www.e-t-a.de Module 17plus 2409

Description

Module 17plus is a mounting and power distribution system for use with the following plug-in type devices: l 2210-S, 3600 and 3900 circuit breakers l ESS30-S, ESX10 and ESX10-S electronic circuit breakers and protectors l E-1048-S7... solid state remote power controller Each module accommodates two breakers with an individual housing width of 12.5 mm and fits onto all industry standard mounting rails. The two-way modules are mounted side-by-side to provide as many ways as required with a terminal block fitted at each end for connection of signalling circuits. Electrical connections are by means of screwless spring-loaded terminals. Fitting a busbar on the terminal side of the modules provides power distribution onto the individual ways with a common line entry. When plugging in multipole circuit breakers, the busbar cannot be used. In this case each pole has to be individually connected. All internal wirings for the ground potential and the group signal are established by the side-by-side mounting of the individual modules (centre pieces, terminal blocks). The suitable circuit breakers or SSRPCs have integral signal contacts (break and make contacts). Depending on the application they can be used for single or group signalling. When using multipole breakers, auxiliary contacts are required in each pole so as not to interrupt the current loop of the group signalling by missing auxiliary contacts. Fitted with 2210-S: The integral auxiliary contacts of thermal–magnetic circuit breaker type 2210-S (make and break) can be used for single or group signalling, depending on the application. For group fault signalling all required terminals (make contacts, they open in the event of a failure) within the Module 17plus are connected in series. Group signalling is realised via the terminals on the side (13, 14). Single signalling requires connection of the break contacts (they close in the event of a failure). In this case one side of the contacts in the modules is connected in parallel (pin 11). The second contact side is accessible per module way and can be connected via terminal (pin 12). Both types of signalling are available at the same time, if the circuit breaker type used has auxiliary contacts (please note when ordering). Fitted with 3600/3900: The integral auxiliary contacts of thermal–magnetic circuit breaker types 3600/3900 (make and break) can be used for single or group signalling, depending on the application. For group fault signalling all required terminals (make contacts, they open in the event of a failure) within the Module 17plus are connected in series. Group signalling is realised via the terminals on the side (13, 14). Single signalling requires connection of the break contacts (they close in the event of a failure). In this case one side of the contacts in the modules is connected in parallel (pin 11). The second contact side is accessible per module way and can be connected via terminal (pin 12). Both types of signalling are available at the same time. Fitted with ESS30-S: The reference potential for the ESS30-S.. (Gnd pin 11) is also looped through and connected to the terminal elements at the sides. All internal wirings for the ground potential and the group signal are established by the side-by-side mounting of the individual modules (centre pieces, terminal blocks). The ESS30-S003 features an integral auxiliary contact (change-over). The contact SC-SO is used for the group fault indication. For this type of signalling, all contacts in the Modules 17plus are connected in series and are connected via two terminals (13, 14) to the terminals blocks on either side. It is possible with a test probe to contact the series connection in each module and detect possible interruptions. Fitted with ESX10/ESX10-S: The reference potential for the ESX10 (Gnd pin 11) is also looped through and connected to the terminal elements at the sides. The integral signal output SF of the ESX10-124/-S124 can be tapped at terminal 12 of the relevant channel (single signalling). The inverted status output SF can also be tapped at terminal 12 of the corresponding channel. The reset input RE can be connected via terminal 13 or 14 ( ESX10-124/S124/-127/-S127) or terminal 12 (ESX10-125/-S125). The integral control input IN+ of type ESX10- 115/-S115 is fed in via terminal 12. Depending on the option, a potential-free auxiliary contact is also available (ESX10-103/-115/- Fitted with E-1048-S7xx: The reference potential (Gnd pin 11) is also looped through and connected to the terminal elements at the sides. Actuation of the SSRPC (IN+), referenced to GND), is via the separate terminal 12 per way beside the LOAD terminal. The SSRPC has an integral auxiliary contact (break contact) used for group fault signalling. For this type of signalling, all contacts in the Modules 17plus are connected in series and are connected via two terminals (13, 14) to the terminals blocks on either side. It is possible with a test probe to contact the series connection in each module and detect possible interruptions. All internal wirings for the ground potential and the group signal are established by the side-by-side mounting of the individual modules. 17plus

2210-S/3600/3900 Module 17plus www.e-t-a.de Module 17plus 2409 Installation example (with type 2210) 1 Clip modules onto DIN rails. 2 Push modules together (side-by-side). 3 Snap on right-side and left-side terminal blocks. 4 Cut busbar to required length and fit on supply side of the modules. 5 Connect line feed with spring-loaded terminals. 6 Plug in circuit breakers. Installation: LOAD LOAD

