1248960 PHOENIX | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 9

Technical content

Please be informed that the data shown in this PDF document is generated from our online catalog. Please find the complete data in the user documentation. Our general terms of use for downloads are valid. Surge protective device consisting of base element with Push-in connection technology, Push- in remote indication contact, and protective plugs, for mounting on NS 35/7.5. Nominal voltage:

230 V AC, 3+1 circuit

Push-in connection technology for easy installation and uniform connection technology in the entire control cabinet• Time savings when wiring thanks to not having to check the recommended connection torque Savings on additional installation materials thanks to through-wiring Permanent protective device monitoring due to optional remote indication contact with through-wiring Commercial data Item number 1248960 Packing unit 1 pc Minimum order quantity 1 pc Product key CL132A GTIN 4063151351182 Weight per piece (including packing) 371.6 g Weight per piece (excluding packing) 372 g Country of origin DE VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 1 (9)

Product type Surge arrester Product family VALVETRAB MS IIIEC test classification EN type T2 TN-SIEC power supply system TT Type DIN rail module, two-section, divisible Number of positions 4 Surge protection fault message Optical, remote indicator contact Insulation characteristics Overvoltage category III Pollution degree 2 Electrical properties Nominal frequency fN 50 Hz (60 Hz) Indicator/remote signaling Connection name Remote fault indicator contact Switching function Changeover contact 5 V AC ... 250 V ACOperating voltage

30 V DC

5 mA AC ... 750 mA ACOperating current

1 A DC

Connection method Push-in connection Stripping length 10 mm ... 12 mm Conductor cross section rigid 0.5 mm² ... 10 mm² Conductor cross section AWG 20 ... 8 Conductor cross section, flexible, with ferrule, with plastic sleeve 0.5 mm² ... 6 mm² Conductor cross section flexible, with ferrule without plastic sleeve 0.5 mm² ... 10 mm² Remote fault indicator contact Connection method Push-in connection Stripping length 10 mm Conductor cross section AWG 30 ... 12 VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 2 (9)

Width 71.2 mm Height 97.2 mm Depth 65.7 mm (incl. DIN rail 7.5 mm) Horizontal pitch 4 Div. Material specifications Color (Base element) gray (RAL 7042) Color (Male connector) light gray (RAL 7035) Flammability rating according to UL 94 V-0 CTI value of material 600 Insulating material PA 6.6/PBT Material group I PA 6.6Housing material PBT Protective circuit L-N L-PE Mode of protection N-PE Direction of action 3L-N & N-PE 240/415 V AC (TN-S)Nominal voltage UN 240/415 V AC (TT) Nominal frequency fN 50 Hz (60 Hz) Maximum continuous operating voltage UC (L-N) 275 V AC Maximum continuous operating voltage UC (L-PE) 275 V AC Maximum continuous operating voltage UC (N-PE) 260 V AC

32 A (at 6 mm²)Rated load current IL

40 A (at 10 mm²)

Residual current IPE ≤ 5 µA Standby power consumption PC ≤ 360 mVA Nominal discharge current In (8/20) µs 20 kA Maximum discharge current Imax (8/20) µs 40 kA Follow current interrupt rating Ifi (N-PE) 100 A Short-circuit current rating ISCCR 25 kA Voltage protection level Up (L-N) ≤ 1.35 kV Voltage protection level Up (L-PE) ≤ 1.6 kV Voltage protection level Up (N-PE) ≤ 1.5 kV VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 3 (9)

≤ 1.35 kV (at In) ≤ 1.1 kV (at 10 kA) ≤ 1 kV (at 5 kA) Residual voltage Ures (L-N) ≤ 0.9 kV (at 3 kA) ≤ 1.6 kV (at In) ≤ 1.2 kV (at 10 kA) ≤ 1 kV (at 5 kA) Residual voltage Ures (L-PE) ≤ 0.9 kV (at 3 kA) ≤ 0.4 kV (at In) ≤ 0.25 kV (at 10 kA) ≤ 0.15 kV (at 5 kA) Residual voltage Ures (N-PE) ≤ 0.1 kV (at 3 kA)

335 V AC (5 s / withstand mode)TOV behavior at UT (L-N)

440 V AC (120 min / safe failure mode)

TOV behavior at UT (N-PE) 1200 V AC (200 ms / withstand mode) Response time tA (L-N) ≤ 25 ns Response time tA (L-PE) ≤ 100 ns Response time tA (N-PE) ≤ 100 ns

32 A (gG - 6 mm²)

35 A (gG - 10 mm²)

Max. backup fuse with V-type through wiring

40 A (MCB C - 10 mm²)

Max. backup fuse with branch wiring 125 A (gG) Environmental and real-life conditions Ambient conditions Degree of protection IP20 (only when all terminal points are used) Ambient temperature (operation) -40 °C ... 85 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Altitude ≤ 2000 m (amsl) Permissible humidity (operation) 5 % ... 95 % Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation) 2g (10 ... 500 Hz / 2.5 h / X, Y, Z) Standards and regulations Standards/specifications IEC 61643-11 Note 2011 Standards/specifications EN 61643-11 Note 2012 Mounting Mounting type DIN rail: 35 mm VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 4 (9)

89,8 97,2 71,2 65,7 Diagram  [°C] I [A] 40 50 60 70 80 90 10 mm 6 mm VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 5 (9)

VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 6 (9)

To download certificates, visit the product detail page: https://www.phoenixcontact.com/us/products/1248960  IECEE CB Scheme Approval ID: NL-71987 CCA Approval ID: NTR-NL 7875  KEMA-KEUR Approval ID: 71-118125 UAE-RoHS Approval ID: 22-09-51250 VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 7 (9)

ECLASS-11.0 27130805 ECLASS-13.0 27171202 ETIM ETIM 9.0 EC000941 UNSPSC UNSPSC 21.0 39121600 VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 8 (9)

Environmental product compliance EU RoHS Fulfills EU RoHS substance requirements Yes, No exemptions China RoHS EFUP-EEnvironment friendly use period (EFUP) No hazardous substances above the limits EU REACH SVHC REACH candidate substance (CAS No.) No substance above 0.1 wt% EF3.0 Climate Change CO2e kg 2.896 kg CO2e Phoenix Contact 2025 © - all rights reserved https://www.phoenixcontact.com Phoenix Contact USA

586 Fulling Mill Road

Middletown, PA 17057, United States (+717) 944-1300 info@phoenixcon.com VAL-MS 230/3+1 FM-PT - Type 2 surge arrester 1248960 https://www.phoenixcontact.com/us/products/1248960 Mar 24, 2025, 8:11 AM Page 9 (9)