1302-C001-AA COOPER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 20
Technical content
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE P.O. Box 14460 St. Louis, MO 63178-4460 (636) 394-2877 3/11/200 The following data sheets contain information obtained directly from the manufacturer’s installation instruction manuals. Within each application there are specific requirements that detail how the Power Electronic Equipment should be installed and the proper overcurrent protection that has been tested and approved by certified testing agencies. The part numbers shown in this guide were obtained from the latest available published information from the manufacturer. It is recommended that each installation be checked against the manufacturer’s installation guides to determine if any additional requirements are needed. Bussmann is not responsible for mis-application of our products. For the latest, most up-to-date product specifications listed in this guide please visit us at http://www.bussmann.com or by calling the Bussmann Information Fax (BIF) at 636-527-1450. This guide is intended to clearly represent product data and provide technical information that will help the end user with design/installation applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any information contained in this guide. Once a product has been selected, it should be checked and tested by the end user in all possible applications.
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1302 AC Drive (575 Volts) Maximum Short Circuit Rating is 30kA AC Input Line Fuse Selection Values Model Input Fuse Number Voltage HP Current Part Number V A 1302–C001–AA 575 1 2 LPJ-4SP 1302–C001–AF 575 1 2 LPJ-4SP 1302–C002–AA 575 2 3.4 LPJ-7SP 1302–C002–AF 575 2 3.4 LPJ-7SP 1302–C003–AA 575 3 5.2 LPJ-10SP 1302–C003–AF 575 3 5.2 LPJ-10SP 1302–C004–AA 575 5 7.5 LPJ-15SP 1302–C005–AA 575 5 7.5 LPJ-15SP 1302–C005–AF 575 7.5 10.9 LPJ-20SP 1302–C007–AF 575 7.5 10.9 LPJ-20SP 1302–C010–AA 575 10 14.5 LPJ-25SP 1302–C010–AF 575 10 14.5 LPJ-25SP Fuse Block Disconnect Switch J60030-3CR or JP60030-3CR CFD30J3
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1305 Adjustable Frequency AC Drive (Series C) Voltage Bussmann Bussmann Catalog Number V HP kW HP kW Class CC Class J 1305-AA02A 200-230 0.5 0.37 0.25 0.19 KTK-R-6 LPJ-6SP 1305-AA03A 200-230 0.75 0.55 0.5 0.37 KTK-R-6 LPJ-6SP 1305-AA04A 200-230 1 0.75 0.75 0.55 KTK-R-10 LPJ-10SP 1305-AA08A 200-230 2 1.5 1 0.75 KTK-R-15 LPJ-15SP 1305-AA12A 200-230 3 2.2 2 1.5 KTK-R-25 LPJ-25SP 1305-BA01A 380-460 0.5 0.37 LPJ-3SP 1305-BA02A 380-460 0.75 0.55 LPJ-3SP 1305-BA03A 380-460 1 0.75 KTK-R-6 LPJ-6SP 1305-BA04A 380-460 2 1.5 KTK-R-10 LPJ-10SP 1305-BA06A 380-460 3 2.2 KTK-R-15 LPJ-15SP 1305-BA09A 380-460 5 4 KTK-R-20 LPJ-20SP Fuse Blocks Disconnect Switches KTK-R (0 to 30) BC6033B or OPM-NG-SC3 CFD30CC3 LPJ (0 to 30) J60030-3CR or JP60030-3CR CFD30J3 Three Phase Input Single Phase Input
