power consumption Pmax. W 0.26 at 24 V Colour White Degree of Protection IP20 Connection to SmartWire-DT no Notes For indicator lights, illuminated pushbutton actuators, and illuminated selector switch actuators, the following applies: M22…-B in combination with M22-LED…-W or M22-LED…-B Technicaldata General Standards IEC/EN 60947 VDE 0660 Operating torque (screw terminals) Nm 0.8 Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Open °C -25 - +70 Storage °C - 40 - + 80 Mounting position As required Mechanical shock resistance g 30 Shock duration 11 ms Sinusoidal according to IEC 60068-2-27 Terminal capacities mm2 Solid mm2 0.75 - 2.5 Stranded mm2 0.5 - 2.5
07/26/2016 216557 - HPL-ED2016 V24.0 EN 2 / 3 Contacts Rated impulse withstand voltage Uimp V AC 6000 Rated insulation voltage Ui V 500 Overvoltage category/pollution degree III/3 Indoor and protected outdoor installation DesignverificationasperIEC/EN61439 Technical data for design verification Rated operational current for specified heat dissipation In A 0 Heat dissipation per pole, current-dependent Pvid W 0 Equipment heat dissipation, current-dependent Pvid W 0 Static heat dissipation, non-current-dependent Pvs W 0.45 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. °C -25 Operating ambient temperature max. °C 70 IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed. TechnicaldataETIM6.0 Low-voltage industrial components (EG000017) / Lamp holder block for control circuit devices (EC000204) Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Bulb socket block for command and alarm devices With integrated transformer No With integrated voltage decreasing resistor No With integrated lamp Yes With integrated diode Yes Lamp holder None Rated voltage Ue at AC 50 Hz V 0 - 0 Rated voltage Ue at AC 60 Hz V 0 - 0 Rated voltage Ue at DC V 30 - 30
07/26/2016 Eaton Industries GmbH http://www.eaton.eu © 07/2016 by Eaton Industries GmbH 216557 - HPL-ED2016 V24.0 EN Voltage type for actuating AC/DC Type of lamp LED Connection type auxiliary circuit Screw connection Colour lamp White Type of fastening Front fastening Approvals Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking UL File No. E29184 UL Category Control No. NKCR CSA File No. 012528 CSA Class No. 3211-03 North America Certification UL listed, CSA certified Degree of Protection UL/CSA Type: - Dimensions A = 37.2 Pushbutton with M22-(C)K… Pushbutton with M22-(C) LED… + M22-XLED… Additionalproductinformation(links) IL04716002Z(AWA1160-1745)RMQ-TitanSystem IL04716002Z (AWA1160-1745) RMQ-Titan System ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716002Z2015_02.pdf