8447050000 WEIDMULLER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 58

Technical content

Analogue Signal Processing

The real world can be measured in many ways, for example, via temperature, humidity, air pressure and so forth. The parameters of these different physical qualities change continuously. Elements that monitor statuses and changes in sta- tuses of a given environment, must reflect these continual changes. Within the framework of industrial moni- toring tasks, the statuses of an environ- ment are monitored by using sensors. These sensors should provide signals that enable connected evaluating and monitor- ing installations to draw detailed conclu- sions concerning the status of, for exam- ple, a production process. The sensor sig- nals trace the continuous changes in the monitored range. The signals can be in analogue or digital form; which means in normal cases, an electrical voltage or cur- rent value is produced that corresponds proportionally to the monitored physical quantities. Increasing automation with the intention of achieving or maintaining cer- tain predetermined statuses makes the processing of analogue values increasingly important. This is also true of fields beyond those where this has been neces- sary and standard for a long time, for example, processing technology in the chemical industry. Standard electrical signal values are the norm within the framework of this processing technology. Current values from 0...20 mA, 4...20 mA or voltage values from 0...10 V have been introduced as sensor output values for differing physical quantities. Weidmüller has taken account the need for increasing automation with the processing of these analogue signals, and offers a wide range of products that are designed for handling sensor signals. This means, units are made available for standard signals (0...20 that generate output signal values proportional to the variable input signals, and at the same time enable the safe separation of, for example, sensor circuits of an evaluation circuit. This safe separation is particularly important to avoid mutual interference of multiple sensor circuits, for example, ground loops in interlinked measurement circuits. The wide range of products includes all functions for converting separation and monitoring signals. The different designs in connection with the respective functions cover practically all applications in industrial measurement technology. With these new products, Weidmüller offers the possibility of taking into account the demands of modern automation technology with the inclusion of analogue signals. These products guarantee an elementary function between signals from the field and the further processing systems. The mechanical characteristics of these products correspond to those of the well-known Weidmüller products and are part of a continuous, ongoing concept. The signal conditioners can be combined together with other Weidmüller products. They have been electrically and mechanically designed to ensure that only a minimum of wiring and maintenance costs are necessary. The product program contains the following functions: z Current transformer z Voltage transformer z Thermocouple conditioners for resistance thermometers z Frequency signal conditioner z Potentiometer conditioner z AC signal conditioner z Bridge measurement conditioner z Limit value monitoring modules z AD/DA converter These products are categorised according to functionality as pure signal conversion, 2-way-isolation, 3-way-isolation and as passive separation. Analogue Signal Processing

2-way-isolation separates the signals galvanically and decouples the measurement circuits. In so doing it eliminates potential differences caused by long cable lengths and common reference points. Furthermore, the galvanic isolation offers protection against destruction by overvoltage, and against inductive and capacitive interferences. 3-way-isolation also decouples the supply voltage from the input and output circuits, and enables the function with only one operating voltage. The passive isolator offers a further elementary advantage; it needs no additional volt- age supply. The supply to the modules ensues via the input circuit and is the trans- ferred to the output. This current loop supply is distinguished by very low power con- sumption. There are a large number of products available for measuring temperatures. RTD PT100 signals, in 2-, 3- and 4-wire technology, are converted to standardised 0 – 20 mA, 4 – 20 mA and 0 – 10 V signals. The modules which can be connected to commercially available thermocouples have cold junction compensation as standard. Furthermore, the modules amplify and linea- rize the voltage signals from the thermocouple. This guarantees an exact conditioning of analogue signals by eliminating sources of interference and errors. Frequency converters convert frequencies to standard analogue signals. This enables controllers connected in series to directly process impulse trains when making speed or rotational speed measurements. It is inconceivable to think about automation without analogue-digital-analogue converters. To bring together the aforementioned analogue form of describing the envi- ronment and the customary digital processing, within the framework of process moni- toring, it is necessary to convert analogue signals into digital signals. Weidmüller offers for making instantaneous measurements. Current monitoring modules enable the monitoring of current values up to 60 A in alternating or direct voltages. Over range or under range values trip the switching out- put. Modules with analogue outputs enable the continuous monitoring of currents via connected controls. Voltage monitoring modules can be used to monitor direct and alternating voltages. Voltage fluctuations, resulting from switching operations or network overloads, can be reliably recognised and reported via the adjustable threshold function. Modules for monitoring of revolutions and torque enable the control of cyclic move- ments on conveyor belts, ventilators and pumps. The output responds after a set amount of time, should the expected impulse not be received. The reliable potential- free relay contact, signalises the interference to the responsible component group. Analogue Signal Processing

Mini Coupler / Mini Conditioner WAVESERIES DK Mini Coupler / MCZ Mini Conditioner z Extensive range of electronic functions in terminal format z Pluggable cross-connections with mini conditioners z Mini couplers with screw-in cross-connection combs z Mini couplers with screw connections z Mini conditioners with tension clamp connections WAVEANALOG / WAVEANALOG PRO / WAVECONTROL z Pluggable PCB for fast service when the configuration is changed z Pluggable cross-connection in base socket housing to distribute the power supply, marking (CC) in the block diagram on the head plate z Pluggable connections with optional screw or tension clamp connection RS profiles Analog-/Digital-Converters z Mounts onto TS 32 and TS 35 mounting rails z Open, cost-saving design z Variable housing width

Function Areas of application Description Versions Page DC signal conditioners PT100 signal conditioners Thermocouple conditioners Frequency signal conditioners AD/DA converters Current monitoring Voltage monitoring Motion and rotational speed monitoring Namur switching amplifier Setpoint device 160 Signal conditioning, signal isolation, DC input/fixed functions MCZ 164 suppression of mass loops and configurable inputs and WAVE ANALOG 174-184 outputs WAVE ANALOG PRO 185 Motor current limitation, pressure DC input/limit value DK 172 alarm, direct disconnection of monitoring MCZ 173 connected modules, safety function Temperature monitoring, noise rejec- RTD input/fixed functions MCZ 165 tion, electrical decoupling of visualiza- and configurable inputs and WAVE ANALOG 186-188 tion devices, suppression of mass outputs WAVE ANALOG PRO 189 loops, heating and cooling monitoring, overheating protection of motors Temperature monitoring, noise rejec- Thermo input/fixed functions WAVE ANALOG 190 tion, electrical decoupling of visualiza- and configurable inputs and WAVE ANALOG PRO 191 tion devices, suppression of mass outputs loops, heating and cooling monitoring, overheating protection of motors Flow rate measurements, frequency Input/fixed functions and DK 167-168 converter monitoring, speed measure- configurable inputs and MCZ 166 ments, pulse processing outputs Conditioning of voltage and current 8-bit AD/DA converter RS 210-213 signals in 8-bit/12-bit digital form 12-bit AD/DA converter Motor current monitoring, AC input/measuring of DKI 172 emergency lighting monitoring sinusoidal and non sinusoidal WAVE CONTROL 196-199 signals up to 60A SMSI 200-203 Under and overvoltage monitoring, One and three-phase SMSU 204-205 operating status indication overvoltage Downtime monitoring, conveyor-drive PNP/NPN or NAMUR DKLW 169 monitoring, monitoring of fans, pumps input/switching output SMS 206 or pistons Switching amplifier Namur input/switching output EGV 207 Testing measuring distances, defined 1 control input/+/-set value/ EMA/SW24 208 input of analogue values analogue output Selection Table of Functions

DC/DC 0…20mA 0…20mA yes Without auxiliary pwr. Fixed 6 Tens. clamp 8411190000 164 current loop supply from input 0…20mA 0…20mA yes Without auxiliary pwr. Fixed 17.5 Screw/ 8444950000/ 174 current loop supply tens. clamp 8444960000 from input (1-channel) 0…20mA 0…20mA yes Without auxiliary pwr. Fixed 17.5 Screw/ 8463580000/ 174 current loop supply tens. clamp 8463590000 from input (2-channel) 0…20mA 0…20mA 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8445070000/ 176 Voltage supply of tens. clamp 8445080000 both sides 0…20mA 0…20mA yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540180000/ 178 tens. clamp 8540190000 0…20mA 0…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447160000/ 181 tens. clamp 8447170000 0…20mA 4…20mA 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8446970000/ 176 Voltage supply of tens. clamp 8446990000 both sides 0…20mA 4…20mA yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540250000/ 181 tens. clamp 8540260000 0…20mA 4…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447190000/ 181 tens. clamp 8447200000 0…20mA 0…10V 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8447020000/ 176 Voltage supply of tens. clamp 8447030000 both sides 0…20mA 0…10V yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540270000/ 178 tens. clamp 8540280000 0…20mA 0…10V 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447220000/ 181 tens. clamp 8447230000 4…20mA 0…20mA 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8444980000/ 175 Voltage supply of tens. clamp 8444990000 output side 4…20mA 0…20mA yes 18…30Vdc Fixed/10 kHz 17.5 Screw/ 8540200000/ 179 tens. clamp 8540210000 4…20mA 0…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447250000/ 182 tens. clamp 8447260000 4…20mA 4…20mA 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8445010000/ 175 Voltage supply of tens. clamp 8445020000 output side 4…20mA 4…20mA yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540180000/ 178 tens. clamp 8540190000 4…20mA 4…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447160000/ 182 tens. clamp 8447170000 4…20mA 0…10V 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8445040000/ 175 Voltage supply of tens. clamp 8445050000 output side 4…20mA 0…10V yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540230000/ 179 tens. clamp 8540240000 4…20mA 0…10V 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447280000/ 182 tens. clamp 8447290000 0…10V 0…20mA 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8447050000/ 177 Voltage supply of tens. clamp 8447080000 both sides 0…10V 0…20mA yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540310000/ 180 tens. clamp 8540320000 0…10V 0…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447310000/ 183 tens. clamp 8447320000 0…10V 4…20mA 2-way 19.2…28.8V/ Fixed 12.5 Screw/ 8447100000/ 177 Voltage supply of tens. clamp 8447110000 both sides 0…10V 4…20mA yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540290000/ 180 tens. clamp 8540300000 0…10V 4…20mA 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447340000/ 183 tens. clamp 8447350000 0…10V 0…10V 2-way 19.2…28.8Vdc/ Fixed 12.5 Screw/ 8447130000/ 177 Voltage supply of tens. clamp 8447140000 both sides Function Input Output Galvanic Voltage supply Setting Module Connection Cat. No. Page isolation width/mm type Selection Table Analogue Signal Processing 161 Analogue Signal Processing

0…10V 0…10V yes 18…30Vdc Fixed/10 Hz 17.5 Screw/ 8540330000/ 180 tens. clamp 8540340000 0…10V 0…10V 3-way 18…30Vdc Fixed/20 kHz 17.5 Screw/ 8447370000/ 184 tens. clamp 8447380000 Variable voltage Variable voltage yes 20…253Vdc DIP switch 12.5 Screw/ 8560740000/ 185 and current and current Potentiometer tens. clamp 8560750000 +/-0.1mA…+/-100mA) -20mA…+20mA) PT100/ (4)…20mA no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432210000/ 186 tens. clamp 8432220000 RTD/DC PT100/ 0…10V no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432180000/ 186 2-wire Potentiometer tens. clamp 8432190000 PT100/ 4…20mA no current loop supply Fixed 6 Tens. clamp 8425720000 165 2-wire in output PT100/ 0(4)…20mA no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432150000/ 187 3-wire Potentiometer tens. clamp 8432160000 PT100/ 0…10V no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432090000/ 187 3-wire Potentiometer tens. clamp 8432130000 PT100/0 (4)…20mA no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432270000/ 188 4-wire Potentiometer tens. clamp 8432280000 PT100/ 0…10V no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432240000/ 188 4-wire Potentiometer tens. clamp 8432250000 PT100/ 0…10V yes 18…30Vdc DIP switch 17.5 Screw/ 8560700000/ 189 2-/3-/4-conduct. 0…20mA Potentiometer tens. clamp 8560710000 Ni100 4…20mA Potentiometer: min. 0…100 Ω max. 0…100k Ω R: 0…450 Ω Thermo/DC K, J, T, E, N, R, S, B Thermo 0…10V no 19.2…28.8Vdc DIP switch 12.5 Screw/ 8432300000/ 190 K, J, T, E, N, 0…20mA tens. clamp 8432310000 R, S, B 4…20mA Thermocouples 0…10V yes 18…30Vdc DIP switch 17.5 Screw/ 8560720000/ 191 K, J, T, E, N, 0…20mA Potentiometer tens. clamp 8560730000 R, S, B 4…20mA 0…1/5/10/16kHz 0…1/5/10/16kHz 0...1/5/10/16kHz 4…20mA 0...1/5/10/16kHz no current loop supply DIP switch 6 Screw 8081330000 167 in input 4…20mA 0...1/5/10/16kHz no current loop supply DIP switch 6T ens. clamp 8461490000 166 in input Variable, Switching output no 19.2…28.8Vdc Fixed 12 Screw 8248340000 170- programmable PNP 171 Limit value 0…20mA Switching output no 19.2…28.8Vdc Potentiometer 6 Screw 8031320000 172 monitoring PNP 2-channel 0…20mA Switching output no 19.2…28.8Vdc Potentiometer 6T ens. clamp 8227350000 173 PNP 2-channel 0…10V Switching output no 19.2…28.8Vdc DIP switch 6 Screw 8019640000 172 PNP 2-channel Potentiometer 0…10V Switching output no 19.2…28.8Vdc DIP switch 6T ens. clamp 8260280000 173 PNP 2-channel Potentiometer AD convert. 0…20mA 8-bit no 19.2…28.8Vdc Fixed 70 Screw 1160561001 210 4…20mA 8-bit no 19.2…28.8Vdc Fixed 70 Screw 1168561001 210 0…10V 8-bit no 19.2…28.8Vdc Fixed 70 Screw 1160361001 210 8-bit no 19.2…28.8Vdc Fixed 70 Screw 1122361001 210 0…20mA 12-bit no 19.2…28.8Vdc Fixed 70 Screw 1168461001 212 4…20mA 12-bit no 19.2…28.8Vdc Fixed 70 Screw 1169161001 212 0…10V 12-bit no 19.2…28.8Vdc Fixed 70 Screw 1168361001 212 12-bit no 19.2…28.8Vdc Fixed 70 Screw 1168261001 212 Function Input Output Galvanic Voltage supply Setting Module Connection Cat. No. Page isolation width/mm type 162 Selection Table

