Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Battery module (device with battery), VRLA-AGM, 24 V DC, 110 Ah Product description For continuous monitoring and intelligent management, there is constant communication with the QUINT UPS. Thanks to automatic detection of the battery module and tool-free switching during operation, quick installation is possible. The battery modules for QUINT UPS with IQ Technology are fully charged before being sent to our warehouse. Commercial data Item number 1474660 Packing unit 1 pc Minimum order quantity 1 pc Sales key CM24 Product key CMUEV3 GTIN 4063151887711 Weight per piece (including packing) 68,660 g Weight per piece (excluding packing) 68,000 g Customs tariff number 85072080 Country of origin CN UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 1 (9)
Note on the battery This product contains a battery with a limited shelf life that must be charged every few months. The product packaging indicates when the battery must be started up or recharged. The general shelf life can be found in the energy storage devices area under “Latest startup”. Energy storage Input Input voltage 24 V DC (SELV) Nominal capacity 110 Ah Charging current 32.4 A End-of-charge voltage 27.6 V (20 °C) Output Output current max. 45 A Output fuse 2x 25 A 280 min (20 A)Buffer time 130 min (40 A) General yesConnection in parallel max. 3 Battery type BB Battery BP MPL110-FR Battery technology VRLA-AGM IQ-Technology yes Latest startup date (battery only) 12 Months (0 °C ... 20 °C) Accumulator module service life (according to Eurobat) 10 (20 °C) Size designation Block Battery pack yes Suitable for fast charging yes Temperature sensor yes Connection data Conductor connection Connection method Push-in connection 10 mm² ... 16 mm² (recommended)rigid 0.75 mm² ... 16 mm² 10 mm² ... 16 mm² (recommended)flexible UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 2 (9)
0.75 mm² ... 16 mm² 8 ... 4 (recommended)AWG 20 ... 4 Stripping length 18 mm Conductor connection Connection method Push-in connection rigid 0.75 mm² ... 16 mm² (LIN) flexible 0.75 mm² ... 16 mm² (LIN) AWG 20 ... 4 Stripping length 18 mm Product properties Product type Battery module Product family Battery module (device with battery) Disposal Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. Insulation characteristics Protection class III Degree of pollution 2 Dimensions Item dimensions Width 350 mm Height 214 mm Depth 332 mm Drill hole Diameter 5 mm Installation dimensions Installation distance right/left 0 mm / 0 mm Installation distance top/bottom 50 mm / 50 mm Mounting Mounting type Base mounting Cable/line Battery connecting cable: Cable cross section 6 mm² Cable length 265 mm Color red/black Battery connecting cable: UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 3 (9)
Cable cross section 6 mm² Cable length 265 mm Color red/black Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (storage/transport) -20 °C ... 40 °C Ambient temperature (charge) 0 °C ... 50 °C Ambient temperature (discharge) -20 °C ... 50 °C Max. permissible relative humidity (operation) ≤ 95 % Ex data Suited for EX-applications no UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 4 (9)
Current 5 6 7 8 9 10 20 30 40 45 50 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 50 100 Buffertime Minutes Hours 1 2 3 4 1 A 2 A 3 A 5 A 7 A 10 A 15 A 20 A 25 A 30 A 35 A
40 A 2x2x2x
2x: In this case, two battery modules of the same capacity are required. The data is based on an ambient temperature of +25 °C at the start of use. 1274520 UPS-BAT/PB/24DC/1.2AH
1274117 UPS-BAT/PB/24DC/4AH
1274118 UPS-BAT/PB/24DC/7AH
1274119 UPS-BAT/PB/24DC/12AH 1474660 UPS-BAT/PB/24DC/110AH
1348516 UPS-BAT/PB/24DC/20AH
1354641 UPS-BAT/PB/24DC/40AH
Lead battery buffer times for QUINT DC UPS UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 5 (9)
Current 5 10 20 30 40 45 50 1 2 3 5 8 10 15 24 40 60 Buffertime Minutes Hours 1 2 3 15 W 35 W 55 W 90 W 125 W 180 W 275 W 400 W The data is based on an ambient temperature of +25 °C at the start of use.
1274119 UPS-BAT/PB/24DC/12AH 1354641 UPS-BAT/PB/24DC/40AH
1348516 UPS-BAT/PB/24DC/20AH 1474660 UPS-BAT/PB/24DC/110AH
Lead battery buffer times for QUINT AC UPS 500 VA Graphic Load Current 4 5 8 10 15 20 25 30 40 50 1 1.5 2 3 4 6 9 10 15 20 24 40 Buffertime Minutes Hours 1 2 3 100 W 200 W 300 W 400 W 500 W 600 W 700 W 800 W 900 W 2x 2x 2x: There are always two battery modules of the same capacity are required . The data is based on an ambient temperature of +25 °C at the start of use. Buffer times for QUINT AC UPS 1 kVA UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 6 (9)
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1474660 cULus Listed Approval ID: E123528-20220210 IECEE CB Scheme Approval ID: DK-124876-M1-UL cULus Listed Approval ID: E199827-20220302 UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 7 (9)
ECLASS-11.0 27050403 ECLASS-13.0 27050403 ETIM ETIM 9.0 EC000357 UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 8 (9)
Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 7(a), 7(c)-I China RoHS EFUP-10Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC REACH candidate substance (CAS No.) Lead(CAS: 7439-92-1) Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com UPS-BAT/PB/24DC/110AH - Battery module 1474660 https://www.phoenixcontact.com/us/products/1474660 Mar 24, 2025, 8:04 AM Page 9 (9)