PKZM0-10 EATON | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 9
Technical content
Motor-protective circuit-breaker, 4 kW, 6.3 - 10 A, Screw terminals Part no. PKZM0-10 Catalog No. 072739 Alternate Catalog No. XTPR010BC1NL EL-Nummer (Norway) 4355130 Delivery program Product range PKZM0 motor protective circuit-breakers up to 32 A Basic function Motor protection Notes Also suitable for motors with efficiency class IE3. Connection technique Screw terminals Contact sequence Max. motor rating AC-3 220 V 230 V 240 V P kW 2.2
380 V 400 V 415 V P kW 4
440 V P kW 4
500 V P kW 4
660 V 690 V P kW 7.5 Rated uninterrupted current Iu A 10 Setting range Overload releases Ir A 6.3 - 10 short-circuit release max. Irm A 155 Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102 Explosion protection (according to ATEX 94/9/EC) PTB 10, ATEX 3013, Ex II(2) GD Observe manual MN03402003Z-DE/EN. Notes Overload trigger: tripping class 10 A Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height. Technical data General Standards IEC/EN 60947, VDE 0660,UL, CSA Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Storage °C - 40 - 80 Open °C -25 - +55 Enclosed °C - 25 - 40 11/03/2022 Eaton 072739 ED2022 V93.0 EN 1 / 9
Direction of incoming supply as required Degree of protection Device IP20 Terminations IP00 Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25 Altitude m Max. 2000 Terminal capacity main cable Screw terminals Solid mm2 1 x (1 - 6) 2 x (1 - 6) Flexible with ferrule to DIN 46228 mm2 1 x (1 - 6) 2 x (1 - 6) Solid or stranded AWG 18 - 10 Stripping length mm 10 Specified tightening torque for terminal screws Main cable Nm 1.7 Control circuit cables Nm 1 Main conducting paths Rated impulse withstand voltage Uimp V AC 6000 Overvoltage category/pollution degree III/3 Rated operational voltage Ue V AC 690 Rated uninterrupted current = rated operational current Iu = Ie A 10 Rated frequency f Hz 50/60 Current heat loss (3 pole at operating temperature) W 6.48 Impedance per pole mΩ 21 Lifespan, mechanical Operations x 106 0.1 Lifespan, electrical (AC-3 at 400 V) Lifespan, electrical Operations x 106 0.1 Max. operating frequency Ops/h 40 Short-circuit rating DC Short-circuit rating kA 60 Notes up to 250 V Motor switching capacity AC-3 (up to 690V) A 10 DC-5 (up to 250V) A 10 (3 contacts in series) Trip blocks Temperature compensation to IEC/EN 60947, VDE 0660 °C - 5 … 40 Operating range °C - 25 … 55 Temperature compensation residual error for T > 40 °C ≦ 0.25 %/K Setting range of overload releases x Iu 0.6 - 1 short-circuit release Basic device, fixed: 15.5 x Iu Short-circuit release tolerance ± 20% Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102 Rating data for approved types Switching capacity Maximum motor rating Three-phase 200 V 208 V HP 3 11/03/2022 Eaton 072739 ED2022 V93.0 EN 2 / 9
HP 7.5 575 V 600 V HP 10 Single-phase 115 V 120 V HP 0.5 230 V 240 V HP 1.5 Short Circuit Current Rating, type E SCCR
240 V kA 65
480 Y / 277 V kA 65
600 Y / 347 V kA 50
Accessories required BK25/3-PKZ0-E Short Circuit Current Rating, group protection SCCR
600 V High Fault
SCCR (fuse) kA 30 max. Fuse A 600 SCCR (CB) kA 30 max. CB A 600 Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In A 10 Heat dissipation per pole, current-dependent Pvid W 2.16 Equipment heat dissipation, current-dependent Pvid W 6.48 Static heat dissipation, non-current-dependent Pvs W 0 Heat dissipation capacity Pdiss W 0 Operating ambient temperature min. °C -25 Operating ambient temperature max. °C 55 IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed. 11/03/2022 Eaton 072739 ED2022 V93.0 EN 3 / 9
