RE22R2CMR SCHNEIDER

Document overview

  • PDF pages: 6

Technical content

Page 1

Harmony, Modular timing relay, 8 A, 2 CO, 0.05

Characteristics

s...300 h, off delay, 24...240 V AC/DC

Product availability : Stock - Normally stocked in distribution facility

Price\* : 71.60 USD

PDF page 1 diagram

Main

Range of Product

Harmony Timer Relays

Product or Component Type

Single function relay

Discrete output type