TM221ME16R SCHNEIDER

Document overview

  • PDF pages: 16

Technical content

Page 1

Specifications

Logic controller, Modicon M221, 16

PDF page 1 diagram

IO relay Ethernet

Main

Modicon M221

Range of product

Logic controller

Product or component type

24 V DC

[Us] rated supply voltage

8, discrete input conforming to IEC 61131-2 Type 1

Discrete input number

2 at 0...10 V

Analogue input number

Relay normally open

Discrete output type

8 relay

Discrete output number

5...125 V DC

Discrete output voltage

5...250 V AC

2 A

Discrete output current

Complementary

16

Discrete I/O number

7 for relay output

Maximum number of I/O expansion module

20.4…28.8 V

Supply voltage limits

35 A

Inrush current

Maximum power consumption in 23.3 W at 24 V (with max number of I/O expansion module)

4.3 W at 24 V (without I/O expansion module)

W

0.52 A 5 V for expansion bus

Power supply output current

0.46 A 24 V for expansion bus

Sink or source (positive/negative)

Discrete input logic

24 V

Discrete input voltage

DC

Discrete input voltage type

10 bits

Analogue input resolution

10 mV

LSB value

1 ms per channel + 1 controller cycle time for analogue input analog input

Conversion time

+/- 30 V DC for 5 min (maximum) for analog input

Permitted overload on inputs

+/- 13 V DC (permanent) for analog input

= 15 V for input

Voltage state 1 guaranteed

<= 5 V for input

Voltage state 0 guaranteed

7 mA for discrete input

Discrete input current

PDF page 1 diagram

Page 2

5 mA for fast input

100 kOhm for analog input

Input impedance

3.4 kOhm for input 4.9 kOhm for fast input

35 µs turn-off, I2...I5 terminal(s) for input

Response time

5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input 5 µs turn-on, turn-off, Q0...Q1 terminal(s) for output 50 µs turn-on, turn-off, Q2...Q3 terminal(s) for output 300 µs turn-on, turn-off, other terminals terminal(s) for output

0 ms for input

Configurable filtering time

3 ms for input 12 ms for input

125 V DC

Output voltage limits

277 V AC

7 A

Maximum current per output common

+/- 1 % of full scale for analog input

Absolute accuracy error

100000 cycles AC-12, 120 V, 240 VA, resistive

Electrical durability

100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive

300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)

20 switching operations/minute with maximum load

Switching frequency

20000000 cycles for relay output

Mechanical durability

1 mA at 5 V DC for relay output

Minimum load

Without protection at 5 A

Protection type

1 s

Reset time

256 kB for user application and data RAM with 10000 instructions

Memory capacity

256 kB for internal variables RAM

256 kB built-in flash memory for backup of application and data

Data backed up

2 GB SD card (optional)

Data storage equipment

BR2032 lithium non-rechargeable, battery life: 4 year(s)

Battery type

1 year at 25 °C (by interruption of power supply)

Backup time

0.3 ms for event and periodic task

Execution time for 1

0.7 ms for other instruction

KInstruction

0.2 µs Boolean

Execution time per instruction

60 µs response time

Exct time for event task

1 configurable freewheeling/cyclic master task

Application structure

1 cyclic auxiliary task 8 interrupt tasks

512 %KW constant words

Maximum size of object areas

255 %C counters 8000 %MW memory words 255 %TM timers 512 %M memory bits

With

Realtime clock

<= 30 s/month at 25 °C

Clock drift

Adjustable PID regulator up to 14 simultaneous loops

Regulation loop

Frequency generator

Function available

Page 3

PWM PLS

4 fast input (HSC mode) at 100 kHz 32 bits

Counting input number

Single phase

Counter function

A/B Pulse/direction

USB port with mini B USB 2.0 connector

Integrated connection type

Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector

(serial 1)serial link supply: 5 V, <200 mA

Supply

1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485

Transmission rate

1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB

USB port: USB - SoMachine-Network

Communication port protocol

Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet

10BASE-T/100BASE-TX 1 port with 100 m copper cable

Port Ethernet

DHCP client

Communication service

Modbus TCP slave device Ethernet/IP adapter Modbus TCP client Modbus TCP server

1 LED (green) for PWR

Local signalling

1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status)

terminal block, 3 terminal(s) for connecting the 24 V DC power supply

Electrical connection

connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal removable screw terminal block, 10 terminal(s) for inputs removable screw terminal block, 11 terminal(s) for outputs

Shielded cable: <10 m for fast input

Maximum cable distance

Unshielded cable: <30 m for output

between devices

Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input Shielded cable: <3 m for fast output