Function Input Output Galvanic Voltage supply Setting Module Connection Cat. No. Page isolation width/mm type Analogue Signal Processing 163 Analogue Signal Processing 1) Switch output / 1 changeover contact 2) 0…10 V, 0 (4)…20 mA switchable 3) 4…20 mA / current loop supply 4) Switch output / 1 changeover contact 5) 0…10 V, 0 (4)…20 mA switchable DIP switch./P* = DIP switch / Potentiometer Selection Table DA convert. 8-bit 0…20mA no 19.2…28.8Vdc Fixed 70 Screw 1165860000 211 8-bit 4…20mA no 19.2…28.8Vdc Fixed 70 Screw 1169260000 211 8-bit 0…10V no 19.2…28.8Vdc Fixed 70 Screw 1160760000 211 8-bit no 19.2…28.8Vdc Fixed 70 Screw 1123360000 211 12-bit 0…20mA no 19.2…28.8Vdc Fixed 70 Screw 1166060000 213 12-bit 4…20mA no 19.2…28.8Vdc Fixed 70 Screw 1165960000 213 12-bit 0…10V no 19.2…28.8Vdc Fixed 70 Screw 1166160000 213 12-bit no 19.2…28.8Vdc Fixed 70 Screw 1160860000 213 Current 0…1/5/10 Aac 1) 2-way 21.6…26.4Vdc DIP sw./P* 22.5 Screw 8516560000 196 0…20/40/60 Aac 1) 2-way 21.6…26.4Vdc DIP sw./P* 22.5 Screw 8513340000 196 0…1/5/10 Aac 2) 2-way 21.6…26.4Vdc DIP switch 22.5 Screw 8523400000 197 0…1/5/10 Aac 3) 2-way 12…30Vdc DIP sw./P* 22.5 Screw 8528650000 197 0…1/5/10 Aac 3) 2-way 12…30Vdc DIP sw./P* 22.5 Tens. clamp 8528660000 197 0…5/10 Aac 4) 2-way 21.6…26.4Vdc DIP sw./P* 22.5 Screw 8526610000 198 0…20/25/30 Aac 4) 2-way 21.6…26.4Vdc DIP sw./P* 22.5 Screw 8545830000 198 0…20/40/60 Aac 4) 2-way 21.6…26.4Vdc DIP sw./P* 22.5 Screw 8513330000 199 0.1…2A Switching output no 18…30Vdc Fixed 6 Screw PNP 1…50mAdc Opto-coupler yes 10…250Vdc Op. point 22.5 Screw 1157160000 200 40…250mAdc Opto-coupler yes 10…250Vdc Op. point 22.5 Screw 1156360000 200 40…250mAdc Opto-coupler yes 10…250Vdc Op. point 22.5 Screw 1156460000 201 0.2…2.2Aac Opto-coupler yes 10…250Vdc Op. point 22.5 Screw 1157360000 201 1…5Aac 21.6…26.4Vuc yes 10…250Vdc Fixed 22.5 Screw 1112160000 201 1…5Aac 5…48Vdc yes 10…250Vdc Fixed 22.5 Screw 8026930000 201 1…5Aac LED yes 10…250Vdc Fixed 22.5 Screw 1112060000 201 1…5Aac NO 1-channel yes 10…250Vdc Fixed 22.5 Screw 1112260000 203 Voltage 1-24Vdc CO 1-channel yes 21.6…26.4Vuc Op. point 22.5 Screw 0555060000 205 monitoring 1-230Vuc CO 1-channel yes 207…253Vac Op. point 22.5 Screw 0555160000 205 18…24Vac CO 1-channel yes 18…27Vac Op. point 22.5 Screw 1156760000 204 36…48Vac CO 1-channel yes 36…53Vac Op. point 22.5 Screw 1157660000 204 83…110Vac CO 1-channel yes 83…121Vac Op. point 22.5 Screw 1157760000 205 165…220Vac CO 1-channel yes 165…253Vac Op. point 22.5 Screw 1157860000 205 200…260Vac NO 1-channel yes 200…299Vac Op. point 22.5 Screw 1160160000 205 motion and 24Vdc r.p.m. monitoring Namur switch Namur NO 1-channel no 21.6…26.4Vdc no 22.5 Screw 1120360000 207 amplifier Namur PNP/NPN no 21.6…26.4Vdc no 22.5 Screw 1122460000 207

MCZ CCC 0…20 mA/0…20 mA Type Cat. No. MCZ CCC 0…20 mA/0…20 mA 8411190000 without power supply 0…20 mA (max. 15 V) < 100 µA 2.5…3 V (at 20 mA) 50 mA, 15 V 0…20 mA (max. 10 V) approx. 5 ms at 500 Ω working resistance impedance < 10 mVeff approx. 200 kHz < 0.1 % from end value, + 0.05 % from mean/100 Ω working resistance < 50 ppm/K from measurement value for working resistance 0 Ω

510 Veff

CE, UL, CSA -25 °C…+40 °C -25 °C…+50 °C -40 °C …+85 °C AWG 22…12 1.5 mm2 6 mm Page 305 Ordering data for TS 35 Technical data Input Response current Voltage drop Max. overload capacity at input Output Set time (T99) Residual ripple Chopper frequency Transmission error Temperature effect Voltage strength Input/output EMC Approvals Ambient temperature - assembled without spacing - assembled with 20 mm spacing Storage temperature Conductor Conductor cross-section Overall width Dimensions and accessories see Working resistance diagram 100 500 RB ( Ω) IE = IA = 20 mA UE (V) This module is a reasonably priced passive separator for galvanically separating standard It draws its power from the measurement signal and requires no further auxiliary power. The measurement signal is transmitted 1:1. The module is distinguished by its low power con- sumption as well as a response current <100 µA.

RTD Thermocouple Conditioners Analogue Signal Processing Block diagram MCZ PT100/3 CLP Type Cat. No. MCZ PT100/3 CLP 0…100 °C 8425720000 MCZ PT100/3 CLP 0…120 °C 8483680000 MCZ PT100/3 CLP 0…150 °C 8604420000 MCZ PT100/3 CLP 0…200 °C 8473010000 MCZ PT100/3 CLP 0…300 °C 8473020000 MCZ PT100/3 CLP -50…+150 °C 8473000000 MCZ PT100/3 CLP -40…100 °C 8604430000 PT 100 (according to IEC 751) 3-wire / 2-wire* each 50 Ω max. 0.006 °C/ Ω 0.8 mA 4…20 mA 750 Ω at 24 V max:30V/min:9V+20mA x R L max: 1.5 V at 100 Hz 10 ms <0.1 % v. FSR max. ±250 ppm/°C yes EMVG EN 50081-1 EN 50082-2 CE, UL, CSA 0 °C…+50 °C -20 °C…+85 °C AWG 22…12 1.5 mm2 6 mm current loop supplied Page 305 Ordering data for TS 35 Technical data Input Connection Max. wire resistance Leadwire resistance effect Supply current Output Load Supply voltage Residual ripple of supply voltage Set time Accuracy Linearity Temperature coefficient Open circuit recognition EMC Approvals Ambient temperature Storage temperature Conductor Conductor cross-section Overall width * Putting a bridge between Pins 4 and 5 Dimensions and accessories see The temperature module converts measurement values from a PT 100 into analogue measure- ment signals. The module supplies the sensor with power. The module is distinguished by its accuracy and linearity.

  • for 2 and 3 wire sensors

*w ithout DC/DC converter input supply vie current loop 166 Frequency Signal Conditioners Ordering data for TS 35 W Technical data Input ranges Overload limits, input Input resistance Voltage drop, input Output Output frequency, end value Frequency adjustment Readjustment range Output level Output current Display Supply voltage Power consumption Making current limit Polarisation protection Accuracy Temperature coefficient Coordination of insulation according to EN 50178 Voltage strength input/output Rated voltage Rated surge voltage Overvoltage category Voltage strength I/O to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section Dimensions and accessories see Type Cat. No. MCZ VFC 8461470000 0…10 V 30 V 100 kΩ 1 kHz, 4 kHz, 8 kHz, 16 kHz DIL switch ±10 %, internal PNP , Ub- 0.7 V max. 20 mA LED, pulsing

24 Vdc ±10 %

14 mA, w/o load 200 mA yes 0.2 % v. FSR < 250 ppm/°C 1 kVdc 100 V 1.5 kV III 4 kVeff/ 1 min 0 °C…+50 °C -25 °C…+85 °C 6 mm 1.5 mm2 Page 305 Type Cat. No. MCZ CFC 8461480000 0…20 mA 50 mA 50 Ω

1 V at 20 mA

1 kHz, 4 kHz, 8 kHz, 16 kHz DIL switch ±10 %, internal PNP , Ub- 0.7 V max. 20 mA LED, pulsing 0.2 % v. FSR < 250 ppm/°C 1 kVdc 100 V 1.5 kV III 4 kVeff/ 1 min 0 °C…+50 °C -25 °C…+85 °C 6 mm 1.5 mm2 Page 305 Type Cat. No. MCZ CFC 8461490000 4…20 mA LP* 50 mA 5.8…6.4 at 20 mA 1 kHz, 4 kHz, 8 kHz, 16 kHz DIL switch ±10 %, internal PNP , Ub- 0.7 V max. 20 mA LED, pulsing

24 Vdc ±20 %

0.15 % v. FSR < 250 ppm/°C 150 V 2.5 kV III 4 kVeff/ 1 min 0 °C…+50 °C -25 °C…+85 °C 6 mm 1.5 mm2 Page 305 The option of reading-in the analogue signals from the field via counter inputs of the control is made possible by converting the analogue sig- nals in to frequencies. It is recommended that twisted and shielded 2-wire cables are used.

  • Tension clamp connection
  • LED-Display
  • Adjustable frequency output MCZ CFC 0…20 mA MCZ CFC 4…20 mA CLP MCZ VFC 0…10 V MCZ VFZ 0…10 V and MCZ CFC 0…20 mA 12 34 DIP switch 10 00 0…16 kHz 01 00 0…8 kHz 00 10 0…4 kHz 00 01 0…1 kHz MCZ CFC 4…20 mA CLP 12 34 DIP switch 10 00 3.2…16 kHz 01 00 1.6…8 kHz 00 10 0.8…4 kHz 00 01 0.2…1 kHz Block diagram/settings
  • Screw connection
  • LED-Display Adjustable frequency output 167 Frequency Signal Conditioners Analogue Signal Processing DKA U/f and DKA I/f 12 34 DIP switch 10 00 0…16 kHz 01 00 0…8 kHz 00 10 0…4 kHz 00 01 0…1 kHz Block diagram/settings Ordering data for TS 32 Y for TS 35 W with combi foot TS 32/TS 35 Technical data Input ranges Overload limits, input Input resistance Voltage drop, input Output Output frequency, end value Frequency adjustment Readjustment range Output level Output current Display Decoupling diode Supply voltage Power consumption Making current limit Polarisation protection Accuracy Coordination of insulation to DIN VDE 0160, Draft 11/94 Voltage strength input/output Rated voltage Rated surge voltage Overvoltage category Voltage strength to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section Accessories End plate Dimensions and accessories see Type Cat. No. DKA U/f 8242040000 0…10 V 100 V 100 kΩ 1 kHz, 4 kHz, 8 kHz, 16 kHz DIL switch ±10 %, internal PNP , Ub- 0.7 V max. 20 mA LED, pulsing present

14 mA, w/o load 200 mA yes 0.2 % v. FSR <250 ppm/°C 1 kVdc 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Type Cat. No. AP DK5 8268870000 Page 305 Type Cat. No. DKA I/f 8258870000 0…20 mA 50 mA 50 Ω 1 kHz, 4 kHz, 8 kHz, 16 kHz DIL switch ±10 %, internal PNP , Ub- 0.8 V max. 20 mA LED, pulsing present 0.2 % v. FSR <250 ppm/°C 1 kVdc 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Type Cat. No. AP DK5 8268870000 Page 305 Type Cat. No. DKA I/f * 8081330000 4…20 mA 50 mA max. 320 Ω at 20 mA max. 6.4 V at 20 mA 5 kHz (1…5 kHz) Ub- 3 V max. 20 mA present 19.2…28.8 Vdc <13 mA w/o load yes 0.15 % v. FSR <250 ppm/°C 2 4 kVeff 150 V 2.5 kV III 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Type Cat. No. AP DK5 8268870000 Page 305 DKA I/f DKA I/f*DKA U/f For EMC reasons, frequency processing mod- ules must be used in conjunction with shielded cables. This measure prevents interference of analogue and frequency signals by other signal cables and vice versa. * without DC/DC converter Input current loop supplied

Frequency Signal Conditioners Ordering data for TS 32 Y for TS 35 W with combi foot TS 32/TS 35 Technical data Input ranges Overload limits, input Input resistance Voltage drop, input Output Output frequency, end value Frequency adjustment Readjustment range Output level Output current Display Decoupling diode Supply voltage Power consumption Making current limit Polarisation protection Accuracy Coordination of insulation to DIN VDE 0160, Draft 11/94 Voltage strength input/output Rated voltage Rated surge voltage Overvoltage category Voltage strength to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section Dimensions and accessories see DKA f/U Type Cat. No. DKA f/U 8283810001 0…50/100/500 Hz 0…1/5/10/16 kHz 10 kΩ 0/2…10 V DIL switch 0.5 % (8-bit resolution) 2.5 kV 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Page 305 DKA f/I Type Cat. No. DKA f/I 8311870001 0…50/100/500 Hz 0…1/5/10/16 kHz 10 kΩ 0/4…20 mA DIL switch 0.5 % (8-bit resolution) 2.5 kV 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Page 305 12 34 DIP switch 00 0X 0…50 Hz 10 0X 0…100 Hz 01 0X 0…500 Hz 11 0X 0…1 kHz 01 1X 0…5 kHz 10 1X 0…10 kHz 11 1X 0…16 kHz 00 1X Customer specific XX X0 0…20 mA / 0…10 V XX X1 4…20 mA / 2…10 V For EMC reasons, frequency processing mod- ules must be used in conjunction with shielded cables. This measure prevents interference of analogue and frequency signals by other signal cables and vice versa. Block diagram/settings

  • Screw connection
  • LED-Display
  • Adjustable frequency output
  • multiplex capable

Reverse polarity protection Output Function Output level Output current Decoupling diode Status LED Short-circuit proof Operating voltage Power consumption Reverse polarity protection Galvanic isolation Voltage strength to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section Insulation stripping length Others Accessories End plate Dimensions and accessories see Type Cat. No. DK LW 8258680000 Initiators, NPN or PNP 10 - 6250 U/min. 3 switchable revolutions ranges: 10-130, 100-1300, 1000-7800 r.p.m. 2 potentiometers for upper/lower revs limit

