1224 BELDEN | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 3

Technical content

Product: 1224 CAT5e+ Horizontal, 4pr, UTP, LSZH Jkt Product Description CAT5e+ (350MHz), 4-Pair, U/UTP-unshielded, Zero Halogen, Premise Horizontal cable, 24 AWG solid bare copper conductors, Polyethylene insulation, ripcord, LSZH jacket. Technical Specifications Product Overview Suitable Applications: Premise Horizontal Cable, Gigabit Ethernet, 100BaseTX, 100BaseVG ANYLAN, 155ATM, 622ATM, NTSC/PAL Component or Composite Video, AES/EBU, Digital Video, RS-422 Physical Characteristics (Overall) Conductor AWG Stranding Material No. of Pairs

24 Solid BC - Bare Copper 4

Conductor Count: 8 Total Number of Pairs: 4 Insulation Material PE - Polyethylene Bonded-Pair: N/A Color Chart Number Color

1 White/Blue Stripe & Blue

2 White/Orange Stripe & Orange

3 White/Green Stripe & Green

4 White/Brown Stripe & Brown

Material Material Trade Name Nominal Diameter Ripcord LSZH - Low Smoke Zero Halogen (Flame Retardant) Haloarrest® 0.193 in Yes

Electrical Characteristics

Max. Conductor DCR Max. DCR Unbalance

89 Ohm/km 3 %

Max. Capacitance Unbalance Nom.Mutual Capacitance 330 pF/100m 15 pF/ft Delay Frequency [MHz] Max. Delay Max. Delay Skew Nominal Velocity of Propagation (VP) [%] 100 MHz 537.6 ns/100m 25 ns/100m 70%

[MHz] Max. Insertion Loss (Attenuation) Min. NEXT [dB] Min. PSNEXT [dB] Min. ACR [dB] Min. PSACR [dB] Min. ACRF (ELFEXT) [dB] Min. PSACRF (PSELFEXT) [dB] Min. RL (Return Loss) [dB] Max./Min. Input Impedance (unFitted) Max./Min. Fitted Impedance Voltage UL Voltage Rating

300 V RMS

Installation Temperature Range: +5°C To +50°C Non-UL Temp Rating: +75°C Storage Temperature Range: -20°C To +75°C Operating Temperature Range: -20°C To +75°C Mechanical Characteristics Bulk Cable Weight: 25 lbs/1000ft Max. Pull Tension: 25 lbs Min. Bend Radius During Installation: 2.0 in Min. Bend Radius/Minor Axis: 1.0 in Standards NEC/(UL) Compliance: N/A ISO/IEC Compliance: 11801 ed 2.2 (2011) Class D CPR Euroclass: Eca Data Category: Category 5e ANSI Compliance: S-90-661-2012 Category 5e, ANSI/NEMA WC-63.1 Category 5e TIA/EIA Compliance: ANSI/TIA-568-C.2 Category 5e IEEE Compliance: IEEE 802.3bt Type 1, Type 2, Type 3 Other Specification: Verified Category 5e Applicable Environmental and Other Programs Environmental Space: Indoor - Euroclass Eca EU Directive 2000/53/EC (ELV): Yes EU Directive 2002/96/EC (WEEE): Yes EU Directive 2003/11/EC (BFR): Yes EU Directive 2003/96/EC (BFR): Yes EU Directive 2011/65/EU (RoHS 2): Yes EU Directive 2012/19/EU (WEEE): Yes EU Directive 2015/863/EU (RoHS 2 amendment): Yes EU Directive Compliance: Yes EU CE Mark: No

(yyyy-mm-dd): 2017-07-10 MII Order #39 (China RoHS): Yes Suitability Suitability - Aerial: No Suitability - Burial: No Suitability - Hazardous Locations: No Suitability - Indoor: Yes Suitability - Non-Halogenated: Yes Suitability - Oil Resistance: No Suitability - Outdoor: No Suitability - Sunlight Resistance: No Flammability, LS0H, Toxicity Testing IEC Flammability: IEC 60332-1-2 UL voltage rating: 300 V RMS Plenum/Non-Plenum Plenum (Y/N): No Plenum Number: 1213 Related Part Numbers Non-Plenum Number: 1212 Variants Item # Color Put-Up Type Length UPC/EAN 1224.08U305 Gray UnReel 305 m 8719605000682 1224.07U305 Purple UnReel 305 m 8719605000675 1224 007U1000 Purple UnReel 1,000 ft 612825061526 1224.09U305 White UnReel 305 m 8719605000705

1224.09500 White Reel 500 m 8719605000699

Notes: Electrical values are expected performance based on cable testing and representative performance within a typical Belden system. Values above 350 MHz are for Engineering Information Only. Print Includes Descending Footage/Meter Markings. History Update and Revision: Revision Number: 0.432 Revision Date: 11-09-2022 © 2022 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.