Between input and internal logic at 500 V AC

Insulation

Between fast input and internal logic at 500 V AC Non-insulated between inputs Between output and internal logic at 500 V AC Between output groups at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs

CE

Marking

Top hat type TH35-15 rail conforming to IEC 60715

Mounting support

Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit

90 mm

Height

70 mm

Depth

70 mm

Width

0.264 kg

Net weight

Environment

EN/IEC 61010-2-201

Standards

EN/IEC 61131-2 EN/IEC 60664-1

LR

Product certifications

cULus CSA DNV-GL RCM EAC ABS IACS E10

Page 4

Ordinary and hazardous location

Environmental characteristic

8 kV in air conforming to EN/IEC 61000-4-2

Resistance to electrostatic

4 kV on contact conforming to EN/IEC 61000-4-2

discharge

10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3

Resistance to electromagnetic

3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3

fields

1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3

30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8

Resistance to magnetic fields

2 kV (power lines) conforming to EN/IEC 61000-4-4

Resistance to fast transients

2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4

2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5

Surge withstand

2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5

10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6

Resistance to conducted

3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)

disturbances

10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)

Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz

Electromagnetic emission

conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/

IEC 55011

10 ms

Immunity to microbreaks

-10…55 °C (horizontal installation)

Ambient air temperature for

-10…35 °C (vertical installation)

operation

-25…70 °C

Ambient air temperature for storage

10…95 %, without condensation (in operation)

Relative humidity

10…95 %, without condensation (in storage)

IP20 with protective cover in place

IP degree of protection

<= 2

Pollution degree

0...2000 m

Operating altitude

0…3000 m

Storage altitude

3.5 mm at 5…8.4 Hz on symmetrical rail

Vibration resistance

3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting

98 m/s² for 11 ms

Shock resistance

Packing Units

PCE

Unit Type of Package 1

1

Number of Units in Package 1

442 g

Package 1 Weight

10.7 cm

Package 1 Height

12.8 cm

Package 1 width

9.7 cm

Package 1 Length

Page 5

S04

Unit Type of Package 2

24

Number of Units in Package 2

11.398 kg

Package 2 Weight

30 cm

Package 2 Height

40 cm

Package 2 width

60 cm

Package 2 Length

Offer Sustainability

Green Premium product

Sustainable offer status

REACh Regulation

REACh Declaration

Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Directive

EU RoHS Declaration

Yes

Mercury free

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information

The product must be disposed on European Union markets following specific waste collection and

WEEE

never end up in rubbish bins

Yes

PVC free

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is

California proposition 65

known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Page 6

Dimensions Drawings

Dimensions

PDF page 6 diagram

Page 7

Mounting and Clearance

Mounting on a Rail

PDF page 7 diagram

Page 8

Mounting and Clearance

Direct Mounting on a Panel Surface

PDF page 8 diagram

Install a mounting strip (1)

Page 9

Mounting and Clearance

Mounting

Correct Mounting Position

PDF page 9 diagram

Acceptable Mounting Position

Incorrect Mounting Position

PDF page 9 diagram

Page 10

Mounting and Clearance

Clearance

PDF page 10 diagram

Page 11

Connections and Schema

Digital Inputs

PDF page 11 diagram

The COM0 terminals are connected internally. (1) Sink wiring (positive logic). A : Source wiring (negative logic). B :

I0, I1, I6, I7 Ix

Page 12

Connections and Schema

Digital Outputs

PDF page 12 diagram

(∗) Type T fuse The COM1 and COM2 terminals are not connected internally. (1) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to (2) Source wiring (negative logic). A : Sink wiring (positive logic). B :

PDF page 12 diagram

Page 13

Connections and Schema

Analog Inputs

PDF page 13 diagram
PDF page 13 diagram

The (-) poles are connected internally.

Pin Wire Color
AN0 / AN1 Red
0 V Black

Page 14

Connections and Schema

Ethernet Connection

Pin N ° Signal
1 TD+
2 TD-
3 RD+
4 −
5 −
6 RD-
7 −
8 −
PDF page 14 diagram

Page 15

Connections and Schema

USB Mini-B Connection

PDF page 15 diagram

Page 16

Connections and Schema

SL1 Connection

SL1

N ° RS 232 RS 485
1 RxD N.C.
2 TxD N.C.
3 RTS N.C.
4 N.C. D1
5 N.C. D0
6 CTS N.C.
7 N.C.* 5 Vdc
8 Common Common

N.C.: not connected \* : 5 Vdc delivered by the controller. Do not connect.

PDF page 16 diagram