17CE MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

MODEL: 17CE http://www.m-system.co.jp/ 17CE SPECIFICATIONS ES-2937 Rev.0 Page 1/2 Rack-mounted Power Transducers 17-RACK AC CURRENT TRANSDUCER Functions & Features

  • Converting an alternating current from a current transformer into a standard process signal
  • Minimum ripple
  • True RMS sensing Typical Applications
  • Centralized monitoring and control of motors, pumps or heaters by DCS
  • Monitoring power line and power supply current MODEL: 17CE–[1]6-R

ORDERING INFORMATION

  • Code number: 17CE-[1]6-R Specify a code from below for [1]. (e.g. 17CE-56-R) [1] INPUT Current 1: 0 – 1 A AC 5: 0 – 5 A AC OUTPUT Voltage 6: 1 – 5 V DC (Load resistance 2000 Ω min.) AUXILIARY POWER SUPPLY DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) GENERAL SPECIFICATIONS Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided Connection Input: M3.5 screw terminals (torque 0.8 N·m) Output: Connector Auxiliary power: Supplied from connector Screw terminal: Nickel-plated steel Isolation: Input to output to auxiliary power Input waveform: Up to 15 % of 3rd harmonic content Overrange output: 0 to 120 % Zero adjustment: -5 to +5 % (front) Span adjustment: 95 to 105 % (front) INPUT SPECIFICATIONS Frequency: 50 or 60 Hz Input burden: 0.1 VA (input 0 – 1 A), 0.5 VA (input 0 – 5 A) Overload capacity: 400 % of rating for 1 sec., 120 % continuous Operational range: 0 – 120 % of rating OUTPUT SPECIFICATIONS 2.5 5A 0
  • Operation Diagram (example) OUT IN INSTALLATION Auxiliary power supply Current consumption: Approx. 35 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 40 to 85 % RH (non-condensing) Mounting: Standard Rack 17BXE Weight: 150 g (0.33 lb) PERFORMANCE in percentage of span Accuracy: ±0.4 % (at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz) Response time: ≤ 1 sec. (0 – 100 % ±1 %) Ripple: 1 %p-p max. Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 500 V AC @ 1 minute (output to auxiliary power)

1500 V AC @ 1 minute (input to output or auxiliary power to

ground)

MODEL: 17CE http://www.m-system.co.jp/ 17CE SPECIFICATIONS ES-2937 Rev.0 Page 2/2 CONNECTION DIAGRAM OUTPUT AUXILIARY POWER k l CT L K LOAD SOURCE CONNECTOR DIMENSIONS unit: mm (inch) 110 (4.33 ) 93 (3.66) 24 (.94) 7 (.28) 78 (3.07)32 (1.26) 8–M3.5 SCREW 7 (.28) 2–M3 SCREW TERMINAL ASSIGNMENTS 1 2 3 4 7 8 5 6 Specifications are subject to change without notice.