REXL2TMJD SCHNEIDER
Document overview
- PDF pages: 7
Technical content
Page 1
Harmony, Miniature plug-in timing relay, 5 A, 2
Characteristics
CO, 0.1 s..100 h, on-delay, 12 V DC
Product availability : Non-Stock - Not normally stocked in distribution facility
Price\* : 53.00 USD

Main
Range of Product
Harmony Timer Relays
Product or Component Type
Single function relay
Fixing mode
Plug-in socket)
Discrete output type
Relay
Contacts type and composition
2 C/O
Component name
REXL
Time delay type
Power on-delay
Time delay range
10...100 h 0.1...1 s 1...10 s 6...60 min 1...10 h 1...10 min 6...60 s
Complementary
Contacts material
Cadmium free
[Us] rated supply voltage
12 V DC
Voltage range
0.9...1.1 Us
Line Rated Current
5 A AC
Repeat accuracy
+/- 0.5 % 10 % at full scale 25 °C EN/IEC 61812-1
Setting accuracy of time delay Temperature Drift
0.05 %/°C 250 ms after time delay, on de-energisation
Maximum reset time
50 ms during time delay, on de-energisation
Voltage drift
+/- 0.2 %/V
Maximum switching capacity
4 x 5 A
\* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021
Page 2
Maximum temporary permissible
10 A < 10 s
current Minimum switching current
100 mA
Electrical durability
100000 cycles 250 V AC resistive
Mechanical durability
10000000 cycles
Maximum power consumption
1.5 W
[Ui] rated insulation voltage
250 V IEC 255 Group C 250 V VDE 0010
Output overvoltage protection
2 J
Surge withstand
2 kV EN/IEC 61000-4-5 level 3
Creepage distance
4 kV/3 IEC 60664-1
Local signalling
for output in operation 1 LED (red) for power ON 1 LED (yellow)
Net Weight
0.11 lb(US) (0.05 kg)
Environment
Immunity to microbreaks
5 ms 2 kV 1 mA/1 minute 50 Hz EN/IEC 60601-1
Dielectric strength
2 kV 1 mA/1 minute 50 Hz EN/IEC 61812-1
Standards
93/68/EEC EN/IEC 61812-1 EN/IEC 60601-1 89/336/EEC EN/IEC 60601-2 73/23/EEC EN 61000-6-2 EN 50081-2
Product Certifications
UL CUL
Ambient Air Temperature for
-4…140 °F (-20…60 °C)
Operation Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
IP degree of protection
IP50 conforming to IEC 60529
Vibration resistance
0.35 mm 10…55 Hz)IEC 60068-2-6 95 % without condensation IEC 60068-2-6
Relative Humidity
6 kV in contact EN/IEC 61000-4-2 level 3
Resistance to electrostatic discharge
8 kV in air EN/IEC 61000-4-2 level 3 9.14 V/m (10 V/m) EN/IEC 61000-4-3 level 3
Resistance to electromagnetic fields Resistance to fast transients
2 kV EN/IEC 61000-4-4 level 3 10 V 0.15...80 MHz)EN/IEC 61000-4-6 level 3
Immunity to radioelectric fields Immunity to voltage dips
= 95 % / 1 s EN/IEC 61000-4-11 30 % / 10 ms EN/IEC 61000-4-11 60 % / 100 ms EN/IEC 61000-4-11 Class B EN 55022 (EN 55011 group 1)
Disturbance radiated/conducted
Ordering and shipping details
22370 - RE, RM MISC TIMERS & COUNTERS
Category Discount Schedule
CP2
GTIN
03389119400008
Nbr. of units in pkg.
1
Package weight(Lbs)
1.80 oz (51 g)
Returnability
No
Country of origin
ID
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
1.22 in (3.1 cm)
Page 3
Package 1 width
2.91 in (7.4 cm)
Package 1 Length
1.22 in (3.1 cm)
Offer Sustainability
Sustainable offer status
Green Premium product WARNING: This product can expose you to chemicals including: Nickel compounds, which is known
California proposition 65
to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Directive
EU RoHS Declaration
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile The product must be disposed on European Union markets following specific waste collection and
WEEE
never end up in rubbish bins.
Contractual warranty
Warranty
18 months
Page 4

Page 5
Connections and Schema
Terminal Referencing
Page 6
Technical Description
Function A : Power on Delay Relay
Description The timing period T begins on energisation. After timing, the outputs close. 2 Timed C/O Contacts
Page 7
Technical Description
Legend
Relay de-energised Relay energised Output open Output closed
| R | Relay output |
| T | Timing period |