TCL TRACOPOWER

Document overview

  • PDF pages: 6

Technical content

Page 1

TCL Series, 24 to 240 Watt

Features

UL 60950 UL 508C UL 60950-1

◆ For industrial, office and residential

applications

PDF page 1 diagram

◆ Ultracompact plastic housing

◆ Connection by spring clamp terminals

or detachable screw terminal block

◆ Reliable snap-on mounting on DIN-rails

◆ Adaptor for wall mounting

◆ Universal input 85–264 VAC, 50/60 Hz

◆ Models with 5, 12, 24 & 48 VDC output

◆ Output voltage adjustable

◆ Power OK signal

◆ Low ripple and noise

◆ Overload and short-circuit protection

The TRACO POWER TCL series is a family of DIN-rail power supplies with an excel­ lent price/performance ratio. With tightly regulated output voltage and high im­

◆ Parallel operation possible

munity against electrical disturbances on the mains they provide a reliable power

◆ Worldwide safety approvals

source for sensitive loads in industrial process controls, machine tools and other

◆ Redundancy module

equipment exposed to a difficult industrial environment. Compact size, light weight, easy snap-on mounting on DIN-rails and the choice of two connection terminal

◆ 3-year product warranty

versions are other features of these power supplies. The TCL series complies with all major safety standards for Europe (EN60950-1, EN50178), North America (UL/cUL 60950, UL 508 listed) or elsewhere in the world (CB-Report).

Models

Order Code Input Voltage Ranges Output Power max. *Output Voltage nom. Output Current max. Connection
TCL 024–105 85 – 264 VAC Universal Input 50/60 Hz 85 – 375 VDC 20 W 5 VDC 4.0 A Detachable screw terminal blocks
TCL 024–112 TCL 024–124 24 W 12 VDC 24 VDC 2.0 A 1.0 A
TCL 060–112 TCL 060–124 TCL 060–148 48 W 12 VDC 4.0 A
60 W 24 VDC 48 VDC 2.5 A 1.25 A
TCL 120–112 TCL 120–124 96 W 12 VDC 8.0 A
120 W 24 VDC 5.0 A
TCL 240–124 85–132/187–264 VAC 240 W 24 VDC 10.0 A
TCL 024–124C 85 – 264 VAC Universal Input 50/60 Hz 85 – 375 VDC 24 W 24 VDC 1.0 A Spring clamp terminals
TCL 060–112C TCL 060–124C TCL 060–148C 48 W 12 VDC 4.0 A
60 W 24 VDC 48 VDC 2.5 A 1.25 A
TCL 120–112C TCL 120–124C 96 W 12 VDC 8.0 A
120 W 24 VDC 5.0 A

\* adjustable

Page 1 of 6

Page 2

Input Specifications

Input voltage range

85–264 VAC/85–375 VDC

TCL 240 model: 85–132/187–264 VAC autoselect (no DC input)

– at operation between 85...93 VAC/85...130 VDC 15% for TCL 060 & TCL 120

Output derating

Input frequency Harmonic limits Input current at full load (typ.) (115 VAC / 230 VAC)

Recommended circuit breaker

Output Specifications

Output voltage adjustable range (potentiometer on frontpanel)

Output regulation (10 to 90% load variation) Ripple and noise (20MHz bandwidth) Electronic short circuit protection

Parallel operation

Overvoltage protection, trigger point

Hold-up time (115 VAC / 230 VAC)

Power OK signal (TCL 60, 120 & 240 models only)

General Specifications

Temperature ranges

– Operating – Storage (non operating)

20% for TCL 024-112 & TCL 024-124 & TCL 240 30% for TCL 024-105 47–63 Hz EN 61000-3-2, Class A

TCL 024 models: 0.35 A / 0.2 A TCL 060 models: 1.2 A / 0.6 A TCL 120 models: 2.0 A / 1.0 A TCL 240 model: 3.3 A / 1.7 A TCL 240 model: 10 A (characteristic C or slow blow fuse) all other models: 5 A (characteristic C or slow blow fuse)

5.1 VDC model: 5.0 – 5.25 VDC 12 VDC models: 12 – 15 VDC (12 - 16 VDC for TCL 024-112) 24 VDC models: 24 – 28 VDC 48 VDC models: 48 – 56 VDC

2.5 % (1 % for TCL 60-112) <50 mV pk-pk current limitation at 120 % typ. (constant current, automatic recovery TCL 24 models: foldback, automatic recovery) output current characteristic suitable for parallel operation of max. 5 units (not for TCL 240-124)

5.1 VDC model: <6.5 VDC 12/24 VDC models: <40 VDC 48 VDC models: <60 VDC

min. 15 ms / min. 125 ms

TCL 240 model: min. 15 ms / min. 40 ms

trigger

output signal

point

(reference to – Vout)