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1329 Intergrated Drive/Motor (Series B) 1,0 to 5.0 HP Maximum Short Circuit Rating is 10kA Catalog Number Single Phase Three Phase Input Bussmann Bussmann Voltage Voltage HP Current Class CC Class J 1329I-BJ001 115 1 14 KTK-R-20 LPJ-20SP 1329I-BK001 230 1 5.8 KTK-R-9 LPJ-9SP 1329I-BK002 230 2 14 KTK-R-20 LPJ-20SP 1329I-BL001 230 1 4.5 KTK-R-7 LPJ-7SP 1329I-BL002 230 2 7.6 KTK-R-12 LPJ-12SP 1329I-BM001 460 1 2.3 KTK-R-3.5 LPJ-3.5SP 1329I-BM002 460 2 3.7 KTK-R-6 LPJ-6SP 1329I-BM003 460 3 5.7 KTK-R-9 LPJ-9SP 1329I-BM005 460 5 9 KTK-R-15 LPJ-15SP Fuse Blocks Disconnect Switches KTK-R (0 to 30) BC6033B or OPM-NG-SC3 CFD30CC3 LPJ (0 to 30) J60030-3CR or JP60030-3CR CFD30J3
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1333 3/4 to 20HP (.55-15kW) Adjustable Frequency AC Drive Series D Catalog Number Single Phase Three Phase Single Phase Three Phase Bussmann HP kW Voltage Voltage Current Current Class RK5 1333-ZAA 0.75 0.55 230 230 6.2 4.1 FRS-R-15 1333-AAA 1 0.75 230 230 8.6 6.5 FRS-R-15 1333-YAA 2 1.5 230 230 9.5 9 FRS-R-15 1333-BAA 3 2.2 230 230 13 14 FRS-R-30 1333-CAA 5 4 230 230 18.8 22 FRS-R-40 1333-DAA 7.5 5.5 230 230 23.4 27 FRS-R-70 1333-EAA 10 7.5 230 230 31.1 37 FRS-R-80 1333-FAA 15 11 230 230 41.6 47 FRS-R-100 1333-GAA 20 15 230 230 54.6 62 FRS-R-125 1333-AAB 1 0.75 460 3.3 FRS-R-15 1333-YAB 2 1.5 460 4.5 FRS-R-15 1333-BAB 3 2.2 460 8 FRS-R-15 1333-CAB 5 4 460 13 FRS-R-20 Amperage Fuse Blocks 0 to 30 R60030-3CR 35 to 60 R60060-3CR 65 to 100 R60100-3CR 110 to 200 R60200-3CR
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 FORCE Adjustable Frequncy AC Drive 0.75 - 485 kW (1 - 650 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Numbe r kW HP 200–240V 380–480V 500–600V 1336T– _ _ F10 0.75 1 10 6 – 1336T– _ _ F30 2.2 3 25 15 – 1336T– _ _ F50 3.7 5 40 20 – 1336T– _ _ 001 0.75 1 10 6 6 1336T– _ _ 003 2.2 3 15 10 10 1336T– _ _ 007 5.5 7.5 40 20 15 1336T– _ _ 010 7.5 10 50 30 20 1336T– _ _ 015 11 15 70 35 25 1336T– _ _ 020 15 20 100 45 35 1336T– _ _ 025 18.5 25 100 60 40 1336T– _ _ 030 22 30 125 70 50 1336T– _ _ 040 30 40 150 80 60 1336T– _ _ 050 37 50 200 100 80 1336T– _ _ X060 45 60 – 100 – 1336T– _ _ 060 45 60 250 125 90 1336T– _ _ 075 56 75 – 150 110 1336T– _ _ 100 75 100 – 200 150 1336T– _ _ 125 93 125 – 250 175 1336T– _ _ X150 112 150 – 250 – 1336T– _ _ 150 112 150 – 300 225 1336T– _ _ 200 149 200 – 400 350 1336T– _ _ 250 187 250 – 450 400 1336T– _ _ X300 224 300 – – 400 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 450 to 600 J60600-3CR FD600J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 450 to 600 T60600-1C (Single pole blocks) FD600J3/BDTA6 Use Bussmann LPJ, KTK-R or JJS Fuses
