199BM2X-14 SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Power relay, SE Relays, DPDT, 40A, 120 VDC, magnetic blowout, auxiliary switch, open type Main Product Type Power relay Switch Function DPDT Contact Composition 2 C/O Contact Blow-out Type Magnetic Accessory Type Auxiliary switch Cover Type Open cover Complementary Input Current 40 A Contacts Material Silver alloy contacts Rated Operational Voltage 6...600 V AC 50-60 Hz 6...250 V DC Minimum Switching Current 1000 mA 5 V AC/DC Coil Resistance 6000 Ohm Drop-out Voltage Threshold >= 0.1 Uc AC/DC Rated Operational Current 40 A at 300 V AC (on resistive load) conforming to UL

40 A at 28 V DC (on resistive load) conforming to UL

20 A at 110 V DC (on resistive load) conforming to UL

8 A at 220 V DC (on resistive load) conforming to UL

4 A at 325 V DC (on resistive load) conforming to UL

2 A at 500 V DC (on resistive load) conforming to UL

Power consumption in W 4 W DC Power consumption in VA 10 VA AC Maximum Switching Voltage 600 V DC Motor Power HP 2 hp 120...600 V AC 50/60 Hz Connections Terminals screw terminal Wire Range AWG 14 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Aug 2, 2021

Ambient Air Temperature for Operation Ambient Air Temperature for Storage -67…212 °F (-55…100 °C) Product Certifications UL Listed CSA CE Electrical Durability 100000 cycles resistive DC load Dielectric Strength 2200 V AC between coil and contact

2200 V AC between poles

1500 V AC between open contacts

Ordering and shipping details GTIN 03606481104823 Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration REACh free of SVHC Yes EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Toxic heavy metal free Yes Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Connections and Wiring Diagrams