UE10-3OS4D0 SICK | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
A B C D E F H I J K L M N O P Q R S T UE10-3OS4D0 | UE10-3OS SAFETY RELAYS Illustration may differ
Ordering information
Type Part no. UE10-3OS4D0 1028303 Other models and accessories www.sick.com/UE10-3OS Detailed technical data Safety-related parameters Safety integrity level SIL3 (IEC 61508) 1) SILCL3 (EN 62061) 1) Category Category 4 (EN ISO 13849) 1) Performance level PL e (EN ISO 13849) 1) B10d parameter 1.26 x 106 switching cycles (AC-15, 230 V, I = 1.5 A) 5.9 x 106 switching cycles (AC-15, 230 V, I = 0.75 A) 4.35 x 105 switching cycles (DC-13, 24 V, I = 2.5 A) 1 x 107 switching cycles (DC-13, 24 V, I = 0.63 A) PFHD (mean probability of a dangerous fail- ure per hour) 3.0 x 10-8 (EN ISO 13849) TM (mission time) 20 years (EN ISO 13849) 1) If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit. Interfaces Connection type Plug-in spring terminals Number of enable current (N/O) contacts 3, relevant for safety Electrical data Operating data Voltage supply B1-B2/B3-B4 Output circuit > 25 V AC / 60 V DC PELV Output circuit ≤ 25 V AC / 60 V DC PELV or SELV Power consumption 2.4 W (DC) Overvoltage category III (see operating instructions) Rated insulation voltage Ui 300 V AC Rated impulse withstand voltage Uimp 4 kV
2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE10-3OS4D0 | UE10-3OS SAFETY RELAYS Test voltage 2 kV (50 Hz) (EN 60439-1) Input circuits: B1-B2/B3-B4 Input voltage 24 V DC (15 V DC ... 30 V DC) Input current ≤ 500 mA Electrical output circuits: 13/14, 23/24, 33/34, 41/42, Y1/Y2 Response time (≤ 20 ms) 1) Number of enable current (N/O) contacts 3, relevant for safety Number of signalling current (N/C) contacts 1, not safety-relevant Number of contactor monitoring (N/C) con- tacts 1, external device monitoring (EDM) Contact type Positively driven Contact material Silver alloy, gold flashed Switching voltage Enable current contact 10 V AC ... 230 V AC 10 V DC ... 300 V DC Signalling current contact 10 V AC, 10 V DC ... 230 V AC, 300 V DC Contactor monitoring contact 10 V DC ... 24 V DC Current-carrying capacity per OSSD Enable current contact 5 mA ... 6 A Signalling current contact 5 mA ... 6 A Contactor monitoring contact 5 mA ... 100 mA Total current ≤ 12 A Usage category AC-15/DC-13 (EN 60947-5-1) Rated operating current (voltage) 4 A (230 V AC) 360 switching cycles/h
3 A (230 V AC) 3600 switching cycles/h
4 A (24 V DC) 360 switching cycles/h
2.5 A (24 V DC) 3600 switching cycles/h
Mechanical life (relay contacts) 1 x 107 switching cycles Electrical life (relay contacts) 2 x 106 switching cycles 1) K1/K2. Mechanical data Dimensions (W x H x D) 22.5 mm x 114 mm x 96.5 mm Weight 0.2 kg Classifications ECl@ss 5.0 27371990 ECl@ss 5.1.4 27371990 ECl@ss 6.0 27371819 ECl@ss 6.2 27371819 ECl@ss 7.0 27371819 ECl@ss 8.0 27371819 ECl@ss 8.1 27371819 ECl@ss 9.0 27371819 ETIM 5.0 EC001449 2018-09-11 15:13:28 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3
A B C D E F H I J K L M N O P Q R S T UE10-3OS4D0 | UE10-3OS SAFETY RELAYS ETIM 6.0 EC001449 UNSPSC 16.0901 41113704 Dimensional drawing (Dimensions in mm (inch)) Safety relay (4.24) 107.6 (3.07) (2.28) (3.67) 93.3 (3.80) 96.5 (3.69) 93.7 (0.89) 22.5 (2.96) 75.3 (4.49) 114 (0.20) 5.1 (0.58) 14.8 (0.20) 5.1(0.58) 14.8 (4.29) 109 (3.54) 89.8 (2.81) 71.3
4 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE10-3OS4D0 | UE10-3OS SAFETY RELAYS Connection diagram K 1 K 2 B1 B2 14 24 34 B4 B3 B4 CH 2 CH 1 13 23 Y1 Y2 B3B1 41 42 2313 2018-09-11 15:13:28 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 5
SICK AG | Waldkirch | Germany | www.sick.com SICK At A GlAnCe SICK is one of the leading manufacturers of intelligent sensors and sensor solutions for industrial applica- tions. A unique range of products and services creates the perfect basis for controlling processes securely and efficiently, protecting individuals from accidents and preventing damage to the environment. We have extensive experience in a wide range of industries and understand their processes and require- ments. With intelligent sensors, we can deliver exactly what our customers need. In application centers in Europe, Asia and North America, system solutions are tested and optimized in accordance with customer specifications. All this makes us a reliable supplier and development partner. Comprehensive services complete our offering: SICK lifetime Services provide support throughout the ma- chine life cycle and ensure safety and productivity. For us, that is “Sensor Intelligence.” WOrldWIde preSenCe: Contacts and other locations – www.sick.com