Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user documentation. Our General Terms of Use for Downloads are valid. Primary-switched power supply unit, TRIO POWER, IPD panel feed-through with Push-in spring connection, Wall mounting, input: 1-phase, output: 24 V DC / 3.75 A Commercial Data Item number 1278301 Packing unit 1 pc Minimum order quantity 1 pc Product Key CMPF13 GTIN 4063151474843 Weight per Piece (including packing) 1,022 g Weight per Piece (excluding packing) 1,022 g Country of origin VN Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 1 (16)

Supply system configuration Star network (TN, TT, IT (PE)) Nominal input voltage range 100 V AC ... 277 V AC 115 V AC ... 277 V AC ±10 % (UL) Derating < 100 V AC ... 85 V AC (1 %/V) Switch-on voltage > 75 V AC Shut-down voltage < 70 V AC

120 V ACTypical national grid voltage

230 V AC

Voltage type of supply voltage AC/DC Inrush current ≤ 35 A (typical) Inrush current integral (I2t) < 0.45 A2s AC frequency range 50 Hz ... 60 Hz ±10 % Frequency range (fN) 50 Hz ... 60 Hz ±10 % > 25 ms (120 V AC)Mains buffering time > 25 ms (230 V AC)

1 A (100 V AC)Current consumption

0.4 A (277 V AC)

Protective circuit Transient surge protection; Varistor Power factor (cos phi) > 0.92 Switch-on time < 0.2 s Input fuse 4 A (internal (device protection)) Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C, D, K or comparable) Discharge current to PE < 3.5 mA DC operation Nominal input voltage range 110 V DC ... 250 V DC 120 V DC ... 250 V DC ±10 % (UL) Derating < 110 V DC ... 88 V DC (1 %/V) Switch-on voltage ≥ 75 V DC Shut-down voltage < 70 V DC Voltage type of supply voltage AC/DC

0.88 A (110 V DC)Current consumption

0.38 A (250 V DC)

typ. 92 % (120 V AC)Efficiency typ. 93 % (230 V AC) Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 2 (16)

Nominal output voltage 24 V DC ±1 % Nominal output current (IN) 3.75 A (Class 2 Output) Derating > 60 °C ... 70 °C (2.5%/K) Feedback voltage resistance ≤ 35 V DC Protection against overvoltage at the output (OVP) ≤ 35 V DC < 1 % (change in load, static 10 % ... 90 %) < 3 % (Dynamic load change 10 % ... 90 %, 10 Hz) Control deviation < 0.1 % (change in input voltage ±10 %) Residual ripple ≤ 10 mVPP Short-circuit-proof yes No-load proof yes Output power 90 W Peak switching voltages nominal load < 100 mV < 0.25 W (120 V AC)Maximum no-load power dissipation < 0.28 W (230 V AC) < 7.4 W (120 V AC)Power loss nominal load max. < 6 W (230 V AC) Rise time typ. 100 ms (UOUT (10 % ... 90 %)) Connection in parallel yes, for increasing power and redundancy with diode Connection in series yes, for increased output voltage Signal: DC OK Continuous load current 100 mA Connection data Input Connection method IPD panel feed-through with Push-in spring connection Color-coded gray Type of locking Clip locking Range of positions 3 Push-in connection Output Connection method IPD panel feed-through with Push-in spring connection Color-coded black Type of locking Clip locking Range of positions 3 Push-in connection LED signaling Types of signaling LED Signal output: LED status indicator Signalization designation AC OK Status display LED Color green Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 3 (16)

Signal output: LED status indicator Signalization designation DC OK Status display LED Color green Electrical properties Number of phases 1.00 4 kV AC (type test)Insulation voltage input/output 3 kV AC (routine test) Product properties Product type Power supply > 1475000 h (25 °C) > 1000000 h (40 °C) MTBF (IEC 61709, SN 29500) > 500000 h (60 °C) Insulation characteristics Protection class I Degree of pollution 3 Dimensions Dimensional drawing Width 100 mm Height 212 mm Depth 53 mm Installation dimensions Installation distance right/left 20 mm / 20 mm Installation distance top/bottom 50 mm / 100 mm Mounting Mounting type Wall mounting Assembly instructions Alignable: 20 mm horizontally, 50 mm vertically above, 100 mm vertically below With protective coating No Material specifications Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 4 (16)