24 Vdc = High, O V = Low

30 Vdc

High >18 V, Low <7 V >0.5 ms approx. 3.5 mA (24 V) yes Optional PNP or NPN Output active, if f within set revs limit Ub- 1.8 V 20 mA max. yes green LED no

24 V –10 % + 20 %

<10 mA, w/o load, without initiator yes no 4 kVeff 0…+50 °C -40…+60 °C 12 mm 0.5…4 mm 2 7 mm Initiator power supply via module possible Type Cat. No. AP DKT4 0687560000 Page 278 Monitoring Revolutions DK LW If only one revolution limit is to be evaluated, the potentiometer for fmax must be set to end stop or the potentiometer for fmin to left stop. Then only the other is in each case active for setting the limit value. Block diagram/settings

Reverse polarity protection Galvanic isolation Voltage strength to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section Insulation stripping length Accessories End plate Ordering example: RS FLIP-FLOP Dimensions see Type Cat. No. on request DK PL 8248340000* Programmable, see note

24 Vdc = High, 0 V = Low

High >18 V, Low <7 V >1 ms approx. 1.5 mA per input (24 V) PNP Ub- 1 V 20 mA max. no green LED no

24 V ±20 %

<10 mA yes no 4 kVeff 0 °C…+50 °C -40 °C…+60 °C 12 mm 0.5…4 mm 2 7 mm Type Cat. No. AD DKT4 0687560000 8248340002 Page 278 DK PL

  • Screw connection
  • logic function and time function combined
  • individually programmable (further functions on request) Block diagram * (not programmed - function next page)

Remark: The module is programmed according to customers specifications. Up to 5 inputs can be linked with various logic and timer functions, e.g.: AND, OR, EXOR, NAND, NOR, EXNOR, delay elements, etc. The output is either low or high active. 824834 0002 DKPL Inputs 1 and 2 have the function of a RS FLIP-FLOP Inputs 3, 4 and 5 have no function Input Output 21 6 00 0 (is stored)

01 No change of stored state

10 No change of stored state

11 1 (is stored) Inputs 3, No change of stored state 4 and 5 no function 824834 0001 DKPL A = (E1 OR E2) AND (E3 OR E4) AND E5 State Input Output 54 32 1 6 10 0 0 00 0 20 0 0 01 0 30 0 0 10 0 40 0 0 11 0 50 0 1 00 0 60 0 1 01 0 70 0 1 10 0 80 0 1 11 0 90 1 0 00 0 10 0 1 00 1 0 11 0 1 01 0 0 12 0 1 01 1 0 13 0 1 10 0 0 14 0 1 10 1 0 15 0 1 11 0 0 16 0 1 11 1 0 17 1 0 00 0 0 18 1 0 00 1 0 19 1 0 01 0 0 20 1 0 01 1 0 21 1 0 10 0 0 22 1 0 10 1 1 23 1 0 11 0 1 24 1 0 11 1 1 25 1 1 00 0 0 26 1 1 00 1 1 27 1 1 01 0 1 28 1 1 01 1 1 29 1 1 10 0 0 30 1 1 10 1 1 31 1 1 11 0 1 32 1 1 11 1 1 824834 0003 DKPL - Frequency divider Inputs 1 - 5 determine the divider factor Input 1 = divider factor 1: F OUT = FIN 1 Input 2 = divider factor 2: F OUT =F IN 2 Input 5 = divider factor 5: F OUT = FIN 5; FIN max. = 12 kHz Input Output 1f out = fin 2f out = fin / 2 3f out = fin / 3 4f out = fin / 4 5f out = fin / 5 Note: An new divider factor can only be used if operating voltage is switched off. fin max. = 12 kHz 824834 0004 DKPL Input 1: Signal A of an incremental generator Input 2: Signal B 90 is shifted Input 3: Enable High Active Input 4: Output signal inverts High Active Input 5: No function Output: For each slope of signal A or B, the output is set to 20 - 30 Us. (I.e.: F OUT = 4xFIN) FIN max. 1 kHz Connection Description 1A Signal A 90 ° leading F max = 1 kHz 2B Signal B 90 ° following F max = 1 kHz

3 Enable Output is released

4 Invert Output signal invert

5 No function

6f out = 4 x fA/B (max. 4 kHz) 824834 0006 DKPL Input 1: FOUT = FIN Input 2: FOUT =F IN 10 Input Output 1f out = fin 2f out = fin / 10 3f out = fin / 50 4f out = fin / 100 5f out = fin / 1000 Note: A new divider factor can only be used if the operating voltage is switched off. fin max. = 3 kHz 824834 007 DKPL Input Output 12 345 O u t LL XXX No function HL XXX f = 1 Hz LH XXX f = 10 Hz HH XXX f = 1 Hz L -> 0 V or connection open H -> +24 …30 Vdc X -> no effect on output function, L or H 824834 0005 DKPL Length of input signal between 80 and 100 ms. Length of output signal 100 ms, only 2 pulses, Relation pulse-interruption 1:1. The positive slope of the input signal has to be analysed. Only input E1 is used. 824834 0501 DKPL The module allows the input frequency at connection 1 Depending on connection 2, the output frequency is transmit- ted from output connection 6. Connections 3, 4 and 5 have no function. Connect. 2 Logic Factor Inp. frequency Outp. frequency Connection 1 Connection 2

0 V or open L 75 0…30 kHz 0…400 Hz

24 Vdc H 27 0…10.8 kHz 0…400 Hz 824834 0010 DKPL RS FLIP-FLOP with superior S - input (connection 2) Input connections 3, 4 and 5 must have 0 V or remain open! Connection 1 Logic Connection 2 Logic Connection 6 Logic R-Input S-Input Output

0 V or open L 0 V or open L previous

+24 Vdc H 0 V or open L 0 V L

0 V or open L +24 Vdc H +24 Vdc H

+24 Vdc H +24 Vdc H +24 Vdc H 824834 0008 DKPL Input Output HH H LH L InputInput InputOutput InputInput InputOutput InputInput InputOutput InputInput InputOutput InputInput InputOutput InputNo function Outp.

with combi foot TS 32/TS 35 Technical data Input signal Input resistance Voltage drop, input Cut-off frequeny Switchable input range Switching point settings Hysteresis Output Output level Output current Function Status LED Operating voltage Power consumption Galvanic isolation Voltage strength to mounting rail Operating temperature Storage temperature Overall width Conductor cross-section EMC resistance Burst acc. to EN 61000-4-4 Input/outputs Power supply ESD acc. to EN 61000-4-2 Contact discharge Air discharge Accessories End plate Dimensions see Type Cat. No. DKSC 0-10 V 8019640000 0…10 V 60 kΩ 100 Hz DIL switch for 3 ranges 2 threshold Uth 1 and Uth 2 with 2 front potentiometers each 1 % double switch output per PNP , Ub- 1.2 V 50 mA Uin <Uth1: output 1 active Uin >Uth2: output 2 active no approx. 15 mA no 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Test severity 4, self restoring Test severity 4, self restoring Test severity 4 Test severity 3 Type Cat. No. AP DK5 8268870000 Page 278 Type Cat. No. DKSC 0-20 mA 8031320000 0(4)…20 mA 50 Ω 1 V 100 Hz 2 threshold Uth 1 and Uth 2 with 2 front potentiometers each 1 % double switch output per PNP , Ub- 1.2 V 50 mA Iin <Ith1: output 1 active Iin >Ith2: output 2 active no approx. 15 mA no 4 kVeff 0 °C…+50 °C -25 °C…+60 °C 6 mm 0.5…4 mm 2 Type Cat. No. AP DK5 8268870000 Page 278 Type Cat. No. DKI 2A 8017400000 DKI 2A 8017410000 0.1…2 A 125 mV at 2 A no Fixed:ON >90 mA OFF <50 mA single switch output PNP , Ub-0.1 V 20 mA green LED 18…30 Vdc approx. 10 mA no 4 kVeff -25 °C…+50 °C -40 °C…+85 ° C 6 mm 0.5…4 mm 2 Type Cat. No. AP DKT4 0687560000 Page 278 Threshold Monitoring DKSC 0-20 mA DKI 2A

  • Screw connection
  • Mounts onto on mounting rail
  • Wide spectrum of functions
  • In part, individually adjustable DKSC 0-10 V S1 S2 DIP switch on on 10…100 mV on off 30 mV…1 V off X 300 mV…10 V Block diagram/settings Current sensor

MCZ SC 0…10 Vdc Type Cat. No. MCZ SC 24 V/0…10V 8260280000

24 Vdc ± 20 %

0…10 V 60 kΩ 100 Hz S1 S2 Temperature coefficient Tk 10…100 mV on on 500 ppm max. 0.03…1 V on off 250 ppm max. 0.3…10 V off x 250 ppm max. via 2 potentiometers (12 turns) 1 % of the end value active High for UInput < Uth1 (set via P1) active High for UInput > Uth2 (set via P2) < 250 µs (switch threshold at 90% of the max. input signal; RL ≤ 1 kΩ) 2 channel switching PNP max. 50 mA < 1.2 V at 50 mA none 4 kVeff / 1 min 0 °C…+50 °C -25 °C…+60 °C AWG 22…12 1.5 mm2 CE, UL, CSA 6 mm Page 305 Type Cat. No. MCZ SC 24 V/0…20 mA 8227350000 0.5…20 mA 50 Ω 1 V 40 mA 100 Hz Temperature coefficient Tk 250 ppm max. via 2 potentiometers (12 turns) 1 % of the end value active High for IInput < Ith1 (set via P1) active High for IInput > Ith2 (set via P2) < 250 µs (switch threshold at 90% of the max. input signal; RL ≤ 1 kΩ) 2 channel switching PNP max. 50 mA < 1.2 V at 50 mA none 4 kVeff / 1 min 0 °C…+50 °C -25 °C…+60 °C AWG 22…12 1.5 mm2 CE, UL, CSA 6 mm Page 305 Ordering data for TS 35 Technical data Voltage supply Supply voltage Supply current Input Input voltage Input resistance Voltage drop at full scale Max. input current Cut-off frequeny Transmission behaviour Threshold voltage ranges of Uth Setting of switching threshold Hysteresis of switching threshold Function of output 1 Function of output 2 Response time Output Output current per output Voltage drop at output transistor Insulation coordination/safe separation to EN 50178 Separation input / output Dielectric strength I/O to mounting rail Ambient temperature Storage temperature Conductor Conductor cross-section Approvals Overall width Dimensions and accessories see MCZ SC 0…20 mA The Setpoint Controller allows cost effective units to be built for monitoring analogue signals. An upper and lower limit value, which covers the en- tire signal range, can be set by the user via 2 potentiometers. The respective statuses of the upper and lower limit value are indicated at the 2 digital outputs (upper limit value under/over flow; lower limit value under/over flow).

Type Cat. No. WAS5 CCC LP 8463580000 WAZ5 CCC LP 8463590000 18 V 50 mA < 100 µA approx. 3 V at RL= 0 Ω Iin = 20 mA approx. 13 V at RL= 500 Ω at Iin = 20 mA ≤ 500 Ω < 0.1% of FS < 0.1% from measurement value per 100 Ω load resistance 50 ppm / K of FS 4.5 ms at 500 Ω working resistance < 20 mVeff approx. 170 kHz -25 °C ... +70 °C -40 °C ... +80 °C CE, UL, CSA, GL 300 V 6 kV III ≥ 5.5 mm 4 kVeff / 1 s 4 kVeff / 1 min EN 50178 (safe separation) EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC LP 8444950000 WAZ5 CCC LP 8444960000 18 V 50 mA < 100 µA approx. 3 V at RL= 0 Ω Iin = 20 mA approx. 13 V at RL= 500 Ω at Iin = 20 mA ≤ 500 Ω < 0.1% of FS < 0.1% from measurement value per 100 Ω load resistance 50 ppm / K of FS 4.5 ms at 500 Ω working resistance < 20 mVeff approx. 170 kHz -25 °C ... +70 °C -40 °C ... +80 °C CE, UL, CSA, GL 300 V 6 kV III ≥ 5.5 mm 4 kVeff / 1 s 4 kVeff / 1 min EN 50178 (safe separation) EN 50081, EN 50082, EN 55011 Page 298 + 308 CCC LP (1 channel) CCC LP (2 channel) WAVEANALOG DC/DC z input loop powered z galvanic isolation z 1-, 2-channel versions z low power consumption z safe separation Ordering data Screw connection 1 channel Tension clamp connection 1 channel Screw connection 2 channel Tension clamp connection 2 channel Input/output Technical data* (per channel) Input signal Input voltage max. Input current max Operating current Voltage drop Output signal Load resistance Accuracy at Tu=23 °C Influence of load resistance Temperature coefficient Set time Residual ripple Chopper frequency General Operating temperature Storage temperature Dimensions L / H / W mm Approvals Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Isolation voltage, voltage strength Input/output, channel / channel Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see U = 23 °C single module Coordination of insulation according to EN 50178, 04/98 (safe separation) Approvals:

zvoltage supply on output side z2-way-isolation zanalogue signal conditioning zgalvanic isolation between input/output signal zInput loop powered zcross-connectable voltage supply via cross-connectors Ordering data Screw connection Tension clamp connection Input/output Technical data* Input signal Input voltage max. Input current max Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see U = 23 °C single module Type Cat. No. WAS4 CVC DC 8445040000 WAZ4 CVC DC 8445050000 4 ... 20 mA 7 V 25 mA 0 ... 10 V ≥ 1 kΩ ±0 .2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 20 ms) ≥ 15 Hz (typ. 20 Hz)

24 Vdc ±20%

< 20 mA at Iout = 10 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 CCC DC 8445010000 WAZ4 CCC DC 8445020000 4 ... 20 mA 7 V 25 mA 0 ... 20 mA ≤ 500 Ω ±0 .2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 20 ms) ≥ 15 Hz (typ. 20 Hz) < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 CCC DC 8444980000 WAZ4 CCC DC 8444990000 4 ... 20 mA 7 V 25 mA 4 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 20 ms) ≥ 15 Hz (typ. 20 Hz) < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC-Signal Conditioners Approvals:

Technical data* Input signal Input current max Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption input Power consumption output Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module CCC DC CCC DC CVC DC WAVEANALOG DC/DC zvoltage supply on both sides z2-way-isolation zanalogue signal conditioning zgalvanic isolation between input/output signal zcross-connectable voltage supply via cross-connectorss Type Cat. No. WAS4 CVC DC 8447020000 WAZ4 CVC DC 8447030000 0 ... 20 mA 25 mA 50 Ω 0 ... 10 V ≥ 1 kΩ ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 16 ms) ≥ 15 Hz (typ. 25 Hz) < 11 mA at Iin = 20 mA < 20 mA at Iout = 10 V ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 CCC DC 8446970000 WAZ4 CCC DC 8446990000 0 ... 20 mA 25 mA 50 Ω 4 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 16 ms) ≥ 15 Hz (typ. 25 Hz) < 11 mA at Iin = 20 mA < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 CCC DC 8445070000 WAZ4 CCC DC 8445080000 0 ... 20 mA 25 mA 50 Ω 0 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 16 ms) ≥ 15 Hz (typ. 25 Hz) < 11 mA at Iin = 20 mA < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC-Signal Conditioners Approvals:

Technical data* Input signal Input voltage max. Input resistance Output signal Load resistance Accuracy at Tu=23°C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption input Power consumption output Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module Block diagram WAVEANALOG DC/DC zvoltage supply on both sides z2-way-isolation zanalogue signal conditioning zgalvanic isolation between input/output signal zcross-connectable voltage supply via cross-connectors VCC DC VCC DC VVC DC Type Cat. No. WAS4 VVC DC 8447130000 WAZ4 VVC DC 8447140000 0 ... 10 V 15 V 500 kΩ 0 ... 10 V ≥ 1 kΩ ±0 .2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 25 ms) ≥ 13 Hz (typ. 17 Hz) < 11 mA at Uin = 10 V < 20 mA at Iout = 10 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 VCC DC 8447100000 WAZ4 VCC DC 8447110000 0 ... 10 V 15 V 500 kΩ 4 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 25 ms) ≥ 13 Hz (typ. 17 Hz) < 11 mA at Uin = 10 V < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS4 VCC DC 8447050000 WAZ4 VCC DC 8447080000 0 ... 10 V 15 V 500 kΩ 0 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 30 ms (typ. 25 ms) ≥ 13 Hz (typ. 17 Hz) < 11 mA at Uin = 10 V < 32 mA at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C (mounted) -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners Approvals:

Technical data Input signal Input current max Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see TU = 23 °C single module Block diagram WAVEANALOG DC/DC z3-way-isolation zanalogue signal conditioning zindication LED zcross-connectable voltage supply via cross-connectors CCC CCC CVC Type Cat. No. WAS5 CVC 8540270000 WAZ5 CVC 8540280000 0 ... 20 mA 25 mA ≤ 110 Ω 0 ... 10 V ≥ 1 kΩ 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz

24 Vdc ±25%

< 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC 8540250000 WAZ5 CCC 8540260000 0 ... 20 mA 25 mA ≤ 110 Ω 4 ... 20 mA ≤ 600 Ω 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC 8540180000* WAZ5 CCC 8540190000* 0 ... 20 mA 25 mA ≤ 110 Ω 0 ... 20 mA ≤ 600 Ω 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners NEW Approvals:

Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General* Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module CCC CVC WAVEANALOG DC/DC z3-way-isolation zanalogue signal conditioning zindication LED zcross-connectable voltage supply via cross-connectors Type Cat. No. WAS5 CVC 8540230000 WAZ5 CVC 8540240000 4 ... 20 mA 25 mA ≤ 110 Ω 0 ... 10 V ≥ 1 kΩ 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC 8540200000 WAZ5 CCC 8540210000 4 ... 20 mA 25 mA ≤ 110 Ω 0 ... 20 mA ≤ 600 Ω 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners NEW Approvals:

Technical data* Input signal Input voltage max. Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module Block diagram WAVEANALOG DC/DC z3-way-isolation zanalogue signal conditioning zindication LED zcross-connectable voltage supply via cross-connectors VCC VCC VVC Type Cat. No. WAS5 VVC 8540330000 WAZ5 VVC 8540340000 0 ... 10 V 15 V typ. 100 kΩ 0 ... 10 V ≥ 1 kΩ 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz

24 Vdc ±25%)

< 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 VCC 8540290000 WAZ5 VCC 8540300000 0 ... 10 V 15 V typ. 100 kΩ 4 ... 20 mA ≤ 600 Ω 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 VCC 8540310000 WAZ5 VCC 8540320000 0 ... 10 V 15 V typ. 100 kΩ 0 ... 20 mA ≤ 600 Ω 0.2% ± 250 ppm / K ≤ 45 ms 10 Hz < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C when mounted horizontally -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners NEW Approvals:

Technical data Input signal Input current max Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standardsDimensions and accessories see TU = 23 °C single module CCC HF CCC HF CVC HF WAVEANALOG DC/DC 20 kHz z3-way-isolation ztransmission frequency 20 kHz zanalogue signal conditioning zcross-connectable voltage supply via cross-connectors Block diagram Type Cat. No. WAS5 CVC HF 8447220000 WAZ5 CVC HF 8447230000 0 ... 20 mA 50 mA 50 Ω 0 ... 10 V ≥ 2 kΩ < 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC HF 8447190000 WAZ5 CCC HF 8447200000 0 ... 20 mA 50 mA 50 Ω 4 ... 20 mA ≤ 500 Ω < 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC HF 8447160000* WAZ5 CCC HF 8447170000* 0 ... 20 mA 50 mA 50 Ω 0 ... 20 mA ≤ 500 Ω < 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners Approvals:

ztransmission frequency 20 kHz zanalogue signal conditioning zcross-connectable voltage supply via cross-connectors Ordering data Screw connection Tension clamp connection Input/output Technical data* Input signal Input current max Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module CCC HF CVC HF Block diagram Type Cat. No. WAS5 CVC HF 8447280000 WAZ5 CVC HF 8447290000 4 ... 20 mA 50 mA 50 Ω 0 ... 10 V ≥ 2 kΩ < 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082 EN 55011 Page 298 + 308 Type Cat. No. WAS5 CCC HF 8447250000 WAZ5 CCC HF 8447260000 4 ... 20 mA 50 mA 50 Ω 0 ... 20 mA ≤ 500 Ω < 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 DC/DC Signal Conditioners Approvals:

Technical data* Input signal Input voltage max. Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module VCC HF VCC HF WAVEANALOG DC/DC 20 kHz z3-way-isolation ztransmission frequency 20 kHz zanalogue signal conditioning zcross-connectable voltage supply via cross-connectors Type Cat. No. WAS5 VCC HF 8447340000 WAZ5 VCC HF 8447350000 0 ... 10 V 15 V 500 kΩ 4 ... 20 mA ≤ 500 Ω ±0 .2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082 EN 55011 Page 298 + 308 Type Cat. No. WAS5 VCC HF 8447310000 WAZ5 VCC HF 8447320000 0 ... 10 V 15 V 500 kΩ 0 ... 20 mA ≤ 500 Ω ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.5 W at Iout = 20 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Block diagram DC/DC Signal Conditioners Approvals:

Technical data* Input signal Input voltage max. Input resistance Output signal Load resistance Accuracy at Tu=23 °C Temperature coefficient Response time Cut-off frequeny (-3 dB) General Voltage supply Power consumption Current carrying capacity of cross-connection Operating temperature Storage temperature Dimensions L / H / W mm Approvals Coordination of insulation according to EN 50178, 04/98 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance Coupling capacity Input / output to supply Isolation voltage, voltage strength Input/output to mounting rail Standards/specifications EMC standards Dimensions and accessories see *TU = 23 °C single module Block diagram VVC HF VVC HF WAVEANALOG DC/DC 20 kHz z3-way-isolation ztransmission frequency 20 kHz zanalogue signal conditioning zcross-connectable voltage supply via cross-connectors NEW Type Cat. No. WAS5 VVC HF 8561610000 WAZ5 VVC HF 8587000000 ±10 V / ±10V -10 … + 10 V ± 15 V 500 kΩ -10 … + 10 V ≥ 2 kΩ ±0 .2% of measurement range ≤ 250 ppm / K of measurement range ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, cUL 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Type Cat. No. WAS5 VVC HF 8447370000 WAZ5 VVC HF 8447380000 0 ... 10 V 15 V 500 kΩ 0 ... 10 V ≥ 2 kΩ ± 0.2% of FS ≤ 250 ppm / K of FS ≤ 40 µs (typ. 30 µs) ≥ 15 kHz (typ. 20 kHz) < 1.3 W at Iout = 5 mA ≤ 2 A 0 °C ... +55 °C -20 °C ... +85 °C CE, UL, CSA 300 V 4 kV III ≥ 3 mm 1 nF 4 kVeff / 1 min EN 50178 EN 50081, EN 50082, EN 55011 Page 298 + 308 Approvals: Approvals:

Ordering data Type Cat. No. Screw connection WAS4 PRO DC/DC 8560740000 Tension clamp connection WAZ4 PRO DC/DC 8560750000 Input/output configurable Technical data* Input (adjustable) Voltage uni-/bipolar adjustable 20 mV ... 200 V Voltage calibrated ranges 0 … ±60 mV, 0 … ±100 mV, 0 … ±150 mV, 0 … ±300 mV, Current uni-/bipolar adjustable 0.1 mA ... 100 mA Current calibrated ranges 0 … ±0.3 mA, 0 … ±1 mA, 0 … ±5 mA, 0 … ±16 mA, 0 … 20 mA, 0 … 50 mA Input resistance at current input range < 5 mA / > 5 mA approx. 100 Ω / approx. 5 Ω at voltage input approx. 1 M Ω Input capacity at current input approx. 1 nF Voltage input range < 500 mV / > 500 mV approx. 1 nF / approx. 500 pF Overload capacity at current input range < 5 mA / > 5 mA < 75 mA / < 300 mA Voltage input range < 500 mV / > 500 mV max. < 20 mA / < 3 mA continuous current Output (adjustable) Voltage uni-/bipolar adjustable 0 … 10 V Voltage calibrated ranges 0 … ±10 V, 2 … 10 V, 0 … ±5 V, 1 … 5 V Current uni-/bipolar adjustable 0 … 20 mV Current calibrated ranges 0 … ±20 mA, 4 … 20 mA Offset -100%, -50%, 0%, 50%, 100% of measuring span of the chosen output range Load at output current < 12 V (600 Ω at 20 mA) at output voltage < 10 mA (1 K Ω at 10 V) Offset 20 µA and. 10 mV Residual ripple < 10 mVeff Adjustment zero pot. +25% measuring span of the chosen output range Gain error < 0.1% of FS Temperature coefficient < 60 ppm/K of FS Cut-off frequeny > 10 kHz, < 10 Hz switch General Voltage supply 20 ... 230 V ac/dc +10% Power consumption approx. 1 W Frequency range 48 ... 62 Hz Operating temperature -10 °C ... +70 °C Storage temperature -40 °C ... +85 °C Dimensions L/H/B mm 92.4 / 112.5 / 12.5 Weight approx. 100 g Approvals CE, cUL, GL Coordination of insulation according to EN 50178, 04/98 Rated voltage 600 V Rated surge voltage 5 kV, 1.2/50 us, acc. to IEC 255-4 Overvoltage category III Contamination class 2 Test voltage 4 KV eff input against output against auxiliary power Standards/specifications EN 50178 EMC standards DIN EN 61326, EN 61326/A1, EN 50081-2, EN 61000-6-2 Block diagram PRO DC/DCWAVEANALOG PRO DC/DC zuniversally adjustable via DIP switch zadjustment help via Internet z3-way-isolation zvoltage supply from 20 - 230 V ac/dc zlow power loss zadjustable transmission frequency zindication LED Adjustment help WAVETOOL The service tool enables quick and uncompli- cated configuration of WAVEANALOG PRO. Download from Internet: http://www.weidmueller.de → Products → Downloads (see page 192) Switch position/setting options Switch Input S1 S2 Input range 1234 1234 0 … ±60 mV „ 0 … ±100 mV „„ 0 … ±150 mV „„ 0 … ±500 mV „„ *Offset conversion not calibrated Switch Output S1 S3 Output range 5 6 7 1 2 0 … ±10 V „„ 2 … 10 V „„ „ 0 … ±20 mA „ 4 … 20 mA „„ Offset S1 S2 (in % of output voltage) 89 1 0 5 0 % „ -100 % „„ -50 % „„ +50 % „„ „ +100 % „„ Zero pot. activated: additional ±25 % Switch S3 3 Bandwidth 10 kHz Bandwidth 10 Hz „ Set range can be documented on side of housing. „ = on = off Switch S2 4 calibrated ranges „ DC/DC Signal Conditioners (Configurable) Dimensions and accessories see page 298 + 308 *TU = 23 °C single module NEW Approvals:

Input 0 … 20 mA 4 … 20 mA 0 … 10 V Screw connection 0 … 100 °C 8432210001 8432210011 8432180001 special balancing 8432219999 8432219999 8432189999 Tension clamp connection 0 … 100 °C 8432220001 8432220011 8432190001 special balancing 8432229999 8432229999 8432199999 **You must indicate the temperature range when ordering Please indicate additional output signal of current output Ordering data Type Cat. No. Type Cat. No. Screw connection WTS4 PT100/2 C 8432210000* WTS4 PT100/2 V 8432180000* Tension clamp connection WTZ4 PT100/2 C 8432220000* WTZ4 PT100/2 V 8432190000* Technical data*** Input signal PT100/2-wire PT100/2-wire Supply current 1.45 mA 1.45 mA Conductor resistance Load resistance ≤ 500 Ω≥ 1 kΩ Accuracy at Tu=23 °C ± 0.5% of measurement range ± 0.5% of measurement range Temperature coefficient Measurement range ≥ 200 K ≤ 200 ppm / °C ≤ 200 ppm / °C (typ. 80 ppm / °C) (typ. 80 ppm / °C)

100 K ≤ measurement range < 200 K ≤ 250 ppm / °C ≤ 250 ppm / °C

(typ. 100 ppm / °C) (typ. 100 ppm / °C)