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 (cont.) Model 1336 FORCE Adjustable Frequncy AC Drive 0.75 - 485 kW (1 - 650 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Numbe r kW HP 200–240V 500–600V 1336T– _ _ X250 187 250 – – 1336E– _ _ P250 187 250 – – 1336T– _ _ 300T 224 300 – FWP-400A 1336E– _ _ 300 224 300 – FWP-450A 1336T– _ _ 350 261 350 – FWP-450A 1336E– _ _ 350 261 350 – 1336T– _ _ 400 298 400 – FWP-500A 1336E– _ _ 400 298 400 – 1336T– _ _ 450 336 450 – FWP-600A 1336E– _ _ 450 336 450 – FWP-600A 1336T– _ _ 500 373 500 – FWP-800A 1336T– _ _ 600 448 600 – FWP-800A 1336T– _ _ 650 485 650 – FWP-800A 1336T– _ _ 700C 522 700 – FWP-700A {1} 1336T– _ _ 800C 597 800 – FWP-700A {1} {1} Two Fuses in parallel are required. Amps Fuse Blocks FWP 450 - 600 1BS104
700 BH-3145
FWP-600A{1} FWP-700A{1} FWP-600A FWP-800A FWP-700A FWP-800A FWP-500A FWP-500A FWP-600A FWP-600A FWP-450A FWP-450A FWP-450A Use Bussmann Semiconductor Fuses 380–480V
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 IMPACT Adjustable Frequency AC Drive 0.37 - 597 kW (0.5 - 800 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Number kW HP 200–240V 380–480V 500–600V 1336E-_ _ F05 0.37 0.5 6 3 1336E-_ _ F07 0.56 0.75 6 3 1336E-_ _ F10 0.75 1 10 6 3 1336E-_ _ F15 1.2 1.5 15 6 1336E-_ _ F20 1.5 2 15 10 6 1336E-_ _ F30 2.2 3 25 15 10 1336E-_ _ F50 3.7 5 40 20 0.1 1336E-_ _ F75 5.5 7.5 20 15 1336E-_ _ F100 7.5 10 30 20 1336E-_ _ 007 5.5 7.5 40 20 15 1336E-_ _ 010 7.5 10 50 30 20 1336E-_ _ 015 11 15 70 35 25 1336E-_ _ 020 15 20 100 45 35 1336E-_ _ 025 18.5 25 100 60 40 1336E-_ _ 030 22 30 125 70 50 1336E-_ _ X040 30 40 150 80 60 1336E-_ _ 040 30 40 150 80 60 1336E-_ _ 050 37 50 200 100 80 1336E-_ _ X060 45 60 100 1336E-_ _ 060 45 60 250 125 90 1336E-_ _ 075 56 75 300 150 110 1336E-_ _ 100 75 100 400 200 150 1336E-_ _ 125 93 125 450 250 175 1336E-_ _ X150 112 150 250 1336E-_ _ 150 112 150 300 225 1336E-_ _ 200 149 200 400 350 1336E-_ _ 250 187 250 450 400 1336E-_ _ X300 224 300 400 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 450 to 600 J60600-3CR FD600J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 450 to 600 T60600-1C (Single pole blocks) FD600J3/BDTA6 Use Bussmann LPJ, KTK-R or JJS Fuses