12 VDC models: >11V

11.0 V ±1.0 V / 60 mA max.

24 VDC models: >22V

22.0 V ±2.0 V / 30 mA max.

48 VDC models: >44V

44.0 V ±4.0 V / 15 mA max.

–10°C to +70°C max. –25°C to +85°C

– at 187...264 VAC or 265...375 VDC operation

Temperature derating

1.7 %/K above +50°C

– at 93...132 VAC or 130...187 VDC operation – at 85...130 VDC operation

Humidity (non condensing) Temperature coefficient Switching frequency

Efficiency Isolation voltage

– I/O isolation voltage (60 s)

1.1 %/K above +40°C 1.3 %/K above +30°C 95 % rel. H max. 0.02 %/K 55 – 180 kHz depending on load (frequency modulation) 88 % typ. 3000 VAC

Page 2 of 6

Page 3

General Specifications

TCL 024 models: >2.68 Mio h

Reliability, calculated MTBF at +25°C

TCL 060 models: >2.70 Mio h

(according to IEC-1709)

TCL 120 models: >1.62 Mio h TCL 240 models: >1.38 Mio h

Safety standards

– Information technology equipment

– Industrial control equipment – Electronic equipment for power installation – Electrical equipment for machines – Safety transformers for SMPS – Measurement, Control & Laboratory

Safety approvals

– CB test certificate – UL approval

– UL approval

– CSA certification – Certification documents

Environmental compliance – Reach

– RoHS

Electromagnetic compatibility (EMC), emissions Electromagnetic compatibility (EMC), immunity Safety class Case protection Enclosure material Mounting

Installation instructions

IEC 60950-1, EN 60950-1 (output SELV), UL Std. 60950-1 (2nd Edition) +Am1:2011, CAN/CSA-C22.2 No. 60950-1-07 +Am1:2011 UL 508 EN 50178 EN 60204 EN 61558-2-16 IEC 61010-1, EN 61010-1 IEC 61010-2-201, EN 61010-2-201 IEC 60950-1 UL 508 listed, CSA C22.2 No. 14 File e210002 www.ul.com -> certifications UL 60950, File e181381 (except TCL 240) www.ul.com -> certifications UL 60950-1, CSA 60950-1-03 www.tracopower.com/overview/tcl www.tracopower.com/info/reach-declaration.pdf RoHS directive 2011/65/EU EN 61000-6-3 EN 61000-6-2 degree of protection class 1 IP 20 (IEC 60529) plastic 94V-0 rated DIN-rails as per EN 50022-35x15/7.5 (snap-on with self-locking spring) Adapter for wall-/chassis mounting (included)

www.tracopower.com/overview/tcl

All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.

Page 3 of 6

Page 4

TCL–REM240 Redundancy Module

PDF page 4 diagram

This module enables redundant operation of any two TCL models by decoupling the 2 power supplies. It can also be used to separate sensitive loads from the main power source.

Order Code Nominal Input Voltage Input Voltage Range Max Power per Input Output Voltage Output Current max.
TCL–REM240 5...48 VDC 5...60 VDC 200 W Vin – 0.9 VDC 8 A

Specifications

Operating temperature

Electromagnetic compatibility

Dimensions

Connection Installation instructions

Case Dimensions

TCL 024 and TCL-REM240 models

PDF page 4 diagram

DC-ON LED Output voltage adjust

–10°C to +70°C max. (14°F ... +158°F) derating above +40°C (104°F): 1.5 %/K in correspondence to connected units (no internal switching device) same as model TCL 024 (see page 4)

detachable screw terminal block www.tracopower.com/overview/tcl

Dimensions in [mm], ( ) = Inch Tolerances: ±0.5 mm (±0.02)

Page 4 of 6

Page 5

Case Dimensions

TCL 60 models

PDF page 5 diagram

DC-ON LED

adjust

Input 1 AC Ground 2 Neutral 3 Live

Weight: 265 g (9.4 oz)

TCL 120 models

PDF page 5 diagram

Input 1 AC Ground 2 Neutral 3 Live

Weight: 440 g (15.5 oz)

Dimensions in [mm], ( ) = Inch Tolerances: ±0.5 mm (±0.02)

Page 5 of 6

Page 6

Case Dimensions

TCL 240 model

PDF page 6 diagram
PDF page 6 diagram

Wall Mounting Bracket Instead on a DIN-rail, the modules can be also mounted on a chassis or wall with help of a mounting bracket which is supplied as standard with each power supply

Dimensions in [mm], ( ) = Inch Tolerances: ±0.5 mm (±0.02)

Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com

Rev. September 20, 2021 Page 6 of 6