1 LINE

1 Line 1 Line

Connection and disconnection of cables with screw driver 13 14 12 12 SD 3 SD 1 SD 1 SD 0 Technical data Connection Spring-loaded terminals for rigid wires or flexible cables with unisolated wire end ferrules or without wire end ferrules. Please use appropriate screw driver size (SD) for removing the spring loaded terminals. cable cross section of connecting cable screw driver stripped length Line feed Load output Signalisation terminals (11, 13, 14) 0.25-2.5 mm2 1 (0.6 x 3.5) 10 mm Signalisation 2.5) 9 mm Diameter of test socket ø ≤ 2 mm Voltage rating (without circuit breaker) with 2210-S: with 3600/3900: with ESX10/ ESX10-S: with E-1048-S7..: with ESS30: AC 250 V; 3 AC 433 V; DC 65 V AC 250 V; 3 AC 433 V; DC 65 V AC 240 V (50/60 Hz); DC 65 V 18 V...32 V DC 18 V...36 V DC 18 V...30 V DC Current rating (without circuit breaker) Line feed (1.1/1.2) 50 A Load output (2.1/2.2) 25 A Signalisation Feed (11) (ground with electronic components) 10 A Single output (12.1/12.2) 1 A (with ESX10: 0,5 A) Group signal (13-14) 1 A (with ESX10: 0,5 A) Caution: When several devices are mounted together, each should carry only max. 80 % ( IN ≤ 16 A) or max. 65 % (IN > 16 A) of its rating. Internal resistances (without circuit breaker) Line/load (1.1-2.1) ≤ 5 mΩ Signalisation ≤ 9 mΩ (+ 2 mΩ per additional module) Group signal (13- 14) ≤ 8 mΩ (+ 5 mΩ per additional module) Vibration 5 g (57-500 Hz) ± 0,38 mm (10-57 Hz); to IEC 60068-2-6, test Fc, 10 frequency cycles/axis Shock 25 g (11 ms) to IEC 60068-2-27, test Ea 11 ms half sine Corrosion 96 hours at 5 % salt mist, to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Dielectric strength between main circuits (without busbar): 1 500 V main circuit to auxiliary circuit: 1 500 V between auxiliary circuits: 1 500 V (without circuit breaker) Mass Module 17plus (centre piece) approx. 85 g terminal blocks (pair) approx. 30 g

Ordering information

17PLUS-Q02-00 Module 17plus, centre piece 17PLUS-QA0-LR two-way one each left- and right-side terminal block for supply feed from the side by means of screw terminal For technical data of: l 2210-S, 3600, 3900 l ESS30-S, ESX10, ESX10-S l E-1048-S7 Please use the search function of www.e-t-a.de by entering the product group (e.g. 2210-S) to view individual data sheets. Authority Standard Rated voltage Current ratings UL UL 60950 AC 250 V DC 80 V

25 A per channel

www.e-t-a.de 2210-S/3600/3900 Module 17plus 2409 Module 17plus Dimensions (with type 2210) Dimensions (with type 3600/3900) slot for fitting labels from Phoenix, Weidmüller, Wieland slot for busbar module right-side terminal block test socket left-side terminal block .4132.641.67 1.85 2.48 4.53 2.24 .984.236 .984 max. 1.50 17 plus symmetrical rail EN 50022-35x7.5 G-profile EN 50035-G32 115 42.5 68 10.5 6 25 25 max. 38 12 12 EN 50022-35x7,5 EN 50035-G32115 42,5 51 11,5 6 25 25 max. 38 17 plus 2.2 12.1 12.2 1.2 Line 1.1 Line 2.1 slot for fitting labels from Phoenix, Weidmüller, Wieland slot for busbar module right-side terminal block left-side terminal block symmetrical rail G-profile test socket Module 17plus For technical data see section Power Distribution Systems 13, 14 A 12.1, 12.2 A LOAD 2.1 LINE 1.1 12.1 12.1 LINE 1.2 LINE 1.1 LINE 1.2 terminals for group signalisation feed for single signalisation terminal for single signalisation module 1 module 2 busbar circuit breaker test socket left-side terminal block right-side terminal block Supply Example for circuit breaker types 2210 For connection diagram for electronic circuit breakers and components please see relevant data sheets of types ESS20, ESS21, E-1048-7.. jumper 13, 14 A 12.1, 12.2 A LOAD 2.1 LINE 1.1 12.1 12.1 LINE 1.2 LINE 1.1 LINE 1.2 terminals for group signalisation feed for single signalisation terminal for single signalisation module 1 module 2 busbar circuit breaker test socket left-side terminal block right-side terminal block Supply Example for circuit breaker types 3600/3900 For connection diagram for electronic circuit breakers and components please see relevant data sheets of types ESS20, ESS21, E-1048-7.. jumper Connection diagram 2210-S Connection diagram 3600/3900 2210-S.. Module 17plus 2 (1.1, 1.2) 12 (11) 24 (13) 23 (14) 11 (12.1, 12.2) 1 (2.1, 2.2) 3600/ 3900 Module 17plus 1 (1.1, 1.2) 4 (11) 6 (13) 3 (N.C.) 7 (14) 5 (12.1, 12.2) 2 (2.1, 2.2) Pin selection, fitted with 2210-S.. Pin selection, fitted with 3600/3900

