1472132 PHOENIX | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 11
Technical content
Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Ex i-Temperature transducer for converting and transmitting intrinsically safe signals from RTD and TC sensors to a load in the safe area. Order configuration, Safety Integrity Level (SIL, IEC 61508): 2, Systematic Capability: 3, Push-in connection Commercial data Item number 1472132 Packing unit 1 pc Minimum order quantity 1 pc Note Made to order (non-returnable) Product key DK1225 Country of origin DE MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 1 (11)
Product type Temperature transmitter Product family MINI Analog Pro Application Temperature SoftwareConfiguration App System properties Functionality SoftwareConfiguration App Electrical properties Electrical isolation between input and output yes Step response (0–99%) ≤ 400 ms Electrical isolation Overvoltage category II (≤ 5000 m) Pollution degree 2 (≤ 5000 m) Electrical isolation Input/output/power supply IEC/EN 61010-1 Standards/regulations IEC/EN 61010-1 Rated insulation voltage 300 Vrms Test voltage 2.5 kV AC (50 Hz, 60 s) Insulation Double/reinforced insulation Electrical isolation Output/power supply, input IEC/EN 60079-11 Standards/regulations IEC/EN 60079-11 Rated insulation voltage 265 Vrms Electrical isolation Input/output/power supply IEC/EN 60079-7 Standards/regulations IEC/EN 60079-7 Rated insulation voltage 251 Vrms Supply Nominal supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30 V DC Power consumption ≤ 900 mW Input data Measurement Description of the input intrinsically safe Sensor types (RTD) that can be used Pt, Ni, Si, Cu sensors MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 2 (11)
Sensor types that can be used (TC) J, K, B, E, N, R, S, T, C, A, L, U, A-1, A-2, A-3, Lr, M Temperature measuring range -200 °C ... 850 °C (Range depending on the sensor type) Connection technology 2-, 3-, 4-conductor Linear resistance measuring range 0 Ω ... 40 kΩ (Minimum measuring span: 10% of the selected measuring range) Potentiometer resistance range 0 Ω ... 40 kΩ (Minimum measuring span: 10% of the selected measuring range) -1000 mV ... 1000 mVLinear mV signal range 0 mV ... 1000 mV (SIL) ≤ 25 Ω (adjustable, 3-, 4-conductor, per cable)Max. permissible overall conductor resistance ≤ 50 Ω (adjustable, 2-conductor) Output data Signal: Current Number of outputs 1 Configurable/programmable Yes 4 mA ... 20 mA (SIL) 4 mA ... 20 mA (NE 43) 0 mA ... 20 mA 20 mA ... 0 mA 0 mA ... 21 mA (freely adjustable) Current output signal 21 mA ... 0 mA (freely adjustable) Max. current output signal 21.5 mA Load/output load current output ≤ 600 Ω Connection data Connection method Push-in connection Stripping length 10 mm Conductor cross-section AWG 24 ... 12 (flexible) Ex data GcEx installation (EPL) Div. 2 Ga Da Ma Ex i circuits (EPL) Div. 1 Safety data: Terminal 1-2; 3-4 Max. internal inductance Li negligible Max. internal capacitance Ci 44 nF Max. output voltage Uo 7 V MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 3 (11)
Max. output current Io 10 mA Max. output power Po 18 mW
253 V ACSafety-related maximum voltage Um
125 V DC
IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 1000 mH / 1000 µF IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 1000 mH / 300 µF IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co 300 mH / 15.7 µF IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 100 mH / 950 nF, 50 mH / 950 nF, 5 mH / 950 nF, 1 mH / 950 nF IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co 100 mH / 555 nF, 50 mH / 555 nF, 5 mH / 555 nF, 1 mH / 555 nF, 10 µH / 555 nF Signaling Green LED (supply voltage)Status display Red LED (error messages) Dimensions Width 6.2 mm Height 109.81 mm Depth 119.2 mm Material specifications Color gray (RAL 7042) Housing material PBT Environmental and real-life conditions Ambient conditions Degree of protection IP20 Ambient temperature (operation) -40 °C ... 70 °C (Any mounting position) Ambient temperature (storage/transport) -40 °C ... 85 °C Permissible humidity (operation) 5 % ... 95 % (at 25 °C, non-condensing) Altitude range (IEC/EN 61010-1) Height range > 2000 m ... 3000 m Ambient temperature (operation) -40 °C ... 63 °C Rated insulation voltage 300 Vrms (Input/output/power supply) Insulation Double/reinforced insulation Altitude range (IEC/EN 61010-1) Height range > 3000 m ... 4000 m Ambient temperature (operation) -40 °C ... 56 °C Rated insulation voltage 300 Vrms (Input/output/power supply) Insulation Double/reinforced insulation MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 4 (11)