40 K ≤ measurement range < 100 K ≤ 500 ppm / °C ≤ 500 ppm / °C

Voltage supply 24 Vdc ±20% 24 Vdc ±20% Power consumption < 48 mA at I out = 20 mA < 38 mA at I out = 10 mA Current carrying capacity of cross-connection ≤ 2 A ≤ 2 A Standards/specifications EN 50178, IEC 751 EN 50178, IEC 751 EMC standards EN 50081, EN 50082, EN 50081, EN 50082, EN 55011 EN 55011 Approvals CE, UL, CSA CE, UL, CSA Dimensions and accessories see Page 298 + 308 Page 298 + 308 * without balancing *** T U = 23 °C single module Block diagram PT100/2 PT100/2 Aids z Voltage supply 24 Vdc, 50 mA z Simulator for PT 100 or precision-resistance-decade z Ampere-/voltmeter which can be calibrated to an accuracy of >0.1 % of the end value. WAVEANALOG RTD z2-wire technology zconfigurable temperature range zConfigurable output current range zcross-connectable voltage supply via cross-connectors Switch position/setting options Span 4 5 6 40 … 50 °C „„„ 50 … 75 °C „„ 75 … 110 °C „„ 110 … 165 °C „ 165 … 245 °C „„ 245 … 360 °C „ 360 … 540 °C „ 540 … 800 °C 1) only modules with current output Tmin 1 2 3

0 C° „„„

-10 C° „„ -20 C° „„ -40 C° „ -60 C° „„ -80 C° „ -100 C° „ -200 C° Output1) Range 7 0 … 20 mA 4 … 20 mA „ „ = on = off RTD Signal Conditioners Approvals:

Ordering data Type Cat. No. Type Cat. No. Screw connection WTS4 PT100/3 C 8432150000* WTS4 PT100/3 V 8432090000* Tension clamp connection WTZ4 PT100/3 C 8432160000* WTZ4 PT100/3 V 8432130000* Technical data*** Input signal PT100/3-wire PT100/3-wire Supply current 1.45 mA 1.45 mA Conductor resistance ≤ 50 Ω≤ 50 Ω Load resistance ≤ 500 Ω≥ 1 kΩ Accuracy at Tu=23 °C ± 0.5% of measurement range ± 0.5% of measurement range Temperature coefficient Measurement range ≥ 200 K ≤ 200 ppm / °C ≤ 200 ppm / °C (typ. 80 ppm / °C) (typ. 80 ppm / °C) (typ. 100 ppm / °C) (typ. 100 ppm / °C) (typ. 200 ppm / °C) (typ. 200 ppm / °C) General Voltage supply 24 Vdc ±20% 24 Vdc ±20% Power consumption < 48 mA at I out = 20 mA < 38 mA at I out = 10 mA Current carrying capacity of cross-connection ≤ 2 A ≤ 2 A Standards/specifications EN 50178, IEC 751 EN 50178, IEC 751 EMC standards EN 50081, EN 50082, EN 50081, EN 50082, EN 55011 EN 55011 Approvals CE, UL, CSA CE, UL, CSA Dimensions and accessories see Page 298 + 308 Page 298 + 308 * without balancing * T U = 23 °C single module Block diagram PT100/3 PT100/3 Aids z Voltage supply 24 Vdc, 50 mA z Simulator for PT 100 or precision-resistance-decade z Ampere-/voltmeter which can be calibrated to an accuracy of >0.1 % of the end value. Preconfigured modules Output Input 0 … 20 mA 4 … 20 mA 0 … 10 V Screw connection 0 … 100 °C 8432150001 8432150011 8432090001 special balancing 8432159999 8432159999 8432099999 Tension clamp connection 0 … 100 °C 8432160001 8432160011 8432130001 special balancing 8432169999 8432169999 8432139999 You must indicate the temperature range when ordering Please indicate additional output signal of current output WAVEANALOG RTD z3-wire technology zconfigurable temperature range zconfigurable output current range zcross-connectable voltage supply via cross-connectors Switch position/setting options Span 4 5 6 40 … 50 °C „„„ 50 … 75 °C „„ 75 … 110 °C „„ 110 … 165 °C „ 165 … 245 °C „„ 245 … 360 °C „ 360 … 540 °C „ 540 … 800 °C 1) only modules with current output Tmin 1 2 3 -10 C° „„ -20 C° „„ -40 C° „ -60 C° „„ -80 C° „ -100 C° „ -200 C° Output1) Range 7 0 … 20 mA 4 … 20 mA „ „ = on = off RTD Signal Conditioners Approvals:

Ordering data Type Cat. No. Type Cat. No. Screw connection WTS4 PT100/4 C 8432270000* WTS4 PT100/4 V 432240000* Tension clamp connection WTZ4 PT100/4 C 8432280000* WTZ4 PT100/4 V 432250000* Technical data*** Input signal PT100/4-wire PT100/4-wire Supply current 1.45 mA 1.45 mA Conductor resistance ≤ 50 Ω (3- & 4-wire) ≤ 50 Ω (3- & 4-wire) Load resistance ≤ 500 Ω≥ 1 kΩ Accuracy at Tu=23 °C 100 K ≤ measurement range < 600 K ± 0.1% of measurement range ± 0.1% of measurement range Measurement range ≤ 100 K ± 0.1 K ± 0.1 K Measurement range ≥ 600 K ± 0.2% of measurement range ± 0.2% of measurement range Temperature coefficient Measurement range ≥ 200 K ≤ 200 ppm / °C ≤ 200 ppm / °C (typ. 80 ppm / °C) (typ. 80 ppm / °C)

100 K ≤ measurement range < 200 K ≤ 225 ppm / °C ≤ 225 ppm / °C

(typ. 90 ppm / °C) (typ. 90 ppm / °C)

40 K ≤ measurement range < 100 K ≤ 450 ppm / °C ≤ 450 ppm / °C

(typ. 180 ppm / °C) (typ. 180 ppm / °C) General Voltage supply 24 Vdc ±20% 24 Vdc ±20% Power consumption < 48 mA at I out = 20 mA < 38 mA at I out = 10 mA Current carrying capacity of cross-connection ≤ 2 A ≤ 2 A Standards/specifications EN 50178, IEC 751 EN 50178, IEC 751 EMC standards EN 50081, EN 50082, EN 50081, EN 50082, EN 55011 EN 55011 Approvals CE, UL, CSA CE, UL, CSA Dimensions and accessories see Page 298 + 308 Page 298 + 308 * without balancing * T U = 23 °C single module PT100/4 PT100/4 Aids z Voltage supply 24 Vdc, 50 mA z Simulator for PT 100 or precision-resistance-decade z Ampere-/voltmeter which can be calibrated to an accuracy of >0.1 % of the end value. Preconfigured modules Output Input 0 … 20 mA 4 … 20 mA 0 … 10 V Screw connection 0 … 100 °C 8432270001 8432270011 8432240001 special balancing 8432279999 8432249999 Tension clamp connection 0 … 100 °C 8432280001 8432280011 8432250001 special balancing 8432289999 8432259999 Please indicate the temperature range and the sensor type (2-, 3- or 4-wire). Please indicate additional output signal of current output WAVEANALOG RTD z2-, 3- and 4-wire technology zconfigurable temperature range zconfigurable output current range zcross-connectable voltage supply via cross-connectors Switch position/setting options Span 4 5 6 40 … 50 °C „„„ 50 … 75 °C „„ 75 … 110 °C „„ 110 … 165 °C „ 165 … 245 °C „„ 245 … 360 °C „ 360 … 540 °C „ 540 … 800 °C 1) only modules with current output Tmin 1 2 3 -10 C° „„ -20 C° „„ -40 C° „ -60 C° „„ -80 C° „ -100 C° „ -200 C° Output 1) Range 7 0 … 20 mA 4 … 20 mA „ PT 100 891 0 2 - wire „„„ 3 - wire „„ 4 - wire „ „ = on = off RTD Signal Conditioners Approvals:

Ordering data Type Cat. No. Screw connection WAS5 PRO RTD 8560700000 Tension clamp connection WAZ5 PRO RTD 8560710000 Input/output configurable Technical data* Input (adjustable) PT100/2-/3-/4-wire: -200°C to 850°C Ni100 : -60°C to +250°C Potentiometer: min: 0…100 Ω / max:0…100k Ω Resistance: 0 ... 450Ω / Output (adjustable) Output voltage 0...10 V Offset voltage max. 0.05 V Load resistance ≥ 1 kΩ Output current 0/4 ... 20 mA Offset current max. 100 µA Load resistance ≤ 600 Ω Accuracy, slow/fast step response PT 100,Ni 100: 0.3% of measurement range 0.8%, Measurement range < 100 K / 0.3 K / 0.8 K Potentiometer: 0.2% of FS / 0.3% Resistance: 0.2% of FS / 0.3% Step response (switchable via DIP switch) typ. fast slow RTD, R < 1.2 s < 2.2 s Potentiometer < 500 ms < 1.1 s Temperature coefficient measurement range ≥ 200 K ≤ 200 ppm / °C

100 K ≤ measurement range < 200 K ≤ 250 ppm / °C

40 K ≤ measurement range < 100 K ≤ 400 ppm / °C

Max. wire resistance: 50 Ω for 3- and 4-wire Influence of wire resistances: max. + 0.25°C at 50 Ω wire resistance Open circuit recognition: Output signal > 10 V or > 20 mA, LED blinks Range of man. fine adjustment ≥ ± 5%, from ver. 1: ≥12.5%, potentiometer ≥ 12.5 %…25 % Status LED: Module active: LED lit / open circuit: LED blinks Error: LED off General Current carrying capacity of cross-connection ≤ 2 A Operating temperature 0...55°C Storage temperature -20...85°C No manual fine adjustment; slow step response Dimensions L/H/B mm 92.4 / 112.5 / 17.5 Weight approx. 100 g Approvals CE, cUL, GL Coordination of insulation according to DIN EN 50178, 04/98 Rated voltage 300 V Surge voltage 4 kV Overvoltage category III Contamination class 2 Clearance and creepage distance 3 mm Test voltage 2 kV eff Standards/specifications EN 50178, IEC751 EMC standards EN 50081, EN50082, EN55011 Dimensions and accessories see Page 298 + 308 * TU = 23 °C single module PRO RTDWAVEANALOG PRO RTD zmeasurement from PT 100, Ni 100, R, potentiometer zuniverally adjustable via DIP switch z3-way-isolation zstatus LED zlinearization zcross-connectable voltage supply via cross-connectors Selection of input Switch 1Input 123 PT100 2-wire „„„ PT100 3-wire „„ PT100 4-wire. „„ R 2-wire „ NI100 2-wire „„ NI100 3-wire „ NI100 4-wire „ Potentiometer Selection of minimum input values Switch 1/H9277min Rmin Pot.min 4567 0°C 0 Ω 0% „„„„ -10°C 10 Ω 10% „„„ -25°C 20 Ω 25% „„ -40°C 40 Ω 40% „„ -50°C 50 Ω 50% „„ -60°C 60 Ω 60% „ -70°C 70 Ω 70% „„„ -80°C 80 Ω 80% „„ -90°C 90 Ω „„ -100°C 100 Ω „ -150°C 150 Ω „„ -200°C 200 Ω „ Special range „ = on = off Selection of the measurement range Switch 2TR pot. 12345 50K 25 Ω 25% „„„„ 60K 30 Ω 30% „„„ „ 70K 35 Ω 35% „„„ 80K 40 Ω 40% „„ „„ 90K 45 Ω 45% „„ „ 100K 50 Ω 50% „„ „ 110K 55 Ω 55% „„ 130K 65 Ω 65% „„„ 140K 70 Ω 70% „„ 150K 75 Ω 75% „„ „ 160K 80 Ω 80% „„ 170K 85 Ω 85% „„ 180K 90 Ω 90% „ 190K 95 Ω 95% „„„„ 200K 100 Ω 100% „„„ 300K 150 Ω --- „„ 400K 200 Ω --- „„ 450K 225 Ω --- „„ 500K 250 Ω --- „ 550K 275 Ω --- „„„ 600K 300 Ω --- „„ 650K 325 Ω --- „„ 700K 350 Ω --- „ 750K 375 Ω --- „„ 800K 400 Ω --- „ 850K 425 Ω --- „ 900K 450 Ω --- Selection of output Switch 2 Output 6 7 0...10V „ 0...20mA 4...20mA „ Switching on the manual fine adjustment S.1 man. adj.. 8 off on „ Selection of step set time Time of S.2 step response 8 slow „ fast RTD-Signal Isolating Transformer (Configurable) NEW Adjustment help WAVETOOL This service tool enables quick and uncomplicated config- uration of WAVE ANALOG PRO. Download from Internet: http: //www.weidmueller.de → Products → Downloads (see page 192) Approvals:

Ordering data Type Cat. No. Screw connection WTS4 Thermo Select 8432300000 Tension clamp connection WTZ4 Thermo Select 8432310000 Input/output °C / 0 ... 20 mA °C / 4 ... 20 mA °C / 0 ... 10 V Technical data* Input signal Thermocoupler acc. to IEC584 (fully insulated) Types K -200 ... +1372 °C T -200 ... +400 °C R -50 ... +1760 °C S -50 ... +1760 °C B +50 ... +1820 °C Output signal 0 ... 20 mA Load resistance ≤ 500 Ω Output signal 4 ... 20 mA Load resistance ≤ 500 Ω Output signal 0 ... 10 V Load resistance ≥ 1 kΩ Accuracy at Tu = 23 °C T ype K -200°C ...-150°C ± (5K + 0.1% of set range) -150°C ...1200°C ± (3K + 0.1% of set range) 1200°C ...1372°C ± (4K + 0.1% of set range) Type J -200°C ...-150°C ± (4K + 0.1% of set range) -150°C ...1200°C ± (3K + 0.1% of set range) Type T -200°C ...-150°C ± (5K + 0.1% of set range) -150°C ...400°C ± (3K + 0.1% of set range) Type E -200°C ...-150°C ± (4K + 0.1% of set range) -150°C ...1000°C ± (3K + 0.1% of set range) Type N -200°C ...-150°C ± (6K + 0.1% of set range) -150°C ...1300°C ± (3K + 0.1% of set range) Type R -50°C ...200°C ± (10K + 0.1% of set range) 200°C ...1760°C ± (6K + 0.1% of set range) Type S -50°C ...200°C ± (10K + 0.1% of set range) 200°C ...1760°C ± (6K + 0.1% of set range) Type B 50°C ...250°C ± (25K + 0.1% of set range) 250°C ...500°C ± (10K + 0.1% of set range) 500°C ...1820°C ± (6K + 0.1% of set range) Temperature coefficient ± (200 ppm v. Span + 0.075 K) /K Response time without filter 1.1 s Response time with filter 6 s General Power consumption < 38 mA at I out = 20 mA Current carrying capacity of cross-connection ≤ 2 A Open circuit recognition LED blinks (output value: > 20 mA and. > 10 V) Operating temperature 0 °C ... +55 °C Storage temperature -20 °C ... +85 °C Standards/specifications EN 50178, IEC584 EMC standards EN 50081, EN 50082, EN 55011 Dimensions L / H / W mm 92.4 / 112.5 / 12.5 Approvals CE, UL, CSA Dimensions and accessories see Page 298 + 308 * TU = 23 °C single module Thermo Select °C / 0 ... 20 mA, Block diagram WAVEANALOG Thermo zthermocouples K, J, T, E, N, R, S, B configurable ztemperature range zno adjustment necessary zcold junction compensation zconfigurable output signal zcross-connectable voltage supply via cross-connectors Switch position/setting options SW 2SW 1 Type 1 2 3 K „„„ J „„ T „„ E „ N „„ R „ S „ B Span 12345

