1180-01-10A E-T-A | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 5

Technical content

Thermal Overcurrent Circuit Breaker 1180-... www.e-t-a.de2308

Description

The 1180 is a thermal circuit breaker in a very compact design. It is designed as a replacement for conventional fuses in equipment for the AC and DC voltage range. It features reliable switching behaviour, snap action and positively trip-free mechanisms. Compared to conventional blade fuses, the 1180 significantly increases system availability thanks to its reset option. The plug-in type device is suitable for standard terminal blocks for DIN rail mounting. For maintenance purposes, the load can be directly switched off at the circuit breaker via push-push button. As the 1180 remains within the terminal block for this time, a loss of the device is prevented. Various accessories, such as bridging connectors and jumpers, are available for quick and easy LINE and GND wiring. It meets the requirements of the EN 60934 (IEC 60934) circuit breaker standard: S-Type, TO. Protection of loads in power distribution systems in control cabinets and process control. 1180-... Features and benefits l Easy mounting due to plug-in design matching standard terminal blocks l Fine grading of current ratings, particularly in the range of small ratings l Very small width of only 8.2 mm l Universally suitable for AC and DC applications Your benefits l Increased system availability by resetting the device after tripping and quick troubleshooting thanks to error detection message and/or auxiliary contacts. l Saves space and weight in the equipment thanks to the compact design of only 8.2 mm mounting width. l Saves maintenance costs, as the circuit breaker isolates the load path and can remain in the terminal block. Preferred types Standard current ratings (A) 0.5 1 1.5 2 2.5 3 4 5 6 8 10 1180-01- x x x x x x x x x x x Preferred types – for more details on all configurations please see order numbering code Preferred types are E-T-A products most frequently used by E-T-A customers. We manufacture E-T-A preferred types in particularly high volumes. Our preferred types are supplied at shorter lead times than non-standard versions. The current data sheet is available on our website: www.e-t-a.de/e004 Information onlineApprovals Compliances

Thermal Overcurrent Circuit Breaker 1180-... www.e-t-a.de 2308 Note: When several devices are mounted together, each device should only carry 80 % of its rating or it must be overrated accordingly. Follow the link to „Technical Information“: www.e-t-a.de/ti_e Technical data Technical data Voltage rating AC 250 V; DC 65 V (UL, UL Canada: AC 250 V; DC 72 V) Current ratings 0.1...10 A Typical life 6,000 operations at 1 x In (low-inductance) 3,000 operations at 1 x In (inductive) 500 operations at 2 x In (inductive) Insulation co-ordination rated impulse pollution (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength (IEC 60664 and 60664A) test voltage operating area AC 3,000 V installation area AC 1,500 V Insulation resistance > 100 MΩ (DC 500 V) Rupture capacity Icn 0,1…5 A 6 x In AC 250 V, DC 65 V 6…10 A 8 x In AC 250 V, DC 65 V 0,1...5 A 8 x In AC 120 V 6....10 A 12 x In AC 120 V 0.1…0.7 A 25 x In DC 30 V 0.8…6 A 10 x In DC 30 V 7…10 A 20 x In DC 30 V Rupture capacity AC 250 V 2,000 A (UL 1077) DC 72 V 2,000 A Degree of protection operating area IP40 (IEC 60529/DIN 40050) terminal area IP00 Vibration 5 g (57-500 Hz) ± 0.38 mm (10-57 Hz) without terminal block to IEC 60068-2-6, test Fc, 10 frequency cycles/axis and to EN 50155 Shock 25 g (11 ms) without terminal block to IEC 60068-2-27, test Ea Corrosion 96 hours at 5 % salt mist, to IEC 60068-2-11, test Ka Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab Mass approx. 10 g Preferred types Standard current ratings (A) 0.5 1 1.5 2 2.5 3 4 5 6 8 10 1180-01- x x x x x x x x x x x Preferred types Preferred types are E-T-A products most frequently used by E-T-A customers. We manufacture E-T-A preferred types in particularly high volumes. Our preferred types are supplied at shorter lead times than non-standard versions. Approvals Standard current ratings and typical internal resistance valuesOrdering information Type No. 1180 single pole thermal circuit breaker, plug-in mounting Versions 01 with switching function, without label 02 reset function only, without label Current rating range 0.1...10 A 1180 - 01 - 1 A ordering example Current rating (A) Internal resistance (Ω) Current rating (A) Internal resistance (Ω) 0.1 81 2 0.25 0.2 22 2.5 0.18 0.25 14 3 0.11 0.3 8.7 3.5 0.08 0.4 5.5 4 0.07 0.5 3.4 5 ≤ 0.05 0.6 2.5 6 ≤ 0.05 0.7 1.7 7 ≤ 0.05 0.8 1.5 8 ≤ 0.05 1 0.9 10 ≤ 0.05 1.5 0.4 Authority Standard Rated voltage Current ratings VDE IEC/EN 60934 AC 250 V DC 65 V

