RENF22R2MMW SCHNEIDER
Document overview
- PDF pages: 35
Technical content
Page 1
Harmony, NFC modular timing relay, 8 A, 2 CO,
Characteristics
0.1 s…999 h, multifunction, 24...240 V AC/DC
Product availability : Stock - Normally stocked in distribution facility
Price\* : 90.00 USD

Main
Range of Product
Harmony Timer Relays
Product or Component Type
Multifunction relay
Device short name
RENF22
Supported OS
Android
Software Version
V4.4 and above Zelio NFC downloadable from Google Play store)
App for product
Complementary
Discrete output type
Relay
Nominal output current
8 A 2 C/O timed contact, cadmium free
Contacts type and composition
1 C/O timed and instantaneous contact, cadmium free
Time delay type
Power on-delay On-delay and off-delay Pulse delay Asymmetrical on-delay and off-delay Interval Off-delay Symmetrical flashing Safe-guard Star-delta Asymmetrical flashing Bistable
Time delay range
0.1 s...999 h
Product Compatibility
NFC enabled mobile device
[Us] rated supply voltage
24...240 V AC/DC
Release input voltage
<= 2.4 V
Voltage range
0.85...1.1 Un
\* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021
Page 2
Maximum RF power transmitted
0.0002 mW
NFC operating frequency
13.56 MHz
Supply frequency
50...60 Hz +/- 5 % Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1
Tightening torque
5.3…8.8 lbf.in (0.60…0.99 N.m) IEC 60947-1
Housing material
Self-extinguishing
Repeat accuracy
+/- 0.2 % 10 s...999 h +/- 0.5 % 100 ms...10 s
Temperature Drift
+/- 0.05 %/°C
Voltage drift
+/- 0.2 %/V
Setting accuracy of time delay
+/- 1 % 1...999 h 77 °F (25 °C) +/- 2 % 1 h 77 °F (25 °C) +/- 20 ms 100 ms...10 s 77 °F (25 °C)
Control signal pulse width
100 ms with load in parallel 60 ms no-load
Insulation resistance
100 MOhm 500 V DC IEC 60664-1
Recovery time
120 ms on de-energisation
Power consumption in VA
3 VA 240 V AC
Power consumption in W
1.5 W 240 V DC 0.6 W 24 V DC
Switching capacity in VA
2000 VA
Minimum switching current
10 mA 5 V
Maximum switching current
8 A
Maximum switching voltage
250 V 100000 cycles for resistive load, 8 A at 250 V, AC
Electrical durability Mechanical durability
10000000 cycles
Rated impulse withstand voltage
5 kV 1.2/50 µs IEC 60664-1
Power on delay
100 ms
Creepage distance
4 kV/3 IEC 60664-1
Overvoltage category
III IEC 60664-1 MTTFd = 227.5 years 100 % duty cycle continuous operating condition at 30 °C
Safety reliability data Mounting position
Any position 35 mm DIN rail conforming to EN/IEC 60715
Mounting support Status LED
Un, green LED steady)power ON R1, amber LED steady)relay energised R2, amber LED steady)relay energised Pairing, green LED steady)communication status Un, green LED fast blinking)diagnosis mode R1, amber LED blinking)timing in progress R2, amber LED blinking)timing in progress
Maximum communication distance
10 mm
Response Time
2 s
Maximum Width
0.89 in (22.5 mm)
Net Weight
0.20 lb(US) (0.0904 kg)
Environment
Immunity to microbreaks
10 ms 2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply with basic insulation
Dielectric strength
basic insulation
Standards
EN 61000-6-1 EN 61000-6-2 EN 61000-6-4 EN 61812-1 EN 61000-6-3
Directives
2014/35/EU - low voltage directive
Page 3
2014/53/EU - radio equipment directive 2014/30/EU - electromagnetic compatibility
Product Certifications
CE CSA KC UL CCC EAC DNV-GL
Ambient Air Temperature for
-4…140 °F (-20…60 °C)
Operation Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
IP degree of protection
Housing IP40 IEC 60529 IP40 front face: conforming to IEC 60529 Terminals IP20 IEC 60529
Pollution degree
3 IEC 60664-1 20 m/s² 10…150 Hz)IEC 60068-2-6
Vibration resistance
15 gn not operating 11 ms IEC 60068-2-27
Shock resistance
5 gn in operation 11 ms IEC 60068-2-27
Relative humidity
95 % 77…131 °F (25…55 °C) Electrostatic discharge immunity test 6 kV contact discharge)level 3 EN/IEC 61000-4-2
Electromagnetic compatibility
Electrostatic discharge immunity test 8 kV air discharge)level 3 EN/IEC 61000-4-2 Fast transients immunity test 1 kV capacitive connecting clip)level 3 IEC 61000-4-4 Fast transients immunity test 2 kV direct contact)level 3 IEC 61000-4-4 Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 Radiated radio-frequency electromagnetic field immunity test 10 V 0.15...80 MHz)level 3 IEC 61000-4-6 Electromagnetic field immunity test 10 V/m 80 MHz...1 GHz)level 3 IEC 61000-4-3 Immunity to microbreaks and voltage drops 30 % 500 ms) IEC 61000-4-11
Immunity to microbreaks and voltage drops 100 % 20 ms) IEC 61000-4-11 Radiated emissionclass B EN 55022 Conducted emissionclass A EN 55022 Electromagnetic field immunity test 3 V/m 1.4 GHz...2 GHz)level 2 IEC 61000-4-3 Electromagnetic field immunity test 1 V/m 2...2.7 GHz)level 1 IEC 61000-4-3
Ordering and shipping details
22376 - RELAYS-MEASUREMENT(RM4)
Category Discount Schedule
CP2
GTIN
03606480936203
Nbr. of units in pkg.
1
Package weight(Lbs)
3.66 oz (103.635 g)
Returnability
Yes
Country of origin
ID
Packing Units
Unit Type of Package 1
PCE
Package 1 Height
0.94 in (2.4 cm)
Package 1 width
3.17 in (8.05 cm)
Package 1 Length
3.72 in (9.45 cm)
Offer Sustainability
Sustainable offer status
Green Premium product WARNING: This product can expose you to chemicals including: Nickel compounds, which is known
California proposition 65
to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
REACh Regulation
REACh Declaration Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Directive
EU RoHS Declaration
Mercury free
Yes
Page 4
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
Page 5