150 C° „„„„

200 C° „„„ „

250 C° „„„

300 C° „„ „„

350 C° „„ „

400 C° „„ „

450 C° „„

500 C° „„ „ „

550 C° „„ „

600 C° „„„

650 C° „„

700 C° „„ „

750 C° „„

800 C° „„

850 C° „

900 C° „„„„

950 C° „„„

1000 C° „„ „

1050 C° „„

1100 C° „„ „

1150 C° „„

1200 C° „„

1250 C° „

1300 C° „„„

1350 C° „„

1400 C° „„

1450 C° „

1500 C° „„

1600 C° „

1700 C° „

1800 C° „ = on „ = off Output 6 7 0 - 10 V „ 0 - 20 mA 4 - 20 mA „ Filter 8 off on „ SW 1 Tmin 4567

0 C° „„„„

-10 C° „„„ -20 C° „„ „ -30 C° „„ -40 C° „„ „ -50 C° „„ -100 C° „„ -150 C° „ -200 C° „„„ +50 C° „„ +100 C° „„ +150 C° „ +200 C° „„ +250 C° „ +500 C° „ SW 2 Thermo-Signal Conditioners Approvals:

Ordering data Type Cat. No. Screw connection WAS5 PRO Thermo 8560720000 Tension clamp connection WAZ5 PRO Thermo 8560730000 Input/output configurable Technical data* Input (adjustable) Thermocouples acc. to EN 60584-1 Type K, J, E, N, R, S, B via DIP switch selectable Accuracy at Tu = 23 °C T ype K -200°C ...-150°C ± (5K + 0.1% of set range) -150°C ...1200°C ± (3K + 0.1% of set range) 1200°C ...1372°C ± (4K + 0.1% of set range) Type J -200°C ...-150°C ± (4K + 0.1% of set range) -150°C ...1200°C ± (3K + 0.1% of set range) Type T -200°C ...-150°C ± (5K + 0.1% of set range) -150°C ...400°C ± (3K + 0.1% of set range) Type E -200°C ...-150°C ± (4K + 0.1% of set range) -150°C ...1000°C ± (3K + 0.1% of set range) Type N -200°C ...-150°C ± (6K + 0.1% of set range) -150°C ...1300°C ± (3K + 0.1% of set range) Type R -50°C ...200°C ± (10K + 0.1% of set range) 200°C ...1760°C ± (6K + 0.1% of set range) Type S -50°C ...200°C ± (10K + 0.1% of set range) 200°C ...1760°C ± (6K + 0.1% of set range) Type B 50°C ...250°C ± (25K + 0.1% of set range) 250°C ...500°C ± (10K + 0.1% of set range) 500°C ...1820°C ± (6K + 0.1% of set range) Output (adjustable) Output voltage 0...10 V Offset voltage Max. 0.05 V Load resistance ≥ 1 KΩ Output current 0/4 ... 20 mA Offset current max. 100 µA Load resistance ≤ 600 Ω Step response max. 1.4 s at connected filter function max. 7.5 s Max. wire resistance 50 Ω for 3- and 4-wire Open circuit recognition Output signal > 10 V or > 20 mA, LED blinks Range of man. fine adjustment ≥ ±5% Status LED: Module active: LED lights up / open circuit: LED blinks Error: LED off General Current carrying capacity of cross-connection ≤ 2 A Operating temperature 0 °C ... +55 °C Storage temperature -20 ... +85 °C Standards/specifications EN 50178, IEC751 EMC standards EN 50081, EN50082, EN55011 No manual fine adjustment Dimensions L/H/W mm 92.4 / 112.5 / 17.5 Weight 100 g Approvals CE, cUL, GL Dimensions and accessories see Page 298 + 308 * TU = 23 °C single module PRO Thermo Block diagram WAVEANALOG PRO Thermo z3-way-isolation zthermocouples K, J, T, E, N, R, S, B configurable ztemperature range zno adjustment necessary zcold junction compensation zconfigurable output signal zcross-connectable voltage supply via cross-connectors Selection the thermocoupler SW1 Type 1 2 3 K „„„ J „„ T „„ E „ N „„ R „ S „ B Selection of minimum temperature SW1 /H9277min 4567 0°C „„„„ -10°C „„„ -20°C „„ „ -30°C „„ -40°C „„ „ -50°C „„ -100°C „„ -150°C „ -200°C „„„ +50°C „„ +100°C „„ +150°C „ +200°C „„ +250°C „ 500°C „ Special range Selection of temperature span SW2 Span 12345 150°C „„„„ 200°C „„„ „ 250°C „„„ 300°C „„ „„ 350°C „„ „ 400°C „„ „ 450°C „„ 500°C „ „„„ 550°C „„ „ 600°C „„„ 650°C „„ 700°C „„ „ 750°C „„ 800°C „„ 850°C „ 900°C „„„„ 950°C „„„ 1000°C „„ „ 1050°C „„ 1100°C „„ „ 1150°C „„ 1200°C „„ 1250°C „ 1300°C „„„ 1350°C „„ 1400°C „„ 1450°C „ 1500°C „„ 1600°C „ 1700°C „ 1800°C Selection of output SW2 Output 6 7 0...10V „ 0...20mA 4...20mA „ Switching on the manual fine adjustment SW1 man. adjust. 8 off on „ Switching on the filter function SW2 Filter 8 off on „ „ = on = off Coordination of insulation acc. to DIN EN 50178, 04/98 Rated voltage 300 V Surge voltage 4 kV Overvoltage category III Contamination class 2 Clearance & creep. distance 3 mm Test voltage 2 kV eff Adjustment help WAVETOOL This service tool enables quick and uncomplicated config- uration of WAVE ANALOG PRO. Download from the Internet: http: //www.weidmueller.de → Products → Downloads (see page 192) Thermo Signal Isolating Transformers (Configurable) NEW Approvals:

Once the required input and output parameters have been entered, the program determines the correct switch setting and gives instructions for the electrical connection of the module. Where necessary, it also determines and displays the required calibration values. The entire process can be printed out or saved as a PDF file for installation documentation purposes. Download from the Internet: http://www.weidmueller.de ÖProducts ÖDownload WAVETOOL Menu for selecting the functions For configuring the current/voltage isolating transformer Printout of protocol for the documentation For configuring the temperature signal isolating transformer For configuring the thermo signal isolating transformer The adjustment help – WAVETOOL – enables quick and uncomplicated configuration of WAVEANALOG PRO DC, WAVEANALOG PRT RTD, WAVEANALOG PRO THERMO.

Monitoring flows of currents enables a constant control of individual devices and installation components. Discrepancies or disruptions arising in the electrical circuit can easily be eval- uated as breakdowns. Targeted recti- fying procedures can be taken. The WAVECONTROL range of prod- ucts convert sinusoidal/non-sinusoidal AC/DC currents up to 60 A to stan- dard analogue signals. The measure- ment processes are based on 2 basic principles. One principle is alternating currents up to 10 A ac and 50/60 Hz are mea- sured using the transformer process. The module is looped directly into the measurement circuit. A Hall-effect element comes in to operation at 10 A ac/dc. The potential-free wire is inserted through the module, allowing currents up to 60 A ac/dc to be measured. Quite often, there are high-frequency parts of signals on the wire to be measured. In order to be able to take these parts of the signals into consid- eration, so-called TRMS converters (TRUE Root Mean Square) are con- nected to the Hall sensors. This enables measurements up to 2 kHz, independent of the shape of the curve. or a switch output are on offer. Fig.: Monitoring motor currents Monitoring a motor in a cooling system Monitoring a pump in a sewage treatment plant

Less wiring costs thanks to cross- connections Very good marking options Fast commissioning – pluggable replacement PCBs Connection technology – screw or tension clamp via socket block Tool-free mounting Coding elements in the connections – false plugging not possible Galvanically isolated measurement circuit Measurements of direct and alternat- ing currents possible TRMS versions for measuring non sinusoidal signals Measurement range switch without calibration Relay version with selectable hysteresis Selectable working and closed-circuit current process for defined statuses (optional as normally open or normally closed contact) Error indication via LED indication

zcurrent ranges adjustable via DIP switch zcross-connectable voltage supply via cross-connectors zselectable hysteresis zselectable working and closed-circuit current principle Approvals: 196 Current Monitoring WAS2 CMR WAZ2 CMR WAS2 CMR WAZ2 CMR 1/5/10 A ac selectable with relay output 20/40/60A ac selectable with relay output Ordering data Screw connection Tension clamp connection Technical data* Input Input current Input frequency Pass through diameter Measuring principle Connection type Measurement circuit voltage Max. measuring circuit Output Contact set Min. switching voltage Max. switching voltage Continuous current AC Continuous current DC Max. switching current Min. switching current Status LED Threshold Hysteresis Temperature coefficient Response time (10 ... 90%) Working/closed-circuit current principle Coordination of insulation acc. to DIN EN 50178, 04/98 Rated voltage Surge voltage Overvoltage category Contamination class Clearance and creepage distance Test voltage General Supply Supply voltage Power consumption at rated voltage Reverse polarity protection Current carrying capacity of the cross-connection Operating temperature range Storage/transport Factory setting Dimensions L/H/B (mm) Weight Approvals Dimensions and accessories see * TU = 23 °C single module Type Cat. No. Qty. WAS2 CMR 1/5/10A ac 8516560000 1 WAZ2 CMR 1/5/10A ac 8516570000 1 1A ac/5A ac/10A ac selectable (without additional adjustment) 50Hz/60Hz transformer coupled screw or tension clamp connection 250Vac 100A for 1s 1 changeover contact 6Vdc/6Vac 60Vdc/250Vac 0.7A 100mA green LED 10% ... 100% adjustable via front potentiometer approx. 5% or approx. 10% selectable from set threshold ≤ 800 ppm/K typ. 700 ms selectable 300V 4KV lll ≥ 3 mm 4kV eff 8.3 mA (relay not switched) 24 mA (relay switched) yes ≤ 2 A 0 ... 50ºC -20 ... +70ºC Input range: 5A ac; hysteresis 10%, working current principle 92.4/112.4/22.5 150g CE, cUL Page 298 + 308 Type Cat. No. Qty. WAS2 CMR 20/40/60A ac 8513340000 1 WAZ2 CMR 20/40/60A ac 8526600000 1 20A ac/40A ac/60A ac selectable (without additional adjustment) 50Hz/60Hz 8mm Contact-free current monitoring using Hall sensor Push-through connection 400Vac, higher voltages dependent on wire insulation dependent on wire cross-section 1 changeover contact 6Vdc/6Vac 60Vdc/250Vac 0.7A 100mA green LED 10% ... 100% adjustable via front potentiometer approx. 5% or approx. 10% selectable from set threshold ≤ 250 ppm/K typ. 700 ms selectable 300V 4KV lll ≥ 3 mm 4kV eff 23 mA (relay not switched) 47 mA (relay switched) yes ≤ 2 A 0 ... 50ºC -20 ... +70ºC Input range :40A ac; hysteresis 10% working current principle 92.4/112.4/22.5 150g CE, cUL Page 298 + 308 Block diagram

zcross-connectable voltage supply via cross-connectors Approvals: Analogue Signal Processing 197 Current Monitoring Ordering data Screw connection Tension clamp connection Technical data* Input Input current Input frequency Accuracy Measuring principle Connection type Measurement circuit voltage Max. measuring circuit Output Current/voltage selectable Output voltage Offset voltage Load resistance Output signal limit Output current Offset current Load resistance Status LED Temperature coefficient Response time (10 ... 90%) Coordination of insulation acc. to DIN EN 50178, 04/98 (safe separation) Rated voltage Surge voltage Overvoltage category Contamination class Clearance and creepage distance Test voltage General Supply Supply voltage Power consumption at rated voltage Reverse polarity protection Operating temperature range Storage/transport Factory setting Dimensions L/H/W (mm) Weight Approvals Dimensions and accessories see * TU = 23 °C single module Type Cat. No. Qty. WAS1 CMA 1/5/10A ac 8523400000 1 WAZ1 CMA 1/5/10A ac 8523410000 1

1 A ac/5 A ac/10 A ac selectable (without additional adjustment)

50 Hz/60 Hz

0.5% FSR transformer coupled Screw or tension clamp connection

250 Vac

100 A for 1s

0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10 V max. 0.05 V ≥1 K Ω approx. 13 V and 24 mA 0/4 ... 20 mA max.100 µA ≤ 600 Ω green LED ON–> OK; blinks –> signal out of range; OFF –> Error ≤ 200 ppm/K typ. 700 ms 300V 6KV lll ≥ 5.5 mm 4kV eff 40 mA at Iout = 20 mA yes 0 ... 50ºC - 20 ... + 70ºC 72/92.4/22.5 150g CE, cUL Page 298 + 308 Type Cat. No. Qty. WAS1 LP CMA 1/5/10A ac 8528650000 1 WAZ1 LP CMA 1/5/10A ac 8528660000 1 1A ac/5A ac/10A ac selectable (without additional adjustment) 0.5% FSR transformer coupled Screw or tension clamp connection 4 ... 20mA current loop supply approx. 24 mA 4 ... 20 mA max. 100 µA ≤ 550 Ω (at 24 V) RL = (Vcc - 13V) / 20 mA Dependent on voltage Vcc green LED ON–> OK; blinks –> signal out of range; OFF –> Error ≤ 200 ppm/K typ. 700 ms 300V 6KV lll ≥ 5.5 mm 4kV eff 13 Vdc ... 30 Vdc yes 0 ... 50ºC -20 ... +70ºC 72/92.4/22.5 150g CE, cUL Page 298 + 308 Block diagram WAS1 CMA WAZ1 CMA WAS1 LP CMA WAZ1 LP CMA 1/5/10A ac selec- table with analogue output 0…20 mA / 4…20 mA 0…10 V 1/5/10 A ac selectable with analogue output 4…20 mA loop powered

ztrue TRMS value measurements zhall sensor measurement method 198 Current Monitoring Ordering data Screw connection Tension clamp connection Technical data* Input Input current Input frequency Accuracy Measuring principle Connection type Pass through diameter Measurement circuit voltage Max. measuring circuit Output Current/voltage selectable Output voltage Offset voltage Load resistance Output signal limit Output current Offset current Load resistance Status LED Temperature coefficient Response time (10 ... 90%) Coordination of insulation acc. to DIN EN 50178, 04/98 (safe separation) Rated voltage Surge voltage Overvoltage category Contamination class Clearance and creepage distance Test voltage General Supply Supply voltage Power consumption at rated voltage Reverse polarity protection Operating temperature range Storage/transport Factory setting Dimensions L/H/B (mm) Weight Approvals Dimensions and accessories see * TU = 23 °C single module Type Cat. No. Qty. WAS2 CMA 5/10A uc 8526610000 1 WAZ2 CMA 5/10A uc 8526620000 1

