MODEL: 10PR http://www.m-system.co.jp/ 10PR SPECIFICATIONS ES-0860 Rev.9 Page 1/3 High-density Signal Conditioners 10-RACK PULSE SCALER Functions & Features
- Converting pulse rate into convenient engineering unit for display on a totalizing counter or meter Typical Applications
- Positive displacement flowmeters and turbine flowmeters
- Magnetic tachometers MODEL: 10PR–[1][2]0–R[3]
ORDERING INFORMATION
- Code number: 10PR-[1][2]0-R[3] Specify a code from below for each [1] through [3]. (e.g. 10PR-110-R/Q)
- Input frequency range (e.g. 0 – 356.7 Hz)
- Output frequency range (e.g. 0 – 1.00 Hz)
- Specify the specification for option code /Q (e.g. /C01) [1] INPUT 1: Dry contact (max. 100 kHz) 2: Voltage pulse (max. 100 kHz) [2] OUTPUT 1 1: Open collector (max. frequency 20 kHz) 2: 5 V pulse (max. frequency 20 kHz) 3: Relay contact (max. frequency 2 Hz) 4: 24 V pulse (max. frequency 20 Hz) OUTPUT 2 0: None POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating CAUTION 1) This unit's output waveform is not uniform due to its scaling method. 2) Use input relays which do not cause chattering (e.g. mercury relays). Other relays could be used only with a CR filter, for 10 Hz at maximum. 3) Use M-System’s Model M2PRU instead of this unit in conjunction with the pulse output from M-System’s power transducers. Relay R C PULSE SCALER C = 1 µF R = 10k ohms GENERAL SPECIFICATIONS Construction: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided Connection Input: M3.5 screw terminals (torque 0.8 N·m) Output: Card-edge connector and M3.5 screw terminals (torque 0.8 N·m) Power input: Supplied from card-edge connector Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (black) Isolation: Input to output to power Input pulse sensing: Capacitor coupled; detecting pulse rise Sensitivity adjustment: Single-turn screwdriver adjustment (front); 25 mVp-p – 5 Vp-p Scaling factor: 0.9999 × 100 – 0.0001 × 10–6 INPUT SPECIFICATIONS ■ Dry Contact: Mechanical contact or open collector Max. frequency: 100 kHz Pulse width time requirement: 5 μsec. min. (20 msec. min. for frequencies ≤ 10 Hz) Sensing: Approx. 7.5 V DC @ 1 mA
MODEL: 10PR http://www.m-system.co.jp/ 10PR SPECIFICATIONS ES-0860 Rev.9 Page 2/3 ON/OFF level: ≤ 20 kΩ for ON, ≥ 100 kΩ for OFF ■ Voltage Pulse: Square or sine waveforms* Max. frequency: 100 kHz Pulse width time requirement: 5 μsec. min. (20 msec. min. for frequencies ≤ 10 Hz) Input amplitude: 25 mVp-p – 50 Vp-p Minimum amplitude requirement
- With duty ratio 50 % ±10 % (frequency: amplitude) 0 – 2 kHz: 25 mVp-p 0 – 20 kHz: 50 mVp-p 0 – 40 kHz: 1 Vp-p 0 – 100 kHz: 5 Vp-p
- With duty ratio other than 50 % ±10 % (pulse width: amplitude) 5 μsec.: 5 Vp-p 10 μsec.: 3.5 Vp-p 50 μsec.: 2 Vp-p 100 μsec.: 1 Vp-p 500 μsec.: 0.5 Vp-p Input impedance: 100 kΩ minimum 25mV – 50V 25mV – 50V 25mV p-p – 50V p-p 0V *Voltage pulse examples OUTPUT SPECIFICATIONS ■ Open Collector: 50 V DC @ 50 mA (resistive load) Frequency range: 0 – 20 kHz ON pulse width: Approx. 30 μsec. Saturation voltage: 0.6 V DC ■ Relay Contact: 120 V AC @ 200 mA (cos ø = 1)
240 V AC @ 100 mA (cos ø = 1)
24 V DC @ 200 mA (resistive load)
Maximum switching voltage: 240 V AC or 30 V DC Maximum switching power: 24 VA or 4.8 W Minimum load: 5 V DC @ 10 mA Frequency range: 0 – 2 Hz ON pulse width: Approx. 30 msec. Relay life: ≥ 5 × 107 cycles (mechanical) ≥ 105 cycles (electrical) ■ 5 V Pulse Frequency range: 0 – 20 kHz Low pulse width: Approx. 30 μsec. High level: 5 V ±10 % Low level: ≤ 0.5 V Load resistance: 600 Ω minimum ■ 24 V Pulse Frequency range: 0 – 20 Hz High pulse width: Approx. 30 msec. High level: 24 V ±10 % Low level: ≤ 0.5 V Load current: 30 mA max. Load resistance: 800 Ω minimum INSTALLATION Current consumption: Approx. 80 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Standard Rack 10BXx Weight: 200 g (0.44 lb) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 500 V AC @ 1 minute (input to output to power)
1500 V AC @ 1 minute (input or output or power to ground)
MODEL: 10PR http://www.m-system.co.jp/ 10PR SPECIFICATIONS ES-0860 Rev.9 Page 3/3 EXTERNAL VIEW 1 2 5 6 7 8 Sensitivity Adj. EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 130 (5.12) 3 (.12) 51 (2.01) 82 (3.23) 2–4.3 (.17) dia. MTG HOLE TERMINAL COVER 7–M3.5 SCREW 8 (.31) 91 (3.58) 99 (3.90 ) 25 (.98) 1 2 5 6 7 8 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Isolation Pulse Volt. Amplifier Output Driver OUTPUT INPUT 6CONNECTOR SENSITIVITY ADJ. OUTPUT POWER Scaler One-Shot *Dry contact input only. +7.5V Specifications are subject to change without notice.