10JDL MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: 10JDL http://www.m-system.co.jp/ 10JDL SPECIFICATIONS ES-0874 Rev.12 Page 1/3 High-density Signal Conditioners 10-RACK CURRENT LOOP SUPPLY (linearizing; field-programmable) Functions & Features
- Powering a 4 – 20mA DC current loop
- Microprocessor based
- Shortcircuit protection
- Applicable to smart transmitters
- Field-programmable linearization data
- Loop testing via hand-held programmer PU-2x
- Usable as Linearizer for 4 – 20 mA DC signals
- Optional second channel output available at the front terminals and at the Standard Rack connector Typical Applications
- Various 2-wire transmitters
- Providing isolation and linearization for a 2-wire temperature transmitter
- Linearizing weir flowmeter output to provide a linear-to- volume signal MODEL: 10JDL–A[1][2][3]–R[4]
ORDERING INFORMATION
- Code number: 10JDL-A[1][2][3]-R[4] Specify a code from below for each [1] through [4]. (e.g. 10JDL-A1A6-R/Q) Default setting (table next) will be used if not otherwise specified. No linearization data will be programmed if you don't specify type of linearization and required data.
- Linearization data Code 1 segment data: Use Ordering Information Sheet (No. ESU-1669) to specify linearization data. Code 3 T/C, Code 4 RTD: Specify input sensor type and temperature range.
- Specify the specification for option code /Q (e.g. /C01) LINEARIZATION CODE DEFAULT r a e n i La t a d t n e m g e S : 1 2: Square root extraction ––– 3: Thermocouple K 0 – 1000°C 0 0 1 – 00 0 1 t PD T R : 4 °C INPUT Current A: 4 – 20 mA DC (Input resistance 250 Ω) [1] LINEARIZATION 0: None 1: Segment data 2: Square root extraction 3: Thermocouple 4: RTD [2] OUTPUT 1 Current A: 4 – 20 mA DC (Load resistance 600 Ω max.) Voltage 6: 1 – 5 V DC (Load resistance 500 Ω min.) [3] OUTPUT 2 0: None Voltage 6: 1 – 5 V DC (Load resistance 5000 Ω min.) POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
RELATED PRODUCTS
- Programming Unit (model: PU-2x)
- PC configurator software (model: JXCON)
MODEL: 10JDL http://www.m-system.co.jp/ 10JDL SPECIFICATIONS ES-0874 Rev.12 Page 2/3 Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types. GENERAL SPECIFICATIONS Construction: Rack-mounted; terminal access via screw terminals at the front and via card-edge connector at the rear; terminal cover provided Connection Input: M3.5 screw terminals (torque 0.8 N·m) Output: Card-edge connector and M3.5 screw terminals (torque 0.8 N·m) Power input: Supplied from card-edge connector Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (black) Isolation: Input to output 1 to output 2 to power Overrange output: Approx. -10 to +120 % at 1 – 5 V Linearization: 16 points max. represented as percentage of full-scale Adjustments: Programming Unit (model: PU-2x); linearization data, zero and span, simulating output, etc. (Refer to the users manual of JXCON for the adjustments configurable with JXCON.) SUPPLY OUTPUT Output voltage: 24 – 28 V DC with no load Current rating: ≤ 22 mA DC
- Shortcircuit Protection Current limited: 30 mA max. Protected time duration: No limit INPUT SPECIFICATIONS ■ DC Current: Input resistor incorporated OUTPUT SPECIFICATIONS The output goes below 0 % when the input is open. LINEARIZATION
- No linearization: The output is proportional to the input.
- Segment data: 16 points (15 segments) max. within the range of -15.00 to +115.00 % input or output represented as percentage of fullscale
- Square root extraction Low-end cutout: 5 % (output); curve characteristics as in the figure below INPUT OUTPUT ■ Square root extraction
- Thermocouple linearizable range USABLE RANGE T/C °C °F (PR) 0 to 1760 32 to 3200 K (CA) -270 to +1370 -454 to +2498 E (CRC) -270 to +1000 -454 to +1832 J (IC) -210 to +1200 -346 to +2192 T (CC) -270 to +400 -454 to +752 B (RH) 0 to 1820 32 to 3308 R -50 to +1760 -58 to +3200 S -50 to +1760 -58 to +3200 Remark: For the temperatures that range below 0 °C, the transmitter may partially not satisfy the described accuracy. Consult factory.
- RTD linearizable range USABLE RANGE RTD °C °F JPt 100 (JIS ’89) -200 to +500 -328 to +932 Pt 100 (JIS ’89) -200 to +650 -328 to +1202 Pt 100 ( JIS ’97, IEC) -200 to +650 -328 to +1202 Pt 50Ω (JIS ’81) -200 to +500 -328 to +932 Ni 508.4Ω -50 to +200 -58 to +392 Remark: Pt 100 (JIS ’89) is deviated from Pt 100 (JIS ’97) only within the described accuracy. INSTALLATION Current consumption: Approx. 75 mA with voltage output 1 Approx. 100 mA with current output 1 Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Standard Rack 10BXx Weight: 220 g (0.49 lb) PERFORMANCE in percentage of span Accuracy: ±0.1 % with segment gain ≤ 1 [±0.1 % × gain] with segment gain > 1 Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 0.5 sec. (0 – 90 %) Line voltage effect Output signal: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 500 V AC @ 1 minute
MODEL: 10JDL http://www.m-system.co.jp/ 10JDL SPECIFICATIONS ES-0874 Rev.12 Page 3/3 (input to output 1 to output 2 to power)
1500 V AC @ 1 minute (input or output or power to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 130 (5.12) 3 (.12) 51 (2.01) 82 (3.23) 2–4.3 (.17) dia. MTG HOLE TERMINAL COVER 7–M3.5 SCREW 8 (.31) 91 (3.58) 99 (3.90 ) 25 (.98) 1 2 5 6 7 8 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Isolation Output Driver OUTPUT 1 SZ Output Driver OUTPUT 2 6CONNECTOR *1 output type has the output 1 connected to the card-edge connector in parallel. Remark 1) The section enclosed by broken line is only for 2nd output channel. OUTPUT 2* POWER Digital Computation PU-2x MODULAR JACK Current Limiter 250Ω 2-WIRE TRANSMITTER V – (1 – 5V DC) MONITOR SERIAL TRANSMISSION LINE 250Ω No Connection INPUT ■ When Used as Linearizer Specifications are subject to change without notice.