5 A uc/10 A uc selectable (without additional adjustment)

0 Hz - 2 kHz (True RMS to DC Converter)

1% (0 Hz - 1 kHz) Crest factor 3 FSR 2% (0 Hz - 2 kHz) Crest factor 5 FSR Contact-free current monitoring using Hall sensor Push-through connection 8 mm

400 Vac, higher voltages dependent on wire insulation

dependent on wire cross-section 0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10 V max. 0.08 V ≥1 KΩ approx. 13 V and. 24 mA 0/4 ... 20 mA max.150 µA ≤ 600 Ω green LED ON–> OK; blinks –> signal out of range; OFF –> Error ≤ 650 ppm/K typ. 700 ms 300 V 6 KV lll ≥ 5.5 mm 4 kV eff 50 mA at Iout = 20 mA yes 0 ... 50 ºC -20 ... +70 ºC 92.4/112.4/22.5 150 g CE, cUL Page 298 + 308 Block diagram Type Cat. No. Qty. WAS2 CMA 20/25/30A uc 8545830000 1 WAZ2 CMA 20/25/30A uc 8545840000 1 20/25/30 A uc selectable (without additional adjustment) 1% (0Hz - 1KHz) Crest factor 3 FSR 2% (0Hz - 2KHz) Crest factor 5 FSR Contact-free current monitoring using Hall sensor Push-through connection 8 mm dependent on wire cross-section 0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10 V max. 0.08 V ≥1 KΩ approx. 13 V and. 24 mA 0/4 ... 20 mA max.150 µA ≤ 600 Ω green LED ON–> OK; blinks –> signal out of range; OFF –> Error ≤ 650 ppm/K typ.700 ms 300 V 6 KV lll ≥ 5.5 mm 4 kV eff 50 mA at Iout = 20 mA yes 0 ... 50 ºC -20 ... +70 ºC 92.4/112.4/22.5 150g CE, cUL Page 298 + 308 WAS2 CMA WAZ2 CMA WAS2 CMA WAZ2 CMA 5/10A ac/dc selectable with analogue output 0 ... 20 mA/ 4 ... 20 mA/ 0 ... 10 V 20/25/30A ac/dc selectable with analogue output 0 ... 20 mA/ 4 ... 20 mA/ 0 ... 10 V Approvals: Input / Output configurable

Technical data* Input Input current Input frequency Accuracy Measuring principle Connection type Pass through diameter Measurement circuit voltage Max. measuring circuit Output Current/voltage selectable Output voltage Offset voltage Load resistance Output signal limit Output current Offset current Load resistance Status LED Temperature coefficient Response time (10 ... 90%) Coordination of insulation acc. to DIN EN 50178, 04/98 (safe separation) Rated voltage Surge voltage Overvoltage category Contamination class Clearance and creepage distance Test voltage General Supply Supply voltage Power consumption at rated voltage Reverse polarity protection Operating temperature range Storage/transport Factory setting Dimensions L/H/W (mm) Weight Approvals Dimensions and accessories see * TU = 23 °C single module Type Cat. No. Qty. WAS2 CMA 40/50/60A uc 8513330000 1 WAZ2 CMA 40/50/60A uc 8526590000 1 40/50/60A uc selectable (without additional adjustment) 1% (0Hz - 1KHz) Crest factor 3 FSR 2% (0Hz - 2KHz) Crest factor 5 FSR Contact-free current monitoring using Hall sensor Push-through connection 8 mm dependent on wire cross-section 0 ... 10 V 0 ... 20 mA 4 ... 20 mA 0 ... 10V max. 0.08 V ≥ 1 kΩ approx. 13 V and. 24 mA 0/4 ... 20 mA max.150 µA ≤ 600 Ω green LED ON–> OK; blinks –> signal out of range; OFF –> Error ≤ 650 ppm/K type 700 ms 300 V 6 KV lll ≥ 5.5 mm 4 kV eff 50 mA at I out = 20 mA yes 0 ... 50ºC -20 ... +70ºC 92.4/112.4/22.5 150 g CE, cUL Page 298 + 308 Block diagram WAS2 CMA WAZ2 CMA 40/50/60A ac/dc selectable with analogue output 0 ... 20 mA/ 4 ... 20 mA/ 0 ... 10 V WAVECONTROL zinput and output range adjustable via DIP switch zno calibration required zcross-connectable voltage supply via cross-connectors ztrue TRMS value measurements zhall sensor measurement method Approvals:

Measurement circuit voltage Max. permissible current in measurement circuit Rated consumption – (W) Rated consumption ~ (VA) Adjustable switching threshold Hysteresis between turn-on and turn-off point Activation time tA Reaction time tR Voltage drop at input Output voltage Max. continuous output current Saturation voltage Auxiliary voltage Auxiliary voltage rated consumption Auxiliary voltage rated data Storage temperature Ambient temperature –, assembled without spacing on TS –, assembled with ≥ 20 mm spacing on TS Coordination of insulation according to VDE, Draft 11/94 Overvoltage category, input Overvoltage category, output Overvoltage category, input 1-input 2, Output 1-output 2, input-output Contamination class Dimensions and connection data see page 306 + 307 Type Cat. No. SMSI 0.05 DC O 1157160000

10 V… 250 Vdc

1 mA…50 mA < 10 ms < 10 ms < 4 V

5 V…50 Vdc

≤ 1.3 V –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. V Type Cat. No. SMSI 0.25 DC O 1156360000 40 mA…250 mA < 3 ms < 3 ms < 3 V

5 V…50 V–

≤ 1.3 V –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. V SMSI DC O With adjustable switching threshold Up to 50 mA Up to 250 mA Block diagram/ timing diagram Current Monitoring This series is particularly suitable for monitoring small currents from 50 mA to 5 A. The adjustable switching threshold activates optionally one relay-or opto-cou- pler output each. Adjustable threshold switching on switching off Hysteresis Relay

  • For AC/DC
  • W ith and without adjustable switching threshold
  • Opto-coupler output

Type Cat. No. SMSI 0.25 AC O 1156460000

10 V…250 Vac

40 mA…250 mA ≤ 5% ≤ 40 ms ≤ 15 ms < 4.3 V~eff (I = 250 mA) ≤ 1.3 V –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. V Type Cat. No. SMSI 2.5 AC O 1157360000 2.8 A 250 mVA 0.2 A…2.2 A ≤ approx. 35% ≤ 55 ms ≤ 20 ms < 100 mV~eff (I = 10 A) ≤ 1.3 V

24 Vuc ±10%

550 mW–/1150 mVA~ 23 mA–/47 mA~ –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. V SMSI AC O With adjustable switching threshold up to 250 mA Up to 2.5 A Type Cat. No. SMSI 5 AC O 1112160000 5…250 Vav

1 A…5 A

≤ 10 ms ≤ 20 ms < 200 mV

24 Vuc ± 10%

< 3.2 V –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. II Type Cat. No. SMSI 5 AC O 8026930000 5…250 Vac ≤ 10 ms ≤ 20 ms < 200 mV 5…48 Vdc 100 mA < 1.6 V –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. II SMSI AC Current monitoring with indicator up to 5 A without switching threshold SMSI AC O Current monitoring units with transistor output up to 5 A without switching threshold Type Cat. No. SMSI 5 AC 1112060000 5…250 Vac < 200 mV –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II I III Fig. II

Measurement circuit voltage Max. permissible current in measurement circuit Rated consumption ~ (VA) Voltage drop at input Adjustable switching threshold Hysteresis between turn-on and turn-off point Activation time tA Reaction time tR Recovery Output voltage Max. continuous output current Auxiliary voltage Rated consumption auxiliary voltage Max. switching current Contact Contact material Storage temperature Ambient temperature –, assembled without spacing on TS –, assembled with ≥ 20 mm spacing on TS Coordination of insulation to DIN VDE 0160,Draft 11/94 Overvoltage category, input, output Overvoltage category, input1-input2, Output1-output 2, input-output Contamination class Dimensions and connection data see page 307 Type Cat. No. SMSI 0.25 DC R 1156660000

10 V…250 Vdc

750 mVA (l = 250 mA) ≤ 3 V (I = 250 mA) 40 mA…250 mA– 2% (250 mA)<lHY<10% (40 mA) ≤ 12 ms 250 V 3 A

24 V~ ±10%

1 NO1)

AgNi, gold-flashed –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II III Fig. V 1) NC on request Type Cat. No. SMSI 0.25 AC R 1159960000 1075 mVA (l = 250 mA) ≤ 3 V (I = 250 mA) 40 mA…250 mA~ ≤ 5% ≤ 25 ms ≤ 15 ms 250 V 3 A AgNi, gold-flashed –25 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II III Fig. V SMSI DC R With adjustable switching threshold up to 250 mA SMSI AC R With adjustable switching threshold up to 250 mA

  • For AC/DC
  • Adjustable switching threshold
  • Relay output

Measurement circuit voltage Max. permissible current in measurement circuit Rated consumption ~ (VA) Voltage drop at input Adjustable switching threshold Hysteresis between turn-on and turn-off point Activation time tA Reaction time tR Recovery Output voltage Max. continuous output current Auxiliary voltage Rated consumption auxiliary voltage Max. switching current Contact Contact material Storage temperature Ambient temperature –, assembled without spacing on TS –, assembled with ≥ 20 mm spacing on TS Coordination of insulation to DIN VDE 0160,Draft 11/94 Overvoltage category, input, output Overvoltage category, input1-input2, Output1-output 2, input-output Contamination class Dimensions and connection data see page 307 Type Cat. No. SMSI 5 AC R 1112260000

1 VA (I = 5 A)

< 1 VA (I = 5 A) 250 V 3 A

24 Vdc ±10%

AgNi, gold-plated 3 µm –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II III Fig. V SMSI AC R Current monitoring with relay output up to 5 A without switching threshold Type Cat. No. SMSI 2.5 AC R 1156960000 250 mVA (I = 2.5 A) 0.2…2.2 A ≤ approx. 5% ≤ 45 ms ≤ 30 ms < 75 ms 250 V 3 A AgNi, gold-plated 3 µm –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C II III Fig. V SMSI AC R With adjustable switching threshold up to 2.5 A

(also Supply voltage) Rated consumption – (W) Rated consumption ~ (VA) Adjustable switch-off threshold Hysteresis/factory setting Switching points Activation time tA Reaction time tR Derating curve a = assembled without spacing on mounting rail b = assembled with ≥ 20 mm spacing on mounting rail Max. output voltage Max. switching current Max. continuous output current Contact Contact material Switching capacity (resistive load) Fuse Storage temperature Ambient temperature –, assembled without spacing on TS –, assembled with ≥ 20 mm spacing on TS Coordination of insulation to DIN VDE 0160,Draft 11/94 Overvoltage category, input, input 1-input 2, output Overvoltage category, input-output, output 1-output 2 Contamination class Dimensions and connection data see page 306 Type Cat. No. SMSU 24 R 1156760000

18 Vdc…27 Vdc or

18 Vac…27 Vac/50 Hz

< 0.8 W < 0.9 VA

18 Vuc…24 Vuc

1%…10%/5% < 4 s < 300 ms 250 V~ 8 A 3 A 1 changeover contact AgNi 0.15 gold-flashed 2000 VA –40 °C…+60 °C –25 °C…+50 °C –25 °C…+60 °C Type Cat. No. SMSU 48 R 1157660000

36 Vdc…53 Vdc or

36 Vac…53 Vac/50 Hz

< 1 W < 1.5 VA

36 Vuc…48 Vuc

1%…10%/5% < 2.5 s < 300 ms 250 V~ 8 A 3 A 1 changeover contact AgNi 0.15 gold-flashed 2000 VA –40 °C…+60 °C –25 °C…+50 °C –25 °C…+60 °C SMSU 24 R SMSU 48 R Block diagram/ timing diagram Continuous current Ambient temperature Adjustable threshold switching on switching off Hysteresis Relay

  • V oltage monitoring from 18 to 299 V
  • One and three phase version
  • Adjustable switching threshold

Type Cat. No. SMSU 110 R 1157760000

83 Vdc…121 Vdc or

83 Vac…121 Vac/50 Hz

< 1.6 W < 1.5 W

83 Vuc…110 Vuc

1%…10%/5% < 4 s < 300 ms 250 V~ 8 A 3 A 1 changeover contact AgNi 0.15 gold-flashed 2000 VA –40 °C…+60 °C –25 °C…+30 °C –25 °C…+55 °C Type Cat. No. SMSU 220 R 1157860000

165 Vac…253 Vac/50 Hz

< 10 VA

165 Vac…220 V ac

1%…15%/5% < 3 s < 2 s 250 V~ 8 A 3 A 1 changeover contact AgNi 0.15 gold-flashed 2000 VA –40 °C…+60 °C –25 °C…+45 °C –25 °C…+60 °C Type Cat. No. SMSU 260 R 1160160000

200 V…299 Vac/50 Hz

< 10 VA

200 V…260 V

1%…15%/5% < 3 s < 2 s 250 V~ 8 A 3 A 1 changeover contact AgNi 0.15 gold-flashed 2000 VA –40 °C…+60 °C –25 °C…+45 °C –25 °C…+60 °C Type Cat. No. SMSU 3x220 R, 2 NO 1156560000 3x220 R,1 NC./1 NO 1178760000

165 V~…230 Vac 50 Hz

9 VA (L3); 60 mVA (L 1/L 2)

150 V~…205 V~

–/7% < 4 s < 80 ms 250 V~ 8 A 3 A

2 NO (115656)

1 NO/1 NC (117876)

AgCdO, gold-flashed 5x107 switching operations 2x105 switching operations 105 switching operations –40 °C…+60 °C –5 °C…+40 °C –5 °C…+55 °C II III Type Cat. No. SMSU 24 DC 0555060000

