TM221C16R_V01 SCHNEIDER
Document overview
- PDF pages: 17
Technical content
Page 1
Specifications
Modicon M221, Logic controller,

16 inputs/outputs, 7 relay outputs,
100…240 V AC
Main
Modicon M221
Range of product
Logic controller
Product or component type
100...240 V AC
[Us] rated supply voltage
9, discrete input conforming to IEC 61131-2 Type 1
Discrete input number
2 at 0...10 V
Analogue input number
Relay normally open
Discrete output type
7 relay
Discrete output number
5...125 V DC
Discrete output voltage
5...250 V AC
2 A
Discrete output current
Complementary
16
Discrete I/O number
4 for transistor output
Maximum number of I/O
4 for relay output
expansion module
85…264 V
Supply voltage limits
50/60 Hz
Network frequency
40 A
Inrush current
Maximum power consumption in 46 VA at 100...240 V with max number of I/O expansion module
31 VA at 100...240 V without I/O expansion module
VA
0.325 A 5 V for expansion bus
Power supply output current
0.12 A 24 V for expansion bus
Sink or source (positive/negative)
Discrete input logic
24 V
Discrete input voltage
DC
Discrete input voltage type
10 bits
Analogue input resolution
10 mV
LSB value
1 ms per channel + 1 controller cycle time for analogue input analog input
Conversion time
+/- 30 V DC for 5 min (maximum) for analog input
Permitted overload on inputs
+/- 13 V DC (permanent) for analog input
= 15 V for input
Voltage state 1 guaranteed
<= 5 V for input
Voltage state 0 guaranteed

Page 2
7 mA for discrete input
Discrete input current
5 mA for fast input
3.4 kOhm for discrete input
Input impedance
100 kOhm for analog input 4.9 kOhm for fast input
35 µs turn-off, I2...I5 terminal(s) for input
Response time
10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input
0 ms for input
Configurable filtering time
3 ms for input 12 ms for input
125 V DC
Output voltage limits
277 V AC
6 A at COM 1
Maximum current per output
7 A at COM 0
common
+/- 1 % of full scale for analog input
Absolute accuracy error
100000 cycles AC-12, 120 V, 240 VA, resistive
Electrical durability
100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
20 switching operations/minute with maximum load
Switching frequency
20000000 cycles for relay output
Mechanical durability
1 mA at 5 V DC for relay output
Minimum load
Without protection at 5 A
Protection type
1 s
Reset time
256 kB for user application and data RAM with 10000 instructions
Memory capacity
256 kB for internal variables RAM
256 kB built-in flash memory for backup of application and data
Data backed up
2 GB SD card (optional)
Data storage equipment
BR2032 lithium non-rechargeable, battery life: 4 year(s)
Battery type
1 year at 25 °C (by interruption of power supply)
Backup time
0.3 ms for event and periodic task
Execution time for 1 KInstruction
0.2 µs Boolean
Execution time per instruction
60 µs response time
Exct time for event task
512 %KW constant words
Maximum size of object areas
512 %M memory bits 255 %C counters 8000 %MW memory words 255 %TM timers
With
Realtime clock
<= 30 s/month at 25 °C
Clock drift
Adjustable PID regulator up to 14 simultaneous loops
Regulation loop
4 fast input (HSC mode) at 100 kHz 32 bits
Counting input number
Single phase
Counter function
Frequency meter
Page 3
Dual phase (quadrature) Dual phase (pulse/direction)
USB port with mini B USB 2.0 connector
Integrated connection type
Non isolated serial link serial 1 with RJ45 connector and RS485 interface Non isolated serial link serial 2 with RJ45 connector and RS232/RS485 interface
(serial)serial link supply: 5 V, <200 mA
Supply
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB
USB port: USB - SoMachine-Network
Communication port protocol
Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
1 LED (green) for PWR
Local signalling
1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for SL1 1 LED (green) for SL2 1 LED per channel (green) for I/O state
removable screw terminal block for inputs
Electrical connection
removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal
Shielded cable: <10 m for fast input
Maximum cable distance
Unshielded cable: <30 m for output
between devices
Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input
Between input and internal logic at 500 V AC
Insulation
Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC
CE
Marking
24 V DC at 250 mA supplied by the controller
Sensor power supply
Top hat type TH35-15 rail conforming to IEC 60715
Mounting support
Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
90 mm
Height
70 mm
Depth
95 mm
Width
0.346 kg
Net weight
Environment
EN/IEC 60664-1
Standards
EN/IEC 61131-2 EN/IEC 61010-2-201
IACS E10
Product certifications
RCM CSA ABS LR DNV-GL EAC cULus
Ordinary and hazardous location
Environmental characteristic
8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electrostatic
4 kV on contact conforming to EN/IEC 61000-4-2
discharge
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
Resistance to electromagnetic
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
fields
1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Page 4
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to magnetic fields
2 kV (power lines) conforming to EN/IEC 61000-4-4
Resistance to fast transients
2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5
Surge withstand
2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
Resistance to conducted
3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL)
disturbances
10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz
Electromagnetic emission
conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/
IEC 55011
10 ms
Immunity to microbreaks
-10…55 °C (horizontal installation)
Ambient air temperature for
-10…35 °C (vertical installation)
operation
-25…70 °C
Ambient air temperature for storage
10…95 %, without condensation (in operation)
Relative humidity
10…95 %, without condensation (in storage)
IP20 with protective cover in place
IP degree of protection
<= 2
Pollution degree
0...2000 m
Operating altitude
0…3000 m
Storage altitude
3.5 mm at 5…8.4 Hz on symmetrical rail
Vibration resistance
3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting
98 m/s² for 11 ms
Shock resistance
Packing Units
PCE
Unit Type of Package 1
1
Number of Units in Package 1
300.0 g
Package 1 Weight
10.6 cm
Package 1 Height
14 cm
Package 1 width
13.9 cm
Package 1 Length
S04
Unit Type of Package 2
20
Number of Units in Package 2
6.983 kg
Package 2 Weight
30 cm
Package 2 Height
40 cm
Package 2 width
Page 5
60 cm
Package 2 Length
Offer Sustainability
Green Premium product
Sustainable offer status
REACh Regulation
REACh Declaration
Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Directive
EU RoHS Declaration
Yes
Mercury free
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
The product must be disposed on European Union markets following specific waste collection and
WEEE
never end up in rubbish bins
Yes
PVC free
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is
California proposition 65
known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Page 6
Dimensions Drawings
Dimensions