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 (cont.) Model 1336 IMPACT Adjustable Frequency AC Drive 0.37 - 597 kW (0.5 - 800 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Use Bussmann Semiconductor Fuses Number kW HP 200–240V 380–480V 500–600V 1336E-_ _ 300 224 300 FWP-500A FWP-400A 1336E-_ _ P300 224 300 FWP-500A 1336E-_ _ 350 224 300 FWP-600A FWP-450A 1336E-_ _ P350 261 350 FWP-600A 1336E-_ _ 400 298 400 FWP-600A FWP-500A 1336E-_ _ P400 298 400 FWP-600A 1336E-_ _ 450 336 450 FWP-800A FWP-600A 1336E-_ _ P450 336 450 FWP-700A 1336E-_ _ 500 373 500 FWP-800A FWP-800A 1336E-_ _ 600 448 600 FWP-900A FWP-800A 1336E-_ _ 650 485 650 FWP-800A 1336E-_ _ 700C 522 700 FWP-600A {1} FWP-700A{1} 1336E-_ _ 800C 597 800 FWP-700A {1} FWP-700A{1} {1} Two Fuses in parallel are required. Amps Fuse Blocks FWP 450 - 600 1BS104
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 PLUS Adjustable Frequency AC Drive 0.37 - 448 kW (0.5 - 600 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Number kW HP 200–240V 380–480V 500–600V 1336S-_ _ F05 0.37 0.5 6 3 1336S-_ _ F07 0.56 0.75 6 3 1336S-_ _ F10 0.75 1 10 6 6 1336S-_ _ F15 1.2 1.5 15 6 1336S-_ _ F20 1.5 2 15 10 10 1336S-_ _ F30 2.2 3 25 15 15 1336S-_ _ F50 3.7 5 40 20 20 1336S-_ _ F75 5.5 7.5 20 1336S-_ _ F100 7.5 10 30 1336S-_ _ 007 5.5 7.5 40 20 15 1336S-_ _ 010 7.5 10 50 30 20 1336S-_ _ 015 11 15 70 35 25 1336S-_ _ 020 15 20 100 45 35 1336S-_ _ 025 18.5 25 100 60 40 1336S-_ _ 030 22 30 125 70 50 1336S-_ _ 040 30 40 150 80 60 1336S-_ _ 050 37 50 200 100 80 1336S-_ _ X060 45 60 100 1336S-_ _ 060 45 60 250 125 90 1336S-_ _ 075 56 75 300 150 110 1336S-_ _ 100 75 100 400 200 150 1336S-_ _ 125 93 125 450 250 175 1336S-_ _ X150 112 150 250 1336S-_ _ 150 112 150 300 225 1336S-_ _ 200 149 200 400 350 1336S-_ _ 250 187 250 450 400 1336S-_ _ X300 224 300 400 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 450 to 600 J60600-3CR FD600J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 450 to 600 T60600-1C (Single pole blocks) FD600J3/BDTA6 Use Bussmann LPJ, KTK-R or JJS Fuses
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 (cont.) Model 1336 PLUS Adjustable Frequency AC Drive 0.37 - 448 kW (0.5 - 600 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Use Bussmann Semiconductor Fuses Number kW HP 200–240V 380–480V 500–600 V 1336S-_ _ P250 187 250 FWP-450A 1336S-_ _ X250 187 250 FWP-450A 1336S-_ _ 300 224 300 FWP-450A FWP-400A 1336S-_ _ P300 224 300 FWP-500A 1336S-_ _ 350 261 350 FWP-500A FWP-450A 1336S-_ _ P350 261 350 FWP-600A 1336S-_ _ 400 298 400 FWP-600A FWP-500A 1336S-_ _ P400 298 400 FWP-600A 1336S-_ _ 450 336 450 FWP-800A FWP-600A 1336S-_ _ P450 336 450 FWP-700A 1336S-_ _ 500 373 500 FWP-800A FWP-800A 1336S-_ _ 600 448 600 FWP-900A FWP-800A Amps Fuse Blocks FWP 450 - 600 1BS104