24 Vdc ± 10%

0.5 W On: 18.5 V, off: 5 V 15 ms 10 ms

24 V– ± 10%

AgNi, gold-flashed 106 switching operations 100 mA –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C Type Cat. No. SMSU 230 AC/DC 0555160000

230 Vdc ±10%

0.9 W 1.1 W On: 140 V–/130 V~, off: 70 V–/80 V~ AgNi, gold-flashed 106 switching operations 100 mA –40 °C…+60 °C –25 °C…+40 °C –25 °C…+50 °C SMSU 110 R SMSU 220 R SMSU 260 R SMSU 1–230 AC/DC Single-phase without adjustable switching threshold SMSU 3x220 R Three-phase with adjustable switching threshold SMSU 1–24 DC Single-phase without switching threshold

Movement and Rotational Speed Monitoring SMS SIZA Rotational speed monitoring Ordering data

Description

Initiator type/initiator voltage Output voltage Continuous current Max. switching capacity (resistive load) Contact Contact material Mechanical service life Time range Coordination of insulation to VDE DIN 0160, draft11/94 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance EMC Accessories and dimensions see page 307 Type Cat. No. SMS/SIZA 1110560000

230 Vdc +5 –15%

AgNi 0.15 gold-flashed > 107 switching operations 0.5…5 s 300 V 4 kV III ≥ 3 mm EN 50 081-1/50 082-2 Fig. VI Block diagram Power supply with delayed turn-off relay output for three-condu- cutor DC initiators (NPN or PNP). The transformer supplies the initiator with 24 V DC. The initiator signal activates the relay, at which time the adjustable turn-off delay becomes effective. This module is particularly suitable for monitoring cyclic movements, e.g, down-times monitoring of conveyor drives, ventilators and pumps or stroke monitoring of valves, die cutters and drilling heads. A contact element actuates the initiator at regular intervals. If these pulses cease, i.e. the proximity switch is continuously actuated (t 4-t6) or deactivated (t1-t3), the relay transmits a signal after the set time has elapsed. During normal operation, the time function bridges the gaps between regular pulses (t 0-t2)

Type Cat. No. EGV Namur 1120360000 approx. 8 Vdc

250 Vac/dc

AgNi 0.15 gold-flashed > 107 switching operations 40 °C mounted 300 V 4 kV III ≥ 3 mm EN 50 081, EN 50 082, EN50 011 Fig. VI Type Cat. No. EGV Inverter 1122460000

24 Vdc ± 10% (closed circuit current < 10 mA)

24 Vdc ± 10% (switching threshold approx. 15 V) 200 mA EN 50 081, EN 50 082, EN50 011 Fig. V Switching amplifier for 2-wire Namur initiators with relay output. Enables the use of economic Namur initiators with short design lengths. This is particularly valid for areas where initiators are subjected to heavy mechanical stresses, and often need to be replaced. A potential-free NO contact is available on the output side for switching larger ratings (2000 VA). The Namur initiator can be directly connected to the module. LED function indicators indicate switching statuses. This module inverts the switching function of electronic outputs. A PNP output is changed into an NPN output with the load con- nected unilaterally against the positive potential (the negative potential is switched through). An NPN output is changed into a PNP output with the load connected unilaterally to the frame potential (the positive potential is switched through). The module reduces the inventory of sensors and electronic switches with PNP/NPN outputs to a single type. Ordering data Initiator type/initiator voltage Output voltage, -current Continuous current Max. switching capacity (resistive load) Contact Contact material Mechanical service life Ambient temperature Coordination of insulation to VDE DIN 0160, draft11/94 Rated voltage Rated surge voltage Overvoltage category Contamination class Clearance and creepage distance EMC Accessories and dimensions see page 307 Block diagram

Set point 1 or set point 2 can be switched to the module’s output as required. The changeover is performed safely separated via the control input E1. The output voltage val- ues (0…10.5 V) can be set using the spindle operated potentiometers SW1 and SW2. The control input E“ determines the polarity safely separated Control input E1: 0 V = set point 1,

24 V = set point 2,

Control input E2: 0 V = positive set point,

24 V = negative set point

Input signal/measurement range Control voltage Max. input current Display Setting Output signal Output Output current Load resistance Slew-Rate Supply voltage UB Residual ripple Reaction time Isolation voltage, voltage strength Input/output/supply Input-Output/TS Storage temperature Operating temperature Insulation coordination according to EN 50 178 Overvoltage category Contamination class Accessories, dimensions and connection data see page 307 electronic changeover switch Type Cat. No. EMA/SW 1172660000 0=0 V, 1=+24 V

24 V±20 %

≤ 7 mA at 24 V each control input: red LED via trimming potentiometer 25 rotations nom. adjustable from –10.5 V…+10.5 V Voltage output selection by E1/E2 max. ±25 mA at Urated=24 V– min. 400 Ω at Urated=24 V

0.168 V/µs

30 mV/106 kHz (at Umax) rising 50 µs decreasing 80 µs 1 kV- 4 kVeff –20 °C…+70 °C 0 °C…+50 °C III Fig. V EMA/SW 24

  • Set point generator
  • switchable –10.5 V/+10.5 V

Type Cat. No. RS/I-D 8 1160561001 0…20 mA 3.5 V 25 mA ≥ 51 Ω 5 kHz at Full-Scale (Sinus)1) 78 µA c1 LSB

8 Bit

≤ 25 mA (as source) approx. 17 V cH, 0 V cL ±1 LSB ≤ 4 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Enable 2) Terminal 10 Hold Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/I-D 8 1168561001 4…20 mA 3.5 V 25 mA ≥ 51 Ω 5 kHz at Full-Scale (Sinus)1) 62.5 µA c 1 LSB ≤ 25 mA (as source) approx. 17 V cH, 0 V cL ±1 LSB ≤ 4 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Enable 2) Terminal 10 Hold Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C RS/I-D 8 8-Bit Analogue/Digital Converters Block diagram Block diagramFunctions table (example) Ordering data Technical data Input signal Max. input voltage Max. input current Input resistance Max. limit frequency Resolution Output signal Output current Output level Prefix Transmission error Conversion time Supply Connection arrangement Storage temperature Operating temperature EMC EN 50 081-1/50 082-2 Type Cat. No. RS/U-D 8 1122361001 –10 V…+10 V ≤ 55 µA ≥ 200 kΩ 5 kHz at Full-Scale (Sinus)1) 78 mV c 1 LSB

8 Bit (1 Bit prefix)

≤ 25 mA (as source) approx. 17 V cH, 0 V cL MSB: H c positive, L c negative ±1 LSB ≤ 4 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Enable 2) Terminal 10 Hold Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/U-D 8 1160361001 0…10 V ≤ 25 µA ≥ 400 kΩ 5 kHz at Full-Scale (Sinus)1) 39 mV c1 LSB ≤ 25 mA (as source) approx. 17 V cH, 0 V cL ±1 LSB ≤ 4 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Enable 2) Terminal 10 Hold Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C 1) 1 LSB-Accuracy 2) Enable: 24 V = tristate

0 V = free conversion

Hold function (H): The converter can, for example, by means of the hold function (H) be matched to the cycle time of a PLC. Holding and release of the conversion. The Hold input (H) is internally connected to 0V via a resistor. In order to store the last signal, the Hold input (H) must be supplied with 24 V. Enable function (E): The Enable circuit (E) allows several converters, e.g. on an input card of a PLC, to be switched on. The Enable input (E) is connected internally to 0 V via a resistor. In order to make the connection to the PLC, one converter must be disconnected. The other converters are supplied with 24 V (at least 12 V). This causes the convert- ers at the output to be highly resistive. Terminal PIN MSB LSB E8 E7 E6 E5 E4 E3 E2 E1 0000000 0 0000000 1 0000001 0 0000001 1 -- - - -- - - 1111110 1 1111111 0 1111111 1 Digital volue/ digital value Analog voltage Analogue voltage 0 V +10 V

Type Cat. No. RS/D 8-I 1165861001 5…24 V (typ., max. 30 V) cH 50 kΩ per input 78 µA c 1 LSB 0…20 mA 0…20 mA (as source) max. 0.08 mA ≤ 500 Ω ±1 LSB ≤ 30 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Hold Terminal 10 0 V Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/D 8-I 1169261001 5…24 V (type., max. 30 V) cH 50 kΩ per input 62.5 µA c1 LSB 4…20 mA 4…20 mA (as source) 4 mA ≤ 500 Ω ±1 LSB ≤ 30 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Hold Terminal 10 0 V Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C RS/D 8-I 8-Bit Digital/Analogue Converters Block diagram Pin assignment Ordering data Technical data Input signal Max. input voltage Max. input current Input resistance Prefix Resolution Output signal Output current Offset Load resistance Transmission error Conversion time Supply Connection arrangement Storage temperature Operating temperature EMC EN 50 081-1/50 082-2 Type Cat. No. RS/D 8-U 1123361001 5…24 V (typ. 24 V) 2.5 mA 50 kΩ per input MSB: H cpositive, L cnegative 78 mV c 1 LSB –10 V…+10 V ≤ 10 mA max. current ≤ 20 mV ≥ 1 kΩ ±1 LSB ≤ 30 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Hold Terminal 10 0 V Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/D 8-U 1160761001 5…24 V (typ. 24 V) 2.5 mA 50 kΩ per input 39 mV c1 LSB 0…10 V ≤ 10 mA ≤ 20 mV ≥ 1 kΩ ±1 LSB ≤ 30 µs (plus output current) Terminal 1 LSB Terminal 8 MSB Terminal 9 Hold Terminal 10 0 V Hold function: High c+24 V cstorage of last converted value Low c0 V cfree conversion –40 °C…+85 °C 0 °C…+50 °C RS/D 8-U … Block diagram Pin assignment

12-Bit Analogue/Digital Converters Block diagram Block diagram Ordering data Technical data Input signal/measurement range Max. input voltage Max. input current Input resistance Prefix Resolution Output signal Output current Output level Load resistance Transmission error Conversion time Temperature coefficient Supply Max. power loss Connection arrangement Storage temperature Operating temperature EMC EN 50 081-1/50 082-2 Type Cat. No. RS/U-D 12 1168261001 –10…+10 V ±15 V 100 kΩ MSB: H cpositive, L cnegative 4.88 mV c1 LSB

12 Bit (1 Bit prefix)

≤ 25 mA (as source)

24 V cH, 0 V cL

±1 LSB ≤ 50 µs

1 LSB *

24 V–, ±20 %

Hold function: High c +24 V c storage of digital signal Low c 0 V c enabling the conversion cycle –40 °C…+80 °C 0 °C…+50 °C Type Cat. No. RS/U-D 12 1168361001 0…10 V 15 V 100 kΩ 2.44 mV c1 LSB

12 Bit

≤ 25 mA (as source) ±1 LSB ≤ 50 µs Hold function: High c+24 V cstorage of digital signal Low c0 V cenabling the con- version cycle –40 °C…+80 °C 0 °C…+50 °C Type Cat. No. RS/I-D 12 1168461001 0…20 mA 30 mA 500 Ω 4.9 µA c1 LSB ≤ 25 mA (as source) ±1 LSB ≤ 50 µs Hold function: High c+24 V cstorage of digital signal Low c0 V cenabling the con- version cycle –40 °C…+80 °C 0 °C…+50 °C Type Cat. No. RS/I-D 12 1169161001 4…20 mA 30 mA 500 Ω 4 µA c1 LSB ≤ 25 mA (as source) ±1 LSB ≤ 50 µs Hold function: High c+24 V cstorage of digital signal Low c0 V cenabling the con- version cycle –40 °C…+80 °C 0 °C…+50 °C … Hold function (H): The converter can, for example, by means of the hold function (H) be matched to the cycle time of a PLC. Holding and release of the conversion. The Hold input (H) is internally connected to 0V via a resistor. In order to store the last signal, the hold input (H) must be supplied with 24 V. Terminal PIN MSB LSB 12 11 10 9 8 7 6 5 4 3 2 1 000000000 0 0 0 000000000 0 0 1 000000000 0 1 0 000000000 0 1 1 -- - - -- - - 111111111 1 0 1 111111111 1 1 0 111111111 1 1 1 Digital volue/ digital Analog value current Analog current 4 mA 20 mA Functions table (example)

12-Bit Digital/Analogue Converters Type Cat. No. RS/D 12-U 1160861001

12 Bit (1 Bit as prefix)

4.2 mA 5.7 kΩ MSB: H cpositive, L cnegative 4.88 mV c1 LSB –10 V…+10 V ≤ 10 mA ≥ 1 kΩ ±1 LSB ≤ 4 µs ±100 ppm from FSR/°C Terminal 1 LSB Terminal 12 MSB Hold function: High c+24 V cstorage of analogue signal Low c0 V cenabling the conversion cycle –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/D 12-U 1166161001 4.2 mA 5.7 kΩ 2.44 mV c1 LSB

0 V…10 V

≤ 10 mA ≥ 1 kΩ ±1 LSB ≤ 4 µs ±100 ppm from FSR/°C Terminal 1 LSB Terminal 12 MSB Hold function: High c+24 V cstorage of analogue signal Low c0 V cenabling the conversion cycle –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/D 12-I 1166061001 4.2 mA 5.7 kΩ 4.9 µA c1 LSB 0…20 mA 0…20 mA (as source) ≤ 500 Ω ±1 LSB ≤ 4 µs ±100 ppm from FSR/°C Terminal 1 LSB Terminal 12 MSB Hold function: High c+24 V cstorage of analogue signal Low c0 V cenabling the conversion cycle –40 °C…+85 °C 0 °C…+50 °C Type Cat. No. RS/D 12-I 1165961001 4.2 mA 5.7 kΩ 4 µA c1 LSB 4…20 mA 4…20 mA (as source) ≤ 500 Ω ±1 LSB ≤ 4 µs ±100 ppm from FSR/°C Terminal 1 LSB Terminal 12 MSB Hold function: High c+24 V cstorage of analogue signal Low c0 V cenabling the conversion cycle –40 °C…+85 °C 0 °C…+50 °C Ordering data Technical data Input signal/measurement range Max. input voltage Input current, Inom Input resistance Prefix Resolution Output signal Output current Output level Load resistance Transmission error Conversion time Temperature coefficient Supply Max. power loss Connection arrangement Storage temperature Operating temperature EMC EN 50 081-1/50 082-2 Block diagram Block diagram