Flammability rating according to UL 94 (housing / terminal blocks) Housing material Metal Type of housing Aluminum (AlMg3) Environmental and real-life conditions Ambient conditions Degree of protection IP67 Ambient temperature (operation) -25 °C ... 70 °C (Derating > 60 °C: 2 %/K) Ambient temperature (storage/transport) -40 °C ... 85 °C Maximum altitude ≤ 4000 m (> 2000 m, Derating: 10 %/1000 m) Climatic class 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation) ≤ 100 % (at 25 °C, non-condensing) Permissible humidity (operation) ≤ 100 % (at 25 °C, non-condensing) Shock 18 ms, 30g, in each space direction (according to IEC 60068-2- 27) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)Vibration (operation) 15 Hz ... 150 Hz, 4g, 90 min. Standards and regulations Overvoltage category EN 61010-1 II (≤ 4000 m) Overvoltage category EN 62477-1 III (≤ 2000 m) Electrical safety Standards/specifications IEC 61010-1 (SELV) Protective extra-low voltage IEC 61010-1 (SELV)Standards/specifications IEC 61010-2-201 (PELV) Safe isolation Standards/specifications IEC 61558-2-16 Low-voltage power supplies, DC output Standards/specifications EN 61204-3 Safety requirements for electrical equipment for measurement, control, and laboratory use Standards/specifications IEC 61010-1 Limit values for harmonic currents Standards/specifications EN 61000-3-2 Degrees of protection provided by enclosures (IP code) Standards/specifications EN/IEC 60529 Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 5 (16)

Identification UL/C-UL Listed UL 61010-1 UL Identification UL/C-UL Listed UL 61010-2-201 EMC data Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU EN 55016Conducted noise emission EN 61000-6-3 (Class B) Interference emission Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) Noise emission EN 55011 (EN 55022) EN 55016Noise emission EN 61000-6-3 (Class B) Noise immunity Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) Harmonic currents EN 61000-3-2Standards/regulations EN 61000-3-2 (Class A) Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 6 kV (Test Level 3) Comments Criterion A Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 10 V/m (Test Level 3) Frequency range 1 GHz ... 2 GHz Test field strength 10 V/m (Test Level 3) Frequency range 2 GHz ... 6 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 6 (16)

Input 4 kV (Test Level 3 - asymmetrical) Output 2 kV (Test Level 3 - asymmetrical) Signal 2 kV (Test Level 3 - asymmetrical) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 2 kV (Test Level 4 - symmetrical)Input 4 kV (Test Level 4 - asymmetrical) 1 kV (Test Level 3 - symmetrical)Output 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 2 - asymmetrical) Comments Criterion A Conducted interference Standards/regulations EN 61000-4-6 Conducted interference Input/Output asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Voltage dips Standards/regulations EN 61000-4-11 Voltage 230 V AC Frequency 50 Hz Voltage dip 70 % Number of periods 25 periods Comments Criterion A Voltage dip 40 % Number of periods 10 periods Comments Criterion A Voltage dip 0 % Number of periods 1 period Comments Criterion A Emitted interference Standards/regulations EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself. Temporary adverse effects on the operating behavior, which the Criterion C Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 7 (16)

device corrects automatically or which can be restored by actuating the operating elements. Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 8 (16)

H [m] I [%]Out 0 1000 2000 3000 4000 5000 I : 100%  60°C N Output current/installation altitude Block diagram -Filter Functions DC OKAC OK Filteractive PFC L N N L PE UVP OVP OTP OCP SCP User Interface Input AC Output DC Block diagram Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 9 (16)

0 1 1,50,5 2 2,5 3 3,5 4 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 IOut [A] Power Factor = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC Power factor Diagram 0 1 1,50,5 2 2,5 3 3,5 4 0,0 0,2 0,4 0,6 0,8 1,0 IOut [A] IIn [A] = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC Input current/output current Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 10 (16)

Output DC 24V 3.75A PE N PHOENIX CONTACT GmbH & Co. KG Flachsmarktstr. 8

32825 Blomberg, Germany

TRIO-PS67/1AC/24DC/3.75/IPD Ord.No.: 1278301 www.phoenixcontact.com Documentation Device dimensions (dimensions in mm) Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 11 (16)

0 0,5 1 1,5 2 2,5 3 3,5 4 100 IOut [A] Eta [%] = UIn: 120 V AC/UOut: 24 V DC = UIn: 230 V AC/UOut: 24 V DC Efficiency Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 12 (16)

 cULus Listed Approval ID: FILE E 123528 Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 13 (16)

ECLASS-11.0 27040701 Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 14 (16)

Environmental Product Compliance REACh SVHC Lead 7439-92-1 Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 15 (16)

Redundancy module - STEP3-DIODE/5-24DC/2X5/1X10/PT - 1283937 https://www.phoenixcontact.com/us/products/1283937 Redundancy module STEP DIODE, DIN rail mounting, 5 V DC ... 24 V DC, 1x 10 A, 2x 5 A Phoenix Contact 2022 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com Power supply unit - TRIO-PS67/1AC/24DC/3.75/IPD 1278301 https://www.phoenixcontact.com/us/products/1278301 Nov 16, 2022, 6:28 AM Page 16 (16)