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 PLUS II Adjustable Frequency AC Drive 0.37 - 448 kW (0.5 - 600 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Number kW HP 200–240V 380–480V 500–600V 1336F- _ _ F05 0.37 0.5 4 3 1336F- _ _ F05 Series A 0.37 0.5 6 3 1336F- _ _ F07 0.56 0.75 4 3 1336F- _ _ F07 Series A 0.56 0.75 6 3 1336F- _ _ F10 0.75 1 6 3 3 1336F- _ _ F10 Series A 0.75 1 10 6 6 1336F- _ _ F15 1.2 1.5 8 4 1336F- _ _ F15 Series A 1.2 1.5 15 6 1336F- _ _ F20 1.5 2 10 5 6 1336F- _ _ F20 Series A 1.5 2 15 10 10 1336F- _ _ F30 2.2 3 15 8 10 1336F- _ _ F30 Series A 2.2 3 25 15 15 1336F- _ _ F50 3.7 5 25 12 15 1336F- _ _ F50 Series A 3.7 5 40 20 20 1336F- _ _ F75 5.5 7.5 30 20 15 1336F- _ _ F100 7.5 10 30 20 1336F- _ _ F150 11 15 35 25 1336F- _ _ F200 15 20 35 30 1336F- _ _ 007 5.5 7.5 40 20 15 1336F- _ _ 010 7.5 10 50 30 20 1336F- _ _ 015 11 15 70 35 25 1336F- _ _ 020 15 20 100 45 35 1336F- _ _ 025 18.5 25 100 60 40 1336F- _ _ 030 22 30 125 70 50 1336F- _ _ 040/X040 30 40 150 80 60 1336F- _ _ 050 37 50 200 100 80 1336F- _ _ X060 45 60 100 1336F- _ _ 060 45 60 250 125 90 1336F- _ _ 075 56 75 300 150 110 1336F- _ _ 100 75 100 400 200 150 1336F- _ _ 125 93 125 450 250 175 1336F- _ _ X150 112 150 250 1336F- _ _ 150 112 150 300 225 1336F- _ _ 200 149 200 400 350 1336F- _ _ 250 187 250 450 400 1336F- _ _ X300 224 300 400 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 450 to 600 J60600-3CR FD600J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 450 to 600 T60600-1C (Single pole blocks) FD600J3/BDTA6 Use Bussmann LPJ, KTK-R or JJS Fuses
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 (cont.) Model 1336 PLUS II Adjustable Frequency AC Drive 0.37 - 448 kW (0.5 - 600 HP) Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Use Bussmann Semiconductor Fuses Number kW HP 200–240V 380–480V 500–600V 1336F- _ _ BP/BPR250 187 250 FWP-450A 1336F- _ _ X250 187 250 FWP-450A 1336F- _ _ 300 224 300 FWP-450A FWP-400A 1336F- _ _ BP/BPR300 224 300 FWP-500A 1336F- _ _ 350 261 350 FWP-500A FWP-450A 1336F- _ _ BP/BPR350 261 350 FWP-600A 1336F- _ _ 400 298 400 FWP-600A FWP-500A 1336F- _ _ BP/BPR400 298 400 FWP-600A 1336F- _ _ 450 336 450 FWP-800A FWP-600A 1336F- _ _ BP/BPR450 336 450 FWP-700A 1336F- _ _ 500 373 500 FWP-800A FWP-800A 1336F- _ _ 600 448 600 FWP-900A FWP-800A Amps Fuse Blocks FWP 450 - 600 1BS104
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 SPIDER Adjustable Frequency Drive for the Fibers Industry 9.9A - 60A Maximum Short Circuit Rating is 200kA Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Drive Catalog Rating Input Number kW Current 200–240V 380–480V 1336Z- _ _ A022 1.8 7.6 30 1336Z- _ _ A036 3 12.5 30 1336Z- _ _ A060 5 24.6 50 1336Z- _ _ B010 1.6 8.7 20 1336Z- _ _ B017 2.7 11.4 20 1336Z- _ _ B033 5.5 19.8 40 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR Use Bussmann LPJ, KTK-R or JJS Fuses
