RE7ML11BU SCHNEIDER

Document overview

  • PDF pages: 19

Technical content

Page 1

time delay relay 6 functions - 0.05..1 s - 24 V AC

Characteristics

DC - 1OC

PDF page 1 diagram

Commercial status

Discontinued on: 01 June 2016

End-of-service on: 01 June 2016

Main

Range of product

Zelio Time

Product or component type

Industrial timing relay

Component name

RE7

Time delay type

Di D W C A H

Time delay range

0.05 s...300 h

Complementary

Discrete output type

Relay

Contacts material

90/10 silver nickel contacts

Width pitch dimension

22.5 mm

[Us] rated supply voltage

110...240 V AC 50/60 Hz 24 V AC/DC 50/60 Hz 42...48 V AC/DC 50/60 Hz

Voltage range

0.85...1.1 Us Screw terminals, 2 x 1.5 mm² flexible with cable end

Connections - terminals

Screw terminals, 2 x 2.5 mm² flexible without cable end

Tightening torque

0.6…1.1 N.m

Setting accuracy of time delay

+/- 10 % of full scale

Repeat accuracy

+/- 0.2 %

Temperature drift

< 0.07 %/°C

Voltage drift

< 0.2 %/V

Minimum pulse duration

20 ms

Reset time

50 ms

Maximum switching voltage

250 V AC/DC

Mechanical durability

20000000 cycles

[Ith] conventional free air thermal

8 A

current Maximum [Ie] rated operational current 2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660

0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660

Mar 4, 2021

Page 2

0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660

Minimum switching capacity

at 12 V 10 mA

Input voltage

< 60 V X1Z2 terminal(s) < 60 V Y1Z2 terminal(s)

Maximum switching current

1 mA (X1Z2) 1 mA (Y1Z2) 3/4 wires sensors PNP/NPN without internal load <50 m X1Z2 terminal(s)

Input compatibility

3/4 wires sensors PNP/NPN without internal load <50 m Y1Z2 terminal(s) Linear 47 kOhm (+/- 20 %), 0.2 W, cable length <25 m Z1Z2 terminal(s)

Potentiometer characteristic Marking

CE

Overvoltage category

III conforming to IEC 60664-1 250 V between contact circuit and control inputs IEC certified

[Ui] rated insulation voltage

250 V between contact circuit and power supply IEC certified 300 V between contact circuit and control inputs CSA certified 300 V between contact circuit and power supply CSA certified

Supply disconnection value

0.1 Uc

Operating position

Any position without derating 2 kV conforming to IEC 61000-4-5 level 3

Surge withstand Power consumption in VA

0.7 VA at 24 V 1.6 VA at 48 V 1.8 VA at 110 V 8.5 VA at 240 V

Maximum power consumption in W

0.5 W at 24 V 1.2 W at 48 V

Terminal description

(Y1)UNUSED (15-16-18)OC (Z1)UNUSED (Z2)UNUSED (B1-A2)CO ALT (X1)UNUSED

Height

78 mm

Width

22.5 mm

Depth

80 mm

Net weight

0.15 kg

Environment

Immunity to microbreaks

3 ms

Standards

EN/IEC 61812-1

Product certifications

CSA GL UL

Ambient air temperature for storage

-40…85 °C

Ambient air temperature for operation

-20…60 °C 15…85 % 3K3 conforming to IEC 60721-3-3

Relative humidity

0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6

Vibration resistance

15 gn for 11 ms conforming to IEC 60068-2-27

Shock resistance IP degree of protection

IP20 (terminals) IP50 (housing)

Pollution degree

3 conforming to IEC 60664-1

Dielectric strength

2.5 kV

Non-dissipating shock wave

4.8 kV 6 kV in contact conforming to IEC 61000-4-2 level 3

Resistance to electrostatic discharge

8 kV in air conforming to IEC 61000-4-2 level 3 10 V/m conforming to IEC 61000-4-3 level 3

Resistance to electromagnetic fields

2 kV conforming to IEC 61000-4-4 level 3

Resistance to fast transients Disturbance radiated/conducted

CISPR 11 group 1 - class A CISPR 22 - class A

Page 3

Packing Units

Package 1 Weight

0.131 kg

Package 1 Height

0.270 dm

Package 1 width

0.820 dm

Package 1 Length

0.870 dm

Contractual warranty

Warranty

18 months

Page 4

Dimensions Drawings

Width 22.5 mm

Rail Mounting

PDF page 4 diagram

Screw Fixing

PDF page 4 diagram

Page 5

Connections and Schema

Internal Wiring Diagram

Page 6

Connections and Schema

Recommended Application Wiring Diagram

Start on Energisation

PDF page 6 diagram

1 Supply 2 12…48 V 3 24 V

Page 7

Connections and Schema

Recommended Application Wiring Diagram

Start by External Control

PDF page 7 diagram

1 Supply 2 12…48 V 3 24 V

Page 8

Connections and Schema

Recommended Application Wiring Diagram

External Control of Partial Stop

PDF page 8 diagram

1 Supply 2 12…48 V 3 24 V

Page 9

Connections and Schema

Connection of Potentiometer

PDF page 9 diagram

Page 10

Connections and Schema

Connection Precautions

PDF page 10 diagram
PDF page 10 diagram

Page 11

Performance Curves

Performance Curves

A.C. Load Curve 1

Electrical durability of contacts on resistive loading millions of operating cycles

PDF page 11 diagram

X Current broken in A Y Millions of operating cycles

A.C. Load Curve 2

Reduction factor k for inductive loads (applies to values taken from durability curve 1).

PDF page 11 diagram

X Power factor on breaking (cos ϕ) Y Reduction factor k Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos ϕ = 0.3. For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles. As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore becomes:1.5 106 operating cycles x 0.6 = 900 000 operating cycles.

D. C. Load Limit Curve

PDF page 11 diagram

Page 12

X Current in A Y Voltage in V 1 L/R = 20 ms 2 L/R with load protection diode 3 Resistive load

Page 13

Technical Description

Function A : Power on Delay Relay

Description The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.

Function: 1 Output

Function: 2 Outputs

PDF page 13 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Page 14

Technical Description

Function C : Off-Delay Relay with Control Signal

Description After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

Function: 1 Output

PDF page 14 diagram

Function: 2 Outputs

PDF page 14 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Page 15

Technical Description

Function D : Symmetrical Flasher Relay (Starting Pulse Off)

Description Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous.

Function: 1 Output

Function: 2 Outputs

PDF page 15 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Page 16

Technical Description

Function Di : Symmetrical Flasher Relay (Starting Pulse On)

Description Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous.

Function: 1 Output

Function: 2 Outputs

PDF page 16 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Page 17

Technical Description

Function H : Interval Relay

Description On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/ their initial state. The second output can be either timed or instantaneous.

Function: 1 Output

Function: 2 Outputs

PDF page 17 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Page 18

Technical Description

Function W : Interval Relay with Control Signal Off

Description After power-up and opening of the control contact, the output(s) close(s) for a timing period T. At the end of this timing period the output(s) revert(s) to its/their initial state. The second output can be either timed or instantaneous.

Function: 1 Output

PDF page 18 diagram

Function: 2 Outputs

PDF page 18 diagram

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).

Page 19

Technical Description

Legend

Relay de-energised Relay energised Output open Output closed

C Control contact
G Gate
R Relay or solid state output
R1/R2 2 timed outputs
R2 inst. The second output is instantaneous if the right position is selected
T Timing period
Ta - Adjustable On-delay
Tr - Adjustable Off-delay
U Supply

RE7ML11BU is replaced by:

PDF page 19 diagram

Relay Output RE22R1MYMR

Modular timing relay, 8 A, 0.05 s…300 h, 1 CO, multi-function, 24...240 V AC/DC

Qty 1

Reason for Substitution: End of life | Substitution date: 18 August 2016