Altitude range (IEC/EN 61010-1) Height range > 4000 m ... 5000 m Ambient temperature (operation) -40 °C ... 49 °C Rated insulation voltage 150 Vrms (Input/output/power supply) Insulation Double/reinforced insulation Altitude range (IEC/EN 60079-11) Height range > 2000 m ... 3000 m Ambient temperature (operation) -40 °C ... 63 °C
121 V ACSafety-related maximum voltage Um
110 V DC
Rated insulation voltage 150 Vrms (Output/supply, input) Altitude range (IEC/EN 60079-11) Height range > 3000 m ... 4000 m Ambient temperature (operation) -40 °C ... 56 °C Safety-related maximum voltage Um 33 V AC/DC Rated insulation voltage 60 Vrms (Output/supply, input) Altitude range (IEC/EN 60079-11) Height range > 4000 m ... 5000 m Ambient temperature (operation) -40 °C ... 49 °C Safety-related maximum voltage Um 33 V AC/DC Rated insulation voltage 60 Vrms (Output/supply, input) Altitude range (IEC/EN 60079-7) Height range > 2000 m ... 3000 m Ambient temperature (operation) -40 °C ... 63 °C Rated insulation voltage 162 Vrms (Input/output/power supply) Altitude range (IEC/EN 60079-7) Height range > 3000 m ... 4000 m Ambient temperature (operation) -40 °C ... 56 °C Rated insulation voltage 60 Vrms (Input/output/power supply) Altitude range (IEC/EN 60079-7) Height range > 4000 m ... 5000 m Ambient temperature (operation) -40 °C ... 49 °C Rated insulation voltage 60 Vrms (Input/output/power supply) Approvals CE Certificate CE-compliant ATEX II (1) G [Ex ia Ga] IIC MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 5 (11)
II (1) D [Ex ia Da] IIIC II 3 (1) G Ex ec [ia Ga] ic IIC T4 Gc Identification I (M1) [Ex ia Ma] I Certificate IBExU 21 ATEX 1035 X IECEx [Ex ia Ga] IIC [Ex ia Da] IIIC Ex ec [ia Ga] ic IIC T4 Gc Identification [Ex ia Ma] I Certificate IECEx IBE 21.0017 X CCC / China-Ex [Ex ia Ga] IIC [Ex ia Da] IIIC Identification Ex ec [ia Ga] IIC T4 Gc Certificate 2023122310116238 UL, USA/Canada UL 61010-2-201 Listed Class I, Div. 1, Groups A, B, C, D Class II, Div. 1, Groups E, F, G Class III, Div. 1 Class I, Zone 0, 1, 2, Groups IIC, IIB, IIA Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2 AEx ec [ia Ga] IIC T4 Gc; AEx ec [ia IIIC Da] IIC T4 Gc Ex ec [ia Ga] IIC T4 Gc X; Ex ec [ia IIIC Da] IIC T4 Gc X Class I, Zone 0, [AEx ia Ga] IIC, [Ex ia Ga] IIC X Identification Class I, Zone 20, [AEx ia Da] IIIC, [Ex ia Da] IIIC X Certificate , C.D.-No 097285872 Shipbuilding approval Certificate DNV TAA00003FZ Safety Integrity Level (SIL, IEC 61508) Identification 2 Note single-channel Systematic Capability Identification 3 INMETRO [Ex ia Ma] I [Ex ia Ga] IIC [Ex ia Da] IIIC Identification Ex ec [ia Ga] IIC T4 Gc MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 6 (11)
Certificate DNV 23.0187 X Shipbuilding data Temperature B Humidity B Vibration A EMC A Enclosure Required protection according to the Rules shall be provided upon installation on board EMC data Electromagnetic compatibility Tested in accordance with the following standards and regulations: EN 61326-1 For industrial use, NAMUR NE 21 Noise immunity EN 61000-6-2 Noise immunity EN 61326-3-2 Noise emission Standards/regulations EN 61000-6-4 Standards and regulations GB Standard GB/T 3836.1 GB/T 3836.3 Standards/regulations GB/T 3836.4 Mounting Mounting type DIN rail mounting Mounting position any MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 7 (11)
PWR – PWR + FM IN OUT I +IN OUT I – active IN IN TI+S-PORT PWR– PWR+ 2.Div Zone 2 passive mV 1,2.Div one 20,21,22Z one 0,1,2Z Sensor / Field OUTIN or RTD RTD Poti or or RTD2RTD1 TC or or PLC/DCS MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 8 (11)
To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1472132 cULus Listed Approval ID: E238705 DNV Approval ID: TAA00003FZ IECEx Approval ID: IECEx IBE 21.0017X CCC Approval ID: 2023122310116238 ATEX Approval ID: IBExU21ATEX1035 X cULus Listed Approval ID: E196811 cULus Listed Approval ID: E196811 INMETRO Approval ID: DNV 23.0187 X MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 9 (11)
ECLASS-13.0 27210129 ECLASS-15.0 27210129 ETIM ETIM 9.0 EC002919 MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 10 (11)
Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes Exemption 7(a), 7(c)-I China RoHS EFUP-50Environment friendly use period (EFUP) An article-related China RoHS declaration table can be found in the download area for the respective article under "Manufacturer declaration". For all articles with EFUP-E, no China RoHS declaration table issued and required. EU REACH SVHC Lead(CAS: 7439-92-1)REACH candidate substance (CAS No.) 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol(CAS: 79-94-7) Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com MINI MCR-EX-T-I-PT-C - Temperature measuring transducer 1472132 https://www.phoenixcontact.com/us/products/1472132 Nov 10, 2025, 12:17AM Page 11 (11)