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 1336/1336VT/1336 PLUS/1336 PLUS II/FORCE/IMPACT Series A Brake Chopper Dynamic Brake Fuse All brake modules are internally fused to protect brake components. Dynamic Brake Fuse Rating Recommended Fuse 1336-WA018 F1 & F2 30A, 600V FWC-30A10F 1336-WB009 F1 & F2 15A, 600V FWC-15A10F 1336-WC009 F1 & F2 15A, 600V FWC-15A10F 1336-WA070 F1 & F2 125A, 700V FWP-125A 1336-WB035 F1 & F2 60A, 700V FWP-60A 1336-WC035 F1 & F2 60A, 700V FWP-60A 1336-WA115 F1 & F2 200A, 700V FWP-200A 1336-WB110 F1 & F2 200A, 700V FWP-200A 1336-WC085 F1 & F2 200A, 700V FWP-200A
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336 Adjustable Frequency AC Drive Maximum Recommended AC Input Line Fuse Ratings (fuses are user supplied) Input Input Catalog Number Current Voltage 1336-B003 5.7 460 KTK-R-10 JJS-10 1336-B005 9.2 460 KTK-R-15 JJS-15 1336-B007 13.3 460 KTK-R-20 JJS-20 1336-B010 17 460 KTK-R-25 JJS-25 1336-B015 25 460 JJS-35 JKS-35 1336-B020 34 460 JJS-45 JKS-45 1336-B025 42 460 JJS-60 JKS-60 1336-B030 49 460 JJS-70 JKS-70 1336-B040 61 460 JJS-80 JKS-80 1336-B050 76 460 JJS-100 JKS-100 1336-B075 122 460 JJS-150 JKS-150 1336-B100 153 460 JJS-200 JKS-200 1336-B125 184 460 JJS-250 JKS-250 1336-B150 222 460 JJS-300 JKS-300 1336-B200 296 460 JJS-400 JKS-400 1336-C003 3.2 575 KTK-R-6 JJS-6 1336-C005 4.1 575 KTK-R-6 JJS-6 1336-C007 7.7 575 KTK-R-10 JJS-10 1336-C010 10.2 575 KTK-R-15 JJS-15 1336-C015 15 575 JJS-20 JKS-20 1336-C020 19 575 JJS-25 JKS-25 1336-C025 24 575 JJS-30 JKS-30 1336-C030 29 575 JJS-35 JKS-35 1336-C040 39 575 JJS-45 JKS-45 1336-C050 48 575 JJS-60 JKS-60 1336-C075 73 575 JJS-90 JKS-90 1336-C100 97 575 JJS-125 JKS-125 1336-C125 121 575 JJS-150 JKS-150 1336-C150 146 575 JJS-175 JKS-175 1336-C200 193 575 JJS-250 JKS-250 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 Recommended Bussmann Fuse
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Heavy Duty Dynamic Braking for use with 1336/1336VT/1336 PLUS/1336 FORCE Drives All brake modules are internally fused to protect brake components. Dynamic Brake Fuse Rating Recommended Fuse 1336-MOD-KA005 F1 10A, 500V FWH-10A14F 1336-MOD-KB005 F1 5A, 600V FWC-5A10F 1336-MOD-KC005 F1 5A, 700V FWP-5A14F 1336-MOD-KA010 F1 20A, 500V FWH-20A14F 1336-MOD-KB010 F1 10A, 600V FWC-10A10F 1336-MOD-KC010 F1 10A, 700V FWP-10A14F 1336-MOD-KA050 F1 & F2 50A, 500V FWH-50A 1336-MOD-KB050 F1 & F2 35A, 700V FWP-35A 1336-MOD-KC050 F1 & F2 35A, 700V FWP-35A