Page 6
Connections and Schema
Internal Wiring Diagram

Page 7
Connections and Schema
Wiring Diagram

Page 8
Function A: Power On-Delay Relay
Description On energisation of power supply, the timing period T starts. After timing, the output(s) R close(s).The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 9
Function At: Power On-Delay Relay with Pause / Summation Control Signal
Description
On energisation of power supply, the timing period T starts.Timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

T = t1 + t2 +…
Page 10
Function Ac: On-Delay and Off-Delay Relay with Control Signal
Description
After energisation of power supply and energization of Y1 causes the timing period T to start. At the end of this timing period, the output(s) R close(s). When deenergization of Y1, the timing T starts. At the end of this timing period T,the output(s) R revert(s) to its/their initial position. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 11
Function Ad : Pulse Delayed Relay with Control Signal
Description
After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. At the end of this timing period T, the output(s) R close(s). The output(s) R reverts to its initial position the next time Y1 is energized in pulsation or permanent energized manner. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 12
Function Ah : Pulse Delayed Relay (Single Cycle) with Control Signal
Description
After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. A single flashing cycle then starts with 2 timing periods T of equal duration (start with output(s) R in initial position). Output(s) R closes at the end of the first timing period T and reverts to its initial position at the end of the second timing period T. Re-energizing of Y1, either in pulsation or permanent energized manner, will re-start the single flashing cycle again. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 13
Function Ak: Asymmetrical On-Delay and Off-Delay Relay With Control Signal
Description
After energisation of power supply and energization of Y1, timing starts for a period Ta. At the end of this timing period Ta, the output(s) R closes. Deenergization of Y1 causes a second timing period Tr to start. At the end of this timing period Tr, the output(s) R reverts to its initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 14
Function B: Single Interval Relay with Control Signal
Description After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. The output(s) R close(s) for the duration of the timing period T then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 15
Function Bw : Double Interval Relay with Control Signal
Description After energisation of power supply, transition of Y1 (either from energization to deenergization or vice-versa) will cause the output(s) R close(s) for the duration of the timing period T then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 16
Function C: Off-Delay Relay with Control Signal
Description After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 17
Function D: Symmetrical Flashing Relay (Starting Pulse-Off)
Description On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 18
Function Di: Symmetrical Flashing Relay (Starting Pulse-On)
Description On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 19
Function Dt: Symmetrical Flashing Relay (Starting Pulse-Off) With Pause / Summation Control Signal
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then changes to output(s) R close(s).The output(s) R close state will remain for the same timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