Page 7
Mounting and Clearance
Mounting on a Rail

Page 8
Mounting and Clearance
Direct Mounting on a Panel Surface

Install a mounting strip (1)
Mounting Hole Layout

Page 9
Mounting and Clearance
Mounting
Correct Mounting Position

Acceptable Mounting Position
Incorrect Mounting Position

Page 10
Mounting and Clearance
Clearance

Page 11
Connections and Schema
Digital Inputs
Wiring Diagram (Positive Logic)

Type T fuse (\*)
Wiring Diagram (Negative Logic)

Type T fuse (\*)
Connection of the Fast Inputs
I0, I1, I6, I7
Page 12
Connections and Schema
Relay Outputs
Negative Logic (Sink)

Type T fuse (\*) The COM1 and COM2 terminals are not connected internally. (1) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to (2) Sink wiring (negative logic) B
Positive Logic (Source)

Type T fuse (\*) The COM1 and COM2 terminals are not connected internally. (1) To improve the life time of the contacts, and to protect from potential inductive load damage, you must connect a free wheeling diode in parallel to (2) Source wiring (positive logic) A
Page 13
Connections and Schema
Analog Inputs


The (-) poles are connected internally.
| Pin | Wire Color |
| 0 V | Black |
| AN1 | Red |
| 0 V | Black |
| AN0 | Red |
Page 14
Connections and Schema
USB Mini-B Connection

Page 15
Connections and Schema
SL1 Connection
SL1
| N ° | RS 232 | RS 485 |
| 1 | RxD | N.C. |
| 2 | TxD | N.C. |
| 3 | RTS | N.C. |
| 4 | N.C. | D1 |
| 5 | N.C. | D0 |
| 6 | CTS | N.C. |
| 7 | N.C*. | 5 Vdc |
| 8 | Common | Common |
N.C.: not connected \* : 5 Vdc delivered by the controller. Do not connect.

Page 16
Connections and Schema
SL2 Connection
| N ° | RS 485 |
| 1 | N.C. |
| 2 | N.C. |
| 3 | N.C. |
| 4 | D1 |
| 5 | D0 |
| 6 | N.C. |
| 7 | N.C. |
| 8 | Common |
N.C.: not connected
Page 17
Performance Curves
Derating Curves
Embedded Digital Inputs (No Cartridge)

Ambient temperature X : Input simultaneous ON ratio Y :
Embedded Digital Inputs (with Cartridge)

Ambient temperature X : Input simultaneous ON ratio Y :