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1336VT Adjustable Frequency AC Drive Input Input Catalog Number Current Voltage 1336VT-B003 5.6 460 KTK-R-10 1336VT-B005 7.5 460 KTK-R-15 1336VT-B007 11.4 460 KTK-R-20 1336VT-B010 14.6 460 KTK-R-25 1336VT-B015 22 460 JJS-35 JKS-30 1336VT-B020 28 460 JJS-45 JKS-45 1336VT-B025 35 460 JJS-60 JKS-60 1336VT-B030 44 460 JJS-70 JKS-60 1336VT-B040 54 460 JJS-80 JKS-80 1336VT-B050 67 460 JJS-100 JKS-100 1336VT-B060 78 460 JJS-110 JKS-110 1336VT-B075 97 460 JJS-150 JKS-150 1336VT-B100 124 460 JJS-200 JKS-200 1336VT-B125 154 460 JJS-250 JKS-250 1336VT-B150 178 460 JJS-300 JKS-300 1336VT-B200 235 460 JJS-400 JKS-400 1336VT-B250 296 460 JJS-500 JKS-500 Amps Fuse Blocks Disconnect Switches KTK-R 0 to 30 BC6033B or OPM-NG-SC3 CFD30CC3 LPJ 0 to 30 J60030-3CR or JP60030-3CR CFD30J3 35 to 60 J60060-3CR CDF60J3 65 to 100 J60100-3CR CFD100J3 110 to 200 J60200-3CR FD200J3 225 to 400 J60400-3CR FD400J3 450 to 600 J60600-3CR FD600J3 JJS 0 to 30 T60030-3CR 35 to 60 T60060-3CR 65 to 100 T60100-3C CFD100J3/BDTA1 110 to 200 T60200-1C (Single pole blocks) FD200J3/BDTA2 225 to 400 T60400-1C (Single pole blocks) FD400J3/BDTA4 450 to 600 T60600-1C (Single pole blocks) FD600J3/BDTA6 Recommended Bussmann Fuse
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1391-DES Digital AC Servo Drive Recommended fuse for transformer primary protection XFMR Catalog Number KVA Rating 208 240 380 415 480 575 1391-T015 1.5 FRS-R-8 FRS-R-7 FRS-R-4-1/2 FRS-R-4 FRS-R-3-1/2 FRS-R-3 1391-T035 3.5 FRS-R-17-1/2 FRS-R-15 FRS-R-9 FRS-R-8 FRS-R-7 FRS-R-6 1391-T050 5 FRS-R-20 FRS-R-20 FRS-R-12 FRS-R-12 FRS-R-10 FRS-R-8 1391-T100 10 FRS-R-40 FRS-R-35 FRS-R-25 FRS-R-20 FRS-R-17-1/2 FRS-R-15 1391-T125 12.5 FRS-R-50 FRS-R-45 FRS-R-30 FRS-R-25 FRS-R-25 FRS-R-20 1391-T150 15 FRS-R-60 FRS-R-50 FRS-R-35 FRS-R-30 FRS-R-30 FRS-R-25 Recommended fusing for shunt regulator. Drive Rating Fuse Location Bussmann
15 Amps Top Panel KLM-10
22.5 Amps Top Panel FNM-6-1/4
22.5 Amps External KTK-15
45 Amps External KLM-20
Bussmann Fuses in Allen-Bradley Drives TECHNICAL LITERATURE 3/11/2002 Model 1394 Digital AC Multi-Axis Motion Control System Maximum Short Circuit Rating of 100kA Line Input Fusing Catalog Number Series 1394-SJT05 Systems Series A and B FRS-R-20 1394C-SJT05 Systems Series C KTK-R-20 LPJ-20SP 1394-SJT10 Systems Series A and B FRS-R-30 1394C-SJT10 Systems Series C KTK-R-30 LPJ-30SP 1394x-SJT22 Systems FRS-R-35 LPS-RK-40SP LPJ-45SP Shunt Module Catalog Number Shunt has UL 1394-SR9A FWP-50A14F 170N2013 FWP-50A22F 1394-SR9AF FWP-50A14F 170N2013 FWP-50A22F 1394-SR10A FWP-40A14F 1394-SR36A FWP-50A14F 170N2013 FWP-50A22F 1394-SR36AF FWP-50A14F 170N2013 FWP-50A22F
24 Volt Logic Input Power