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed. Technical data ETIM 8.0 Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074) Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss10.0.1-27-37-04-01 [AGZ529016]) Overload release current setting A 6.3 - 10 Adjustment range undelayed short-circuit release A 155 - 155 With thermal protection No Phase failure sensitive Yes Switch off technique Thermomagnetic Rated operating voltage V 690 - 690 Rated permanent current Iu A 10 Rated operation power at AC-3, 230 V kW 2.2 Rated operation power at AC-3, 400 V kW 4 Type of electrical connection of main circuit Screw connection Type of control element Turn button Device construction Built-in device fixed built-in technique With integrated auxiliary switch No With integrated under voltage release No Number of poles 3 Rated short-circuit breaking capacity lcu at 400 V, AC kA 150 Degree of protection (IP) IP20 Height mm 93 Width mm 45 Depth mm 76 Approvals Product Standards IEC/EN 60947-4-1; UL 60947-4-1; CSA - C22.2 No. 60947-4-1-14; CE marking UL File No. E36332 UL Category Control No. NLRV CSA File No. 165628 CSA Class No. 3211-05 North America Certification UL listed, CSA certified Specially designed for North America No Suitable for Branch circuit: Manual type E if used with terminal, or suitable for group installations 11/03/2022 Eaton 072739 ED2022 V93.0 EN 4 / 9
1: Standard auxiliary contact 2: Trip-indicating auxiliary contact 3: Shunt releases, undervoltage releases Tripping characteristics motor circuit breaker PKZM0-..., PKZM01 1: Minimum level, 3-phase 2: Maximum level, 3-phase 3: Minimum marker, 2-phase 4: Highest marker, 2-phase 11/03/2022 Eaton 072739 ED2022 V93.0 EN 5 / 9
11/03/2022 Eaton 072739 ED2022 V93.0 EN 6 / 9
① 1 half-cycle Let-through energy Dimensions Motor-protective circuit-breaker with standard auxiliary contact PKZM0-…(+NHI-E-…-PKZ0) PKZM0-…-T(+NHI-E-…-PKZ0) PKM0-…(+NHI-E-…-PKZ0) 11/03/2022 Eaton 072739 ED2022 V93.0 EN 7 / 9
Motor-protective circuit-breakers with lockable rotary handles PKZM0-…+AK-PKZ0 Motor-protective circuit-breakers with early-make auxiliary contacts PKZM0-…+VHI-…-PKZ0 Additional product information (links) IL03407011Z (AWA1210-1925) Motor-protective circuit-breaker IL03407011Z (AWA1210-1925) Motor-protective circuit-breaker https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407011Z.pdf 'IL03402034Z (AWA121-1945) Motor-protective circuit-breaker, Starter 'IL03402034Z (AWA121-1945) Motor-protective circuit-breaker, Starter https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL03402034Z2021_06.pdf MN03402003Z (AWB1210-1458) PKZM0 motor-protective circuit-breakers, overload monitoring of Ex e motors MN03402003Z (AWB1210-1458) PKZM0 motor-protective circuit-breakers, overload monitoring of Ex e motors - Deutsch / English https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN03402003Z_DE_EN.pdf Schaltvermögen https://de.ecat.eaton.com/flip-cat/?edition=MOTCONT1_DE#page_3/44 11/03/2022 Eaton 072739 ED2022 V93.0 EN 8 / 9
Motor starters and "Special Purpose Ratings" for the North American market http://www.eaton.eu/ecm/groups/public/@pub/@europe/@electrical/documents/content/pct_3258146.pdf Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf 11/03/2022 Eaton Industries GmbH http://www.eaton.eu © 07/2022 by Eaton Industries GmbH Eaton 072739 ED2022 V93.0 EN