0.1 A…10 A

C22.2 No 235 AC 250 V / 50/60 Hz DC 72 V CSA C22.2 No 235 AC 250 V DC 72 V CQC GB/T17701 AC 250 V, DC 65 V 0,1...10 A

Thermal Overcurrent Circuit Breaker 1180-... www.e-t-a.de2308 Thermal Overcurrent Circuit Breaker 1180-... The time/current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. Ambient temperature °F -20 +14 -10 +32 +73,4 +23 +104 +40 122 +50 +140 +60 12 46 81 02 04 0 Trip time in seconds … times rated current 0.1 - 5 A 6 - 10 A 10000 1000 100 0.1 Dimensions Typical time/current characteristics at +23 °C/+73.4 °F 8.2 2.3° .717 19,8 18.2 16.6 14.5 5.2 6.4 8.6 8.2 1.9 1.5 48.6 ON 48.8

52.3 OFF

24.4 1.1 3.6 3.1 0.6 .961 .323 .339 .252 .205 .780 .654 .571 .323 .122 .142 .075 .059 1.91 1.92 2.06 .043 .024 slot for fitting labels (see accessory 1) This is a metric design and millimeter dimensions take precedence ( mm ) inch Internal connection diagram Shock directions current rating 1.0 A label Y 307 374 01 Installation drawing 2.5 Installation area Operating area 2.5 2.5 2.5

Thermal Overcurrent Circuit Breaker 1180-... www.e-t-a.de 2308 Accessories - Terminal block with screw terminals 42.7 33.8 36.4 64.3 Dimensions X 222 233 02 LED 1.33 1.43 1.68 2.53 .315 1 Label for circuit breaker 1180, surface for marking 4.5 x 5 mm (packaging quantity 120 pcs) Y30737401

2 Terminal block for DIN rail mounting, with screw terminals

up to 6 mm2 conductor, width 8.2 mm, stripping length: 10 mm dimensions 64 x 42.5 x 8.2 mm, headroom over the upper rail edge with circuit breaker fitted (OFF position) 84 mm. Approvals: UL File E197598 X22223301

3 Terminal block for DIN rail mounting see item 2,

but with LED DC 24 V (lighted after tripping); current rating LED 2 mA Approvals: UL File E197598 X22223302

4 Bus connection for potential bridging of several terminal blocks

see item 2 and 3 (10-pole, separable, mounting hardware included), max. current rating 34 A X22223201

5 Insulation barriers for insertion between two circuits

(packaging quantity 10 pcs) Y30737301

6 Label for terminal block, see item 2 and 3,

surface for marking 8 x 10 mm (packaging quantity 10 pcs) Y30737501 Vibration with terminal block X22223301 and X22223302 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc, 10 frequency cycles/axis and EN 50155 Shock with terminal block X22223301 and X22223302 25 g (11 ms) to IEC 60068-2-27, test Ea This is a metric design and millimeter dimensions take precedence ( mm ) inch

Thermal Overcurrent Circuit Breaker 1180-... www.e-t-a.de2308 Thermal Overcurrent Circuit Breaker 1180-... This is a metric design and millimeter dimensions take precedence ( mm ) inch Accessories - Terminal block with spring-loaded terminals 42.28.2 86.5 Dimensions X 222 316 01 1.66.323 3.41 1 Label for circuit breaker 1180, surface for marking 4.5 x 5 mm (packaging quantity 120 pcs) Y30737401

7 Terminal block for DIN rail mounting, with spring-loaded

terminals up to 4 mm2 conductor, width 8.2 mm, dimensions over the upper rail edge with circuit breaker fitted (OFF position) 82 mm. Approvals: UL File E197598 X22231601

8 Terminal block for DIN rail mounting see item 7, but with

LED DC 24 V (lighted after tripping); current rating LED 2 mA Approvals: UL File E197598 X22231502 9 Jumper 2pole, max. current rating 32 A for terminal blocks items 7 and 8 and feed supply terminal item 11. X22231801 10 Jumper 3pole, max. current rating 32 A for terminal blocks items 7 and 8 and feed supply terminal item 11. X22231802

11 Feed supply terminal with spring-loaded terminals

up to 6 mm2 conductor, width 8.2 mm, suitable for use with jumpers items 9 and 10 (power distribution). X22231701

12 Cover for feed supply terminal item 11 for closing the open

side at the end of an assembly. Y30750701

13 Label for terminal block items 7 and 8,

and feed supply terminal item 11, surface for marking 7.5 x 5 mm (packaging quantity 50 pcs) Y30750801 All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. Vibration with terminal blocks X22231601 and X22231502 vibration axis 3-4: 3 g (57-500 Hz), ± 0.38 mm (10-57 Hz) other axes: 5 g (57-500 Hz), ± 0.38 mm (10-57 Hz) to IEC 60068-2-6, test Fc, 10 frequency cycles/axis and EN 50155 Shock with terminal blocks X22231601 and X22231502 25 g (11 ms) to IEC 60068-2-27, test Ea