1659-G21 ETAL | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Thermal Overcurrent Circuit Breaker 1659-... www.e-t-a.de050215
Description
Ordering information Technical data Single pole thermal reset circuit breaker in a miniaturised design intended for thread neck mounting. Easy and quick reset after tripping due to overcurrent. Trip-free mechanism and automatic disconnection in the event of an overcurrent, even with a blocked actuator button. R-Type TO CBE to EN60934. Very cost effective design to meet international requirements. l Manual reset, trip free mechanism l Extremely small and lightweight Power tools, Industrial equipment, Medical equipment, Power generators, Motors, Battery chargers, UPS. 1659-... Standard current ratings and typical resistance Type No. 1659 single pole thermal circuit breaker, black body Threadneck design G11 M11x1,0 (Plastic), white push-to-reset button G12 M11x1,0 (Plastic), black push-to-reset button G21 3/8“-24 UNF (Plastic), white push-to-reset button G22 3/8“-24 UNF (Plastic), black push-to-reset button Hardware 00 no hardware 01 one integrated knurled nut (plastic), Y 310 777 01 for M11, Y 310 778 01 for 3/8“, bulk Terminals P10 blade terminals A6.3-0,8 (QC .250) P13 blade terminals A6.3-0,8 (QC .250), 90° S83 bent screw terminals 8-32 UNC Current ratings Approvals Current rating (A) Typical Resistance (Ω) Current rating (A) Typical Resistance (Ω) 5 A 0.225 12 A 0.125 6 A 0.175 15 A 0.050 7 A 0.175 20 A 0.040 8 A 0.175 25 A 0.030 10 A 0.125 30 A 0.020 Voltage rating AC 250 V, DC 32 V Current ratings 5...30 A Typical life 500 operations at 1.5 x In resistive AC 125 V Behaviour at rated switching capacity (EN 60934; test sequence D) operat. I N UN 40 5...25 A AC 250 V 6 x In ind. 40 5...30 A AC 250 V 6 x In resis. 40 5...30 A DC 32 V 4 x In ind. Ambient temperatur -10 °C to +60 °C (+14...+140° F) Insulation co-ordination (IEC 60664) 2,5 kV/2 reinforced insulation in operating area Dielectric strength operating area test voltage AC 3,000 V Insulation resistance > 500 MΩ Interrupting capacity (I cn) IN UN 5...30 A AC 250 V 6 x In 5...30 A DC 32 V 6 x In Interrupting capacity (UL 1077) IN UN INC 5...30 A AC 250 V 1000 A, C, 1 5...30 A AC 250 V 400 A, U, 3 5...30 A DC 50 V 300 A, C, 1 Degree of protection (IEC 60529) operating area IP40 terminal area IP00 Vibration 57 Hz acceleration 30m/s 2 (3 g) in X.Y.Z. direction (2 timesl/min.) Shock 300m/s2 (30 g) in X.Y.Z. direction Mass approx. 22 g Authority Standard Voltage rating Current ratings UL UL 1077 (E67320) AC 250 V DC 50 V 5 A...30 A 5 A...30 A TÜV SÜD EN 60934 IEC 60934 AC 250 V DC 32 V 5 A...30 A 5 A...30 A UL UL 1500 AC 250 V DC 50 V 5 A...30 A 5 A...30 A
Thermal Overcurrent Circuit Breaker 1659-... www.e-t-a.de 050215 Dimensions Installation drawing Internal connection diagram Panel cut out Terminal design 7.5 M11 *P1.0 12.8 .504 .157 3.2 1.22 6.3 .248 21.5 4-Ø3.0 .846 9.8 .386 1.38 6.0 3/8-27T .236 12.7 .500 0.8 .031 .126 11.8 .46514.4 .567 .295 1.38 9.4 .370 14.4 .567 8.4 .331 LINE A LOAD 1659 XXA 125/250VAC 125/250VAC 32VDC Suppl.Prot. 50/60Hz TC2/OL0/C1C R US T.V.U SUD.. S China 1659-G11/-G12 1659-G21/-G22 A 5 5 mounting area operating area 34 7 .276 .197 .197 1.34 .157 .157 LINE LOAD 9.9 Ø 10.8 Ø .425 Ø 9.6 Ø .378 .390 8.6 .339 1659-G11/-G12 1659-G21/-G22 6.3 .248 6.3 .248 3.2 .126 21.5 .846 5.4 .213 2.6 .102 0.8 .031 21.5 4-Ø3.0 .846 0.8 .031 4-Ø3.0 6.3 .248
21.5 Screw 8-32
.846 5.4 .213 3.2 .126 11.8 .4653.5 .138 2.6 .102 0.8 .031 LINE LOAD ...-P10 ...-P13 LINE LOAD ...-S83 LINE LOAD This is a metric design and millimeter dimensions take precedence ( mm ) inch
Thermal Overcurrent Circuit Breaker 1659-... www.e-t-a.de050215 Thermal Overcurrent Circuit Breaker 1659-... The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient temp. °F Ambient temp. °C +14 -10 +32 +50 +77 +95 +104 +122 +140 … times rated current Trip time in seconds 10000 5...16 A 1000 100 0.1 0 123 45 67 89 10 … times rated current Trip time in seconds 10000 17...30 A 1000 100 0.1 0 123 45 67 89 10 Typical time/current characteristics Accessories Plastic Nut Ref. Y 310 777 01 Nuts Plastic Nut Ref. Y 310 775 01 Plastic Nut Ref. Y 310 778 01 Plastic Nut Ref. Y 310 776 01 .732 Ø 18.6 .126 3.2 M11 *P1.0 .570 Ø 14.5 .110 2.8 M11 *P1.0 .732 Ø 18.6 .126 3.2 3/8-27T .570 Ø 14.5 .110 2.8 3/8-27T Ref. X 223 358 01 Watersplash protection Ref. X 223 357 01 .768 19.5 .213 5.4 M11 *P1.0 M11 15.8 .622 Ø 18.7 Ø .736 .669 Ref. X 223 355 01 3/8-27T 15.8 .622 Ø 18.3 Ø .720 Ø 13 This is a metric design and millimeter dimensions take precedence ( mm ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.
www.e-t-a.de 050215