DATASHEET SEARCH SITE
Document overview
- PDF pages: 8
Technical content
Page 1

Series T
Differential Pressure Transmitters
The Series T family of differential pressure transmitters measure low pressures and feature low power consumption and a variety of analog signal outputs. A wide selection of standard pressure ranges and electrical ratings is available.
These transmitters feature: no moving parts to wear out, reliable long term stability, and are virtually position insensitive.
The Series T transmitters are an excellent choice for many HVAC, process and automation monitoring requirements. These transmitters monitor: filter differential pressures, fan static pressures, clean room pressures, variable air volume systems and velocity pressures. They have been used for bubbler level systems, leak detection and in medical and analytical instruments.
Amphenol
Advanced Sensors
The transmitters are housed in a flame retardant, glass-reinforced polyphenylene oxide (NORYL™) case. Electrical connections are made by means of a 3/8 in terminal strip with #6 screws.
The Series T includes four models: Model T10, Model T20, Model T30 and Model T40. These four models incorporate a variety of power and signal options.
The span or zero adjustment is performed with a 20-turn potentiometer for fine resolution.
Page 2
T10
Three-wire
DC Voltage In
DC Voltage Out
T20
Four-wire
24, 120, or 240 VAC In
DC Voltage Out
T30
Two-wire
DC Voltage In
4 to 20 mA Out
T40
Four-wire
24, 120, 240 VAC In
4 to 20 mA Out
The piezoresistive sensor is a solid state device designed in a Wheatstone bridge configuration. When pressure is applied to the device, the resistance of the bridge changes by a small amount. This resistance
change is converted to a voltage and amplified.
Page 3
Series T Specifications
General
- Measures differential, gage pressure, or vacuum
- Suitable for air or inert gases
- Maximum safe momentary overpressure: see reference table A
Performance
Accuracy ± 1% of span (including non-linearity and hysteresis)
Calibration (Traceable to NIST)
Environmental
Operating Temperature Range 32°F to 115°F (0°C to 45°C)
Storage Temperature -20°F to 160°F (-30°C to 70°C)
Effect of Temperature
- on zero: ±0.05%/°C
- on span: ±0.02%/°C
Operating Humidity Range 10% to 90% RH non-condensing
Shock Resistance 10 G (11 ms)
Vibration Resistance 5 G to 50 Hz
Electrical Connections
Connections External 3/8 in terminal strip with #6 screws
Physical
Pressure Port Connections 3/16 in diameter suitable for:
- 1/8 in ID Tygon™ or polyurethane tubing 0.11 in to 0.15 in (3 mm to 4 mm)
- 1/4 in OD polyethylene tubing (6 mm) Integral filters at both ports
Dimensions (W x L x H) 3.00 in x 5.15 in x 1.40 in (76 mm x 131 mm x 36 mm)
Material Flame retardant, glass-reinforced polyphenylene oxide (NORYL) case
Weight 0.42 lbs (190 g) maximum
Page 4

Model T10 Specifications
DC Power Input/Voltage Output Diagram shows area of detail. Please see inset diagrams for wiring.
Electrical
Supply Voltage 11 to 32 VDC (14.5 to 32 VDC for 10 Volts output) Protected against reversal of polarity
Supply Current 10 mA
Output
- 0 to 5 Volts, linear
- 0 to 10 Volts, linear
- Sink or source 3.5 mA
- Protected against short circuit
Ordering Information
Order Number (See Table below and Reference Table A on page 8) T10 - PPP - V - O Example: T10 - 01E - 5 - A
PPP = Pressure Range V = Voltage Output O = Offset
(See Note)
See Reference Table A 5 = 0 to 5 Volts
0 = No offset
X = 0 to 10 Volts
A = 1/4 offset B = 1/2 offset
If the measured differential pressure is expected to go from positive to negative, a transmitter with offset (elevated zero) should be ordered.
Three options are available: “0” No offset. At zero differential pressure the output signal is: 0 V (0 to 5 V range) 0 V (0 to 10 V range) Pressure excursion: 0% to 100% of Range, see Table A
“A” 1/4 span offset. At zero differential pressure the output signal is: 1.25 V (0 to 5 V range) 2.5 V (0 to 10 V range) Pressure excursion: -33% to 100% of Range, see Table A “B” 1/2 span offset. At zero differential pressure the output signal is: 2.5 V (0 to 5 V range) 5 V (0 to 10 V range) Pressure excursion: -100% to 100% of Range see Table A
To order: determine the positive pressure range; from Table A find the corresponding pressure code, then add the required offset (none, A, or B). For example, T30 05E A is a transmitter with a maximum range of 1 in (25.40 mm) of H2O at 20 mA and a minimum range of -0.33 in of H2O at 4 mA.
Page 5
Model T20 Specifications
AC Power Input/Voltage Output
Electrical
Transformer isolation between power supply and output is 2500 Vrms
Output Voltage
- 0 to 5 Volts
- 0 to 10 Volts
- Sink or source 3.5 mA
- Protected against short circuit
Ordering Information
Order Number (See Table below and Reference Table A on page 8) T20 - PPP - S - V - O Example: T20 - 07P - C - X - B
PPP = Pressure Range S = Supply Voltage V = Voltage Output O = Offset
(See Note)
See Table Reference A C = 24 VAC 5 = 0 to 5 Volts 0 = No offset
D = 120 VAC X = 0 to 10 Volts A = 1/4 offset E = 240 VAC
B = 1/2 offset
If the measured differential pressure is expected to go from positive to negative, a transmitter with offset (elevated zero) should be ordered.

