1-717-217-2299 www.lumberg-automationusa.com Bus connection M12 Lion-Link connection M12 Power supply M12 1 = +24 V 2 = +24 V 3 = 0 V 4 = 0 V 5 = Earth LioN-Link BusHead CANopen®-Slave

0940 CSL 601 LioN-Link BusHead IP 67 bus coupler module

for the connection between the higher level fieldbus and the fieldbus independent I/O modules, with M12 bus connection, rotary switches for addressing, M12 LioN-Link connection, M12 power supply connection Diagnostic Indication Pin Assignment LED Indication Condition I/O Line 1, I/O Line 2 red green off wrong configuration /module exchanged online, communication with PLC branch not in use (module not connected) U S1 green sensor/system power supply Line 1 US2 green sensor/system power supply Line 2 MS green green flashing red red flashing red/ green flashing device is ready for operating wrong configuration unrecoverable fault recoverable fault self test is running NS green green flashing red flashing red online, communication with PLC online, no communication with PLC timeout state of one or more I/O connections failed communication device, BUS-OFF status, duplicate MAC-ID 1 = Drain 2 = 24 V 3 = GND (0 V) 4 = CAN_H 5 = CAN_L Housing / = Earth 1 = Drain 2 = 24 V Sensor/System 3 = 0 V Sensor/System 4 = Data + 5 = Data - 1.800.Belden1 | www.lumberg-automationusa.com

www.lumberg-automationusa.com 1-717-217-2299 Be Certain with Belden Be Certain with Belden LioN-Link BusHead CANopen®-Slave

0940 CSL 601

The application of these products in harsh environments should always be checked before use. Specifications subject to alteration. Technical Data Environmental Degree of protection IP 67 Operating temperature range -10°C (+14°F) to +60°C (+140°F) Mechanical Weight 200 g Housing material PBT Bus system C ANopen® GSD/ EDS file 0940CSL601.EDS Transmission rate max. 1 MBaud Address range 1–99 dec Rotary address switches 1–99 dec Default address 63 dec Supply of the fieldbus interface US Rated voltage 24 V DC Voltage range 11–30 V DC Power consumption typ. 10 mA Reverse polarity protection yes Indication LED green System/sensors power supply US1, US2* Rated voltage 24 V DC Voltage range 19–30 V DC Power consumption system: typ. 60 mA / fieldbus: typ. 10 mA Reverse polarity protection yes Indication LED green Output current per branch max. 3 A Included in delivery/accessories Dust covers M12, attachable labels * Both supply points on the BusHead must always be connected. Diagnostic Diagnosis for communication status, module breakdown and periphery faults in the Link system Purpose A maximum of 16 LioN-Link I/O modules can be operated on this BusHead 1.800.Belden1 | www.lumberg-automationusa.com