www.e-t-a.de ESS30-S003 - Module 17plus 2409 Dimensions (with type ESS30-S) 115 slot for busbar module right-side terminal block left-side terminal block symmetrical rail EN 50022-35x7,5 GERMANY ON 115,2 (OFF 121,2) 12,5 66 25 ESS30-S003 Module 17 plus GND (11) SC (13) S0 (14) SI (12.1, 12.2) Pin selection, fitted with ESS30-S003 module 1m odule 2 busbar right-side terminal block jumper Supply left-side terminal block LINE 1LINE 1 LOAD 21 2

11 GND

13, 14 terminal for group signalisation LOAD 2 12 LOAD 2 12 LOAD 21 2 ESS30-S003 LINE 1 LINE 1 GND GND test socket test socket Connection diagram ESS30-S003

www.e-t-a.de ESX10 - Module 17plus 2409 ESS30-S003 - Module 17plus Dimensions (with type ESX10) ESX10-124 Module 17 plus GND (11) RE (13) RE (14) SF (12.1, 12.2) Pin selection, fitted with ESX10-124 (example) Module 17plus with ESX10-100 LINE 1LINE 1 LOAD 21 2LOAD 2 module 1

12 LOAD 2

12 LOAD 21 2

left-side terminal block right-side terminal block Supply LINE 1 LINE 1 GND GND jumper 13, 14 looped through 12, 13, 14 terminal group signalisation (change-over) Module 17plus with ESX10-103/ESX10-S103 LINE 1LINE 1 LOAD 21 2LOAD 2 12 LOAD 2 12 LOAD 21 2 ESX10-103/ESX10-S103 LINE 1 LINE 1 >i >i >i>i >i >i>i >i module 1 module 2 busbar left-side terminal block right-side terminal block Supply >i>i GND GND jumper Module 17plus with ESX10-104 LINE 1LINE 1 LOAD 21 2LOAD 2 module 1 left-side terminal block right-side terminal block Supply LINE 1 LINE 1 GND GND jumper 12 status indication SF +24V=O K 13, 14 looped thr ough (+) (+) (+) Connection diagram ESX10-... LINE (+) LOAD (+) Gnd RE RE SI I > ok on / off Control unit Failsafe slot for busbar module right-side terminal block left-side terminal block slot for fitting labels from Phoenix, Weidmüller, Wieland 115 42.5 70 6 25 25 max. 38 17 plus 12 12 EN 50022-35x7.5 2.75 1.85 1.67 2.48 4.53 2.24 .236 max. 1.50 .984 .984 Module 17plus for ESX10-1xx For technical data please see product group Power Distribution Modules

E-1048-S7xx - Module 17plus www.e-t-a.de ESX10 - Module 17plus 2409 Connection diagram ESX10-... 12.1, 12.2 terminal control signal ON (+24V DC) 13, 14 terminal group signalisation (N/O) Module 17plus with ESX10-115/-S115 LINE 1.2LINE 1.1 ESX10-115/-S115 LINE 1.2 >i>i >i >i>i >i >i>i >i module 1 module 2 busbar left-side terminal block right-side terminal block Supply >i>i GND GND jumper (+) (+) (+) Module 17plus with ESX10-124/-S124 module 1 module 2 busbar ESX10-124/-S124 left-side terminal block right-side terminal block Supply LINE 1.1 GND GND jumper* 12.1, 12.2 status indication SF +24V=O K 13, 14 reset input RE ( group r eset), +24V falling edge *Caution: unused slots have to be fitted with jumpers (+) (+) (+) (+ ) (+ ) (+ ) 12.1, 12.2 reset input RE (single r eset), +24V falling edge 13, 14 terminal group signalisation (N/O) *Caution: unused slots have to be fitted with jumpers Module 17plus with ESX10-125/-S125 LINE 1.2LINE 1.1 ESX10-125/-S125 LINE 1.1 >i >i >i>i >i module 1 module 2 busbar left-side terminal block right-side terminal block Supply >i>i GND GND jumper* (+ ) (+ ) (+ ) LINE 1.2 LINE 1.1 LINE 1.2 Module 17plus with ESX10-127/-S127 module 1 module 2 busbar ESX10-127/-S127 left-side terminal block right-side terminal block Supply LINE 1.1 GND GND jumper* 12.1, 12.2 status indication SF 0V=OK 13, 14 reset input RE ( group r eset), +24V falling edge *Caution: unused slots have to be fitted with jumpers (-) (-) (-) (+ ) (+ ) (+ ) LINE 1.2 LINE 1.1 LINE 1.2LINE 1.1 LINE 1.2

www.e-t-a.de E-1048-S7xx - Module 17plus 2409 ESX10 - Module 17plus Dimensions (with type E-1048-S7xx) 13, 14 terminals for group signalisation 11 reference potential GND 12 control IN+ right-side terminal block LOAD LOAD IN +

1 LINE + 1 LINE +

1 LINE +1 LINE +

E-1048-S7.. Module 17plus LINE + (1.1, 1.2) GND (11) SC (13) SO (14) IN+ (12.1, 12.2) LOAD+ (2.1, 2.2) Connection diagram E-1048-S7xx Pin selection, fitted with E-1048-S7.. slot for busbar module right-side terminal block left-side terminal block slot for fitting labels from Phoenix, Weidmüller, Wieland symmetrical rai EN 50022-35x7,5 G-profile EN 50035-G32115 42,5 70 6 25 25 max. 38 17 plus 2.2 12.1 12.2 1.1 Line1.2 Line 2.1 Modul 17plus For technical data see section Power Distribution Systems

www.e-t-a.de Module 17plus 2409 Accessories mounting dimensions mounting dimensions 61.5 Busbar 32 A X 222 005 01 blue insulation, 500 mm/19.68 in. X 222 005 02 red insulation, 500 mm/19.68 in. X 222 005 03 grey insulation, 500 mm/19.68 in. up to 32 A continuous load Busbar 50 A Y 307 016 01 non-insulated, 500 mm/19.68 in. up to 50 A continuous load; plugged in completely, protected against brush contact Busbar 50 A Y 307 016 11 non-insulated, 500 mm/19.68 in. up to 50 A continuous load End bracket X 222 004 01 Width 10 mm Screw terminal for busbar X 211 156 01 non insulated (up to 35 mm2) Retaining clip for circuit breaker 3600/3900 recommended for fitting the devices Y 300 581 11 5.5 44.4 Retaining clip for circuit breaker 2210 recommended for fitting single pole devices Y 302 974 21 .039 .945 .276 .039 1.18 .217 2.36 2.42 1.77 1.74 1.77 2.36 Labels marking area 6 x 10 mm (ordering unit 10 pcs = 1 strip) Y 307 942 61 blade terminals DIN 46244-A 6.3-0.8 2.36 010.3 12.3 terminals 13+14 bridged Signalbrücke Signal loop Germany www.e-t-a.com Signalbrücke Signal loop xxxx SB-S11-P1-01-1-1A Jumper SB-S11-P1-01-1-1A .484 .406 2.76 top view AC 240 V / DC 65 V, 1 A 18.5 4.5 Retaining clip Y 307 754 01 recommended for tight fit of types ESX10 .728 .177 .315 .079 .197 2.52 64.52.54 Retaining clip Y 308 792 01 recommended for tight fit of types ESX10 / E-1048-S6xx / SB-S11-P1-xx and terminal blocks type 17 and 17plus

www.e-t-a.de Module 17plus 2409 Module 17plus Installation example for retaining clip Removal of retaining clip Y 307 754 01 ESX10 with retaining clip Y 307 754 01 for power distribution system module 17plus Installation example for busbar When mounting several modules side by side, proper insertion of the 32 A busbar X 222 005 01/02/03 has to be observed, i.e. the busbar must be pushed in evenly across the whole length from left to right, repeatedly if necessary. The groove of the busbar must be flush with the top edge of the Module 17plus. Please ensure that the busbar audibly latches in into the Module 17plus. top edge 17plus groove nose Installation for busbar 32 A (X222 005 01/02/03) in Module 17plus All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.