Three options are available: “0” No offset. At zero differential pressure the output signal is: 0 V (0 to 5 V range) 0 V (0 to 10 V range) Pressure excursion: 0% to 100% of Range, see Table A “A” 1/4 span offset. At zero differential pressure the output signal is: 1.25 V (0 to 5 V range) 2.5 V (0 to 10 V range) Pressure excursion: -33% to 100% of Range, see Table A “B” 1/2 span offset. At zero differential pressure the output signal is: 2.5 V (0 to 5 V range) 5 V (0 to 10 V range) Pressure excursion: -100% to 100% of Range see Table A
To order: determine the positive pressure range; from Table A find the corresponding pressure code, then add the required offset (none, A, or B).
For example, T30 05E A is a transmitter with a maximum range of 1 in (25.40 mm) of H2O at 20 mA and a minimum range of -0.33 in of H2O at 4 mA.
Page 6

Model T30 Specifications
Two Wire / 4 to 20 mA Output
Electrical
- Supply Voltage: 11 to 32 VDC (See diagram right for maximum loop resistance)
- Protected against reversal of polarity
- Output limited to approx. 3.85 mA at low end of span and approx. 25 mA at upper end of span
Ordering Information
Order Number (See Table below and Reference Table A

on page 8) T30 - PPP - O Example: T30 - 06E - B
PPP = Pressure Range O = Offset
(See Note)
See Reference Table A 0 = No offset
A = 1/4 offset B = 1/2 offset
If the measured differential pressure is expected to go from positive to negative, a transmitter with offset (elevated zero) should be ordered.
Three options are available: “0” No offset. At zero differential pressure the output signal is: 4 mA (4 to 20 mA range) Pressure excursion: 0% to 100% of Range, see Table A
“A” 1/4 span offset. At zero differential pressure the output signal is: 8 mA (4 to 20 mA range) Pressure excursion: -33% to 100% of Range, see Table A “B” 1/2 span offset. At zero differential pressure the output signal is: 12 mA (4 to 20 mA range) Pressure excursion: -100% to 100% of Range see Table A
To order: determine the positive pressure range; from Table A find the corresponding pressure code, then add the required offset (none, A, or B).
For example, T30 05E A is a transmitter with a maximum range of 1 in (25.40 mm) of H2O at 20 mA and a minimum range of -0.33 in of H2O at 4 mA.
Page 7
Model T40 Specifications
AC Power Input / 4 to 20 mA Output
Electrical
| Nominal Input Voltage | Power Consumption | Operating Voltage Range |
|---|---|---|
| 24 VAC, 50/60Hz | 1.5 W | 20 to 30 VAC |
| 120 VAC, 50/60Hz | 1.5 W | 100 to 140 VAC |
| 240 VAC, 50/60Hz | 1.5 W | 200 to 260 VAC |
- Transformer isolation between power supply and output is 2500 Vrms
- Receiver resistance can be from 0 to 600 W
- Output limited to approx. 27 mA at the upper end of span
Ordering Information
Order Number (See Table below and Reference Table A on page 8) T40 - PPP - S - O Example: T40 - 03M - E - B
PPP = Pressure Range S = Supply Voltage O = Offset
(See Note)
See Reference Table A C = 24 VAC 0 = No offset
D = 120 VAC A = 1/4 offset E = 240 VAC B = 1/2 offset
If the measured differential pressure is expected to go from positive to negative, a transmitter with offset (elevated zero) should be ordered.
Three options are available: “0” No offset. At zero differential pressure the output signal is: 4 mA (4 to 20 mA range) Pressure excursion: 0% to 100% of Range, see Table A “A” 1/4 span offset. At zero differential pressure the output signal is: 8 mA (4 to 20 mA range) Pressure excursion: -33% to 100% of Range, see Table A “B” 1/2 span offset. At zero differential pressure the output signal is: 12 mA (4 to 20 mA range) Pressure excursion: -100% to 100% of Range see Table A
To order: determine the positive pressure range; from Table A find the corresponding pressure code, then add the required offset (none, A, or B).
For example, T30 05E A is a transmitter with a maximum range of 1 in (25.40 mm) of H2O at 20 mA and a minimum range of -0.33 in of H2O at 4 mA.
Page 8
Table A - Standard Pressure Ranges

03E 0 to 0.300 in H20
03P
0 to 0.500 in H20
04P
04E
0 to 1.00 in H20
05P
05E
0 to 2.00 in H20
20 in H20
06P
06E
0 to 3.00 in H20
07P
07E
0 to 5.00 in H20
08P
08E
0 to 10.0 in H20
5 psid
09P
09E
Amphenol
Advanced Sensors
0 to 75.0 Pa
03M 0 to 7.50 mm H20
0 to 100.0 Pa
04M 0 to 10.00 mm H20
0 to 250 Pa
05M 0 to 25.0 mm H20
0 to 500 Pa
5 kPa
06M 0 to 50.0 mm H20
500 mm
0 to 750 Pa
07M 0 to 75.0 mm H20
0 to 1.00 kPa
08M 0 to 100 mm H20
0 to 2.50 kPa
35 kPa
09M 0 to 250 mm H20
3.5 m
www.telaire.com
www.amphenol-sensors.com
© 2014 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice. Other company names and product names used in this document are the registered trademarks or
trademarks of their respective owners.