Technical content
Function:
- ANSI/IEEE C37.90-1978
- UL file No. E58048
- CSA file No. LR61158 Phase failure relays protect motors, equipment and personnel from damage or injury caused by open phase, reversed phase sequence, or low voltage in a three phase system. Models are available for 50 and 60 Hz with voltages up to 575 volts. Motor control switchboards are a common application. Operation: The contacts of the relay will close only when it senses normal conditions of three phase power at the proper phase sequence. The relay contacts will remain in their normally open position (de-energized) when voltage with incorrect phase sequence is applied, one or more phases are open, or at undervoltage condition. Phase Failure Relays PRODUCT SPECIFICATIONS Sample Part No. 1004X Type: 1001 = 120 V, 60 Hz, 3 phase,L-L 1007 = 208 V, 60 Hz, 3 phase, L-L 1002 = 230 V, 60 Hz, 3 phase,L-L 1012 = 300 V, 60 Hz, 3 phase, L-L 1013 = 350 V, 60 Hz, 3 phase, L-L 1003 = 380 V, 50 Hz, 3 phase, L-L 1004 = 460 V, 60 Hz, 3 phase,L-L 1005 = 525 V, 60 Hz, 3 phase,L-L 1006 = 575 V, 60 Hz, 3 Phase, L-L Mounting: X = Flange Blank - Stud Consult factory for additional models and options PART NUMBER SELECTION Notes: 1. Remove screw for access to the undervoltage adjustment. 2. Clockwise rotation of the adjustment potentiometer will raise the drop-out voltage. PART NUMBER SELECTION WILMAR™ Protective Relays – 1000 Series Part Number Pick-Up to Drop-Out Differential .... Ambient Operating Temperature ....
1000 Series
75% to 100% of nominal, screwdriver adjustable 3% approx. -40 oC to +70oC ± 1% See Curve One set, normally open 10 amp at 28 VDC resistive 10 amp at 230 VAC resistive 11/64" DIA. 4 MTG. HOLES 3.0 3 1/23 7/8 3 13/16 TERMINAL STRIPS #6 - 32 SCREWS Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.