T = t1 + t2 +… T = t'1 + t'2 +…
Page 20
Function Dit: Symmetrical Flashing Relay (Starting Pulse-On) With Pause / Summation Control Signal
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then revert(s) to its/their initial state.The output(s) R at initial state will remain for the same timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R change(s) to close state.This cycle is repeated indefinitely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

T = t1 + t2 +… T = t'1 + t'2 +…
Page 21
Function H: Interval Relay
Description On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s) to its/ their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 22
Function Ht: Interval Relay With Pause / Summation Control Signal
Description
On energisation of power supply, output(s) R close(s) and timing period T starts.The timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED" or instantaneous (when set to "INST").
Function: 2 Output

T = t1 + t2 +…
Page 23
Function L: Asymmetrical Flashing Relay (Starting Pulse-Off)
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr then change(s) to output(s) R close(s) for the another timing duration Ta. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 24
Function Li: Asymmetrical Flashing Relay (Starting Pulse-On)
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta then change(s) to its/their initial state for timing duration Tr. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 25
Function Lt: Asymmetrical Flashing Relay (Starting Pulse-Off) With Pause / Summation Control Signal
Description
On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s). The output(s) R close state will remain for the same timing duration Ta and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial state. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Tr = t1 + t2 +… Ta = t'1 + t'2 +…
Page 26
Function Lit: Asymmetrical Flashing Relay (Starting Pulse-On) With Pause / Summation Control Signal
Description
On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial state. The output(s) R at initial state will remain for timing duration Tr the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s) This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Ta = t1 + t2 +… Tr = t'1 + t'2 +…
Page 27
Function N : Safe-Guard Relay
Description
After energisation of power supply and on energization of Y1 cause the output(s) R close(s) and starts the timing T. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R close(s) at the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R remain(s) closed and timing restarted base on the last energization of Y1. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 28
Function O : Delayed Safe-Guard Relay
Description
On energisation of power supply, the timing T starts. At the end of this timing period, the output(s) R close(s). On energization of Y1, the output(s) R revert(s) to its/their initial state and the timing T restarts. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R close(s) at the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R remain(s) at its/their initial state and timing restarted base on the last energization of Y1. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 29
Function P : Pulse Delayed Relay with Fixed Pulse Length
Description
On energisation of power supply, the timing T starts. At the end of this period, the output(s) R close(s) for a fixed time P then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

P = 500ms
Page 30
Function Pt : Pulse Delayed Relay With Fixed Pulse Length and Pause / Summation Control Signal
Description
On energisation of power supply, the timing T starts. The timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s) for a fixed time P then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

T = t1 + t2 + … P = 500ms
Page 31
Function Qt: Star-Delta Relay (2 CO Outputs with Split Common)
Description
On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).At the end of the timing period T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. Diagnostic feature not available.
Function: 2 Output

T = 50, 60... ms
Page 32
Function Qtt: Star-Delta Relay (2 CO Outputs With Split Common) with Pause / Summation Control Signal
Description
On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).During STAR connection time, the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. Diagnostic feature not available.
Function: 2 Output

T = t1 + t2 +... t = 50, 60 ... ms
Page 33
Function TL : Bistable Relay with Control Signal On
Description
After energisation of power supply and on energization of Y1 cause the output(s) R close(s). The subsequent on energization of Y1 cause the output(s) R revert(s) to its/their initial state. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 34
Function Tt : Retriggerable Bistable Relay with Control Signal On
Description
After energisation of power supply and on energization of Y1 cause the output(s) R close(s) and starts the timing T. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R will toggle from its/their present status the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R toggle from its/their present status as soon as Y1 energizes without completing T duration. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Page 35
Function W: Interval Relay with Control Signal Off
Description
After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.At the end of the timing period, the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").
Function: 2 Output

Legend
Relay de-energised Relay energised Output open Output closed
| U - | Supply |
| R1/R2 - | 2 timed outputs |
| Ta - | Adjustable On-delay |
| Tr - | Adjustable Off-delay |
| Y1 - | Retrigger / Restart control |
| R2 inst. - | The second output is instantaneous if the right position is selected |
| T - | Timing period |
| R4 - | Delta contact output |
| t - | Delay to switch ON Delta contact output |
| R3 - | Star-Delta contact output |