RE7ML11BU SCHNEIDER
Document overview
- PDF pages: 19
Technical content
Page 1
time delay relay 6 functions - 0.05..1 s - 24 V AC
Characteristics
DC - 1OC

Commercial status
Discontinued on: 01 June 2016
End-of-service on: 01 June 2016
Main
Range of product
Zelio Time
Product or component type
Industrial timing relay
Component name
RE7
Time delay type
Di D W C A H
Time delay range
0.05 s...300 h
Complementary
Discrete output type
Relay
Contacts material
90/10 silver nickel contacts
Width pitch dimension
22.5 mm
[Us] rated supply voltage
110...240 V AC 50/60 Hz 24 V AC/DC 50/60 Hz 42...48 V AC/DC 50/60 Hz
Voltage range
0.85...1.1 Us Screw terminals, 2 x 1.5 mm² flexible with cable end
Connections - terminals
Screw terminals, 2 x 2.5 mm² flexible without cable end
Tightening torque
0.6…1.1 N.m
Setting accuracy of time delay
+/- 10 % of full scale
Repeat accuracy
+/- 0.2 %
Temperature drift
< 0.07 %/°C
Voltage drift
< 0.2 %/V
Minimum pulse duration
20 ms
Reset time
50 ms
Maximum switching voltage
250 V AC/DC
Mechanical durability
20000000 cycles
[Ith] conventional free air thermal
8 A
current Maximum [Ie] rated operational current 2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
Mar 4, 2021
Page 2
0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660 3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
Minimum switching capacity
at 12 V 10 mA
Input voltage
< 60 V X1Z2 terminal(s) < 60 V Y1Z2 terminal(s)
Maximum switching current
1 mA (X1Z2) 1 mA (Y1Z2) 3/4 wires sensors PNP/NPN without internal load <50 m X1Z2 terminal(s)
Input compatibility
3/4 wires sensors PNP/NPN without internal load <50 m Y1Z2 terminal(s) Linear 47 kOhm (+/- 20 %), 0.2 W, cable length <25 m Z1Z2 terminal(s)
Potentiometer characteristic Marking
CE
Overvoltage category
III conforming to IEC 60664-1 250 V between contact circuit and control inputs IEC certified
[Ui] rated insulation voltage
250 V between contact circuit and power supply IEC certified 300 V between contact circuit and control inputs CSA certified 300 V between contact circuit and power supply CSA certified
Supply disconnection value
0.1 Uc
Operating position
Any position without derating 2 kV conforming to IEC 61000-4-5 level 3
Surge withstand Power consumption in VA
0.7 VA at 24 V 1.6 VA at 48 V 1.8 VA at 110 V 8.5 VA at 240 V
Maximum power consumption in W
0.5 W at 24 V 1.2 W at 48 V
Terminal description
(Y1)UNUSED (15-16-18)OC (Z1)UNUSED (Z2)UNUSED (B1-A2)CO ALT (X1)UNUSED
Height
78 mm
Width
22.5 mm
Depth
80 mm
Net weight
0.15 kg
Environment
Immunity to microbreaks
3 ms
Standards
EN/IEC 61812-1
Product certifications
CSA GL UL
Ambient air temperature for storage
-40…85 °C
Ambient air temperature for operation
-20…60 °C 15…85 % 3K3 conforming to IEC 60721-3-3
Relative humidity
0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6
Vibration resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Shock resistance IP degree of protection
IP20 (terminals) IP50 (housing)
Pollution degree
3 conforming to IEC 60664-1
Dielectric strength
2.5 kV
Non-dissipating shock wave
4.8 kV 6 kV in contact conforming to IEC 61000-4-2 level 3
Resistance to electrostatic discharge
8 kV in air conforming to IEC 61000-4-2 level 3 10 V/m conforming to IEC 61000-4-3 level 3
Resistance to electromagnetic fields
2 kV conforming to IEC 61000-4-4 level 3
Resistance to fast transients Disturbance radiated/conducted
CISPR 11 group 1 - class A CISPR 22 - class A
Page 3
Packing Units
Package 1 Weight
0.131 kg
Package 1 Height
0.270 dm
Package 1 width
0.820 dm
Package 1 Length
0.870 dm
Contractual warranty
Warranty
18 months
Page 4
Dimensions Drawings
Width 22.5 mm
Rail Mounting

Screw Fixing

Page 5
Connections and Schema
Internal Wiring Diagram
Page 6
Connections and Schema
Recommended Application Wiring Diagram
Start on Energisation

1 Supply 2 12…48 V 3 24 V
Page 7
Connections and Schema
Recommended Application Wiring Diagram
Start by External Control

1 Supply 2 12…48 V 3 24 V
Page 8
Connections and Schema
Recommended Application Wiring Diagram
External Control of Partial Stop

1 Supply 2 12…48 V 3 24 V
Page 9
Connections and Schema
Connection of Potentiometer

Page 10
Connections and Schema
Connection Precautions


Page 11
Performance Curves
Performance Curves
A.C. Load Curve 1
Electrical durability of contacts on resistive loading millions of operating cycles

X Current broken in A Y Millions of operating cycles
A.C. Load Curve 2
Reduction factor k for inductive loads (applies to values taken from durability curve 1).

X Power factor on breaking (cos ϕ) Y Reduction factor k Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos ϕ = 0.3. For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles. As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore becomes:1.5 106 operating cycles x 0.6 = 900 000 operating cycles.
D. C. Load Limit Curve

Page 12
X Current in A Y Voltage in V 1 L/R = 20 ms 2 L/R with load protection diode 3 Resistive load
Page 13
Technical Description
Function A : Power on Delay Relay
Description The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Page 14
Technical Description
Function C : Off-Delay Relay with Control Signal
Description After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output

Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Page 15
Technical Description
Function D : Symmetrical Flasher Relay (Starting Pulse Off)
Description Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Page 16
Technical Description
Function Di : Symmetrical Flasher Relay (Starting Pulse On)
Description Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Page 17
Technical Description
Function H : Interval Relay
Description On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/ their initial state. The second output can be either timed or instantaneous.
Function: 1 Output
Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Page 18
Technical Description
Function W : Interval Relay with Control Signal Off
Description After power-up and opening of the control contact, the output(s) close(s) for a timing period T. At the end of this timing period the output(s) revert(s) to its/their initial state. The second output can be either timed or instantaneous.
Function: 1 Output

Function: 2 Outputs

2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
Page 19
Technical Description
Legend
Relay de-energised Relay energised Output open Output closed
| C | Control contact |
| G | Gate |
| R | Relay or solid state output |
| R1/R2 | 2 timed outputs |
| R2 inst. | The second output is instantaneous if the right position is selected |
| T | Timing period |
| Ta - | Adjustable On-delay |
| Tr - | Adjustable Off-delay |
| U | Supply |
RE7ML11BU is replaced by:

Relay Output RE22R1MYMR
Modular timing relay, 8 A, 0.05 s…300 h, 1 CO, multi-function, 24...240 V AC/DC
Qty 1
Reason for Substitution: End of life | Substitution date: 18 August 2016