DATASHEET SEARCH SITE | WWW.ALLDATASHEET.COM
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Maximum leakage current each Line to Ground: 3, 6, 10A 20A @ 120 VAC 60 Hz: 2.0 mA 3.5 mA @ 250 VAC 50 Hz: 3.0 mA 5.5 mA Hipot rating (one minute): Line to Ground: 1500 VAC Line to Line: 1450 VDC Rated Voltage (max): Phase to Phase: 440 VAC Phase to Neutral / Ground: 250 VAC Operating Frequency: 50/60 Hz Rated Current: 3 to 20A Operating Ambient Temperature Range (at rated current Ir): -10°C to +40°C In an ambient temperature (Ta) higher than +40°C the maximum operating current (Io) is calculated as follows: Io= Ir(85-Ta)/45 AYO Series A YO Series
- For 3-phase, four wire, WYE applications
- Filters each of the three lines plus neutral
- Good for attenuation beginning at 100kHz
- Space saving design
- Low leakage current
- Easy to connect terminals O rdering Inform ation
10 AYO 1
1 – 0.25 [6.3] spade terminals AYO Series Current Rating 3, 6, 10 or 20A Specifications E lectrical Schem atic N N LINE LOAD A vailable Part Num bers 3AYO1 6AYO1 10AYO1 20AYO1 UL Recognized CSA Certified VDE Approved Compact Low Current 3-phase WYE RFI Filters Three Phase Filters 111 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. Corcom Product Guide Catalog: 1654001 Issue Date: 06.2011 For email, phone or live chat, please go to te.com/help corcom.com
Compact Low Current 3-phase WYE RFI Filters(continued) Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. Corcom Product Guide Catalog: 1654001 Issue Date: 06.2011 For email, phone or live chat, please go to te.com/help corcom.com C ase Dim ensions Part No. A B C D E AYO Series C ase Style A B C D E Typical Insertion Loss Minimum Insertion Loss Common Mode / Asymmetrical (Line to Ground) Differential Mode / Symmetrical (Line to Line) Measured in closed 50 Ohm system Common Mode / Asymmetrical (L-G) Differential Mode / Symmetrical (L-L) Measured in closed 50 Ohm system Perform ance Data 6AYO1 0.1 1 10 30 Frequency in MHz db 100 10AY01 20AYO1 0.1 1 10 30 Frequency in MHz db 100 00.1 1 10 30 Frequency in MHz db 100 3AYO1 0.1 1 10 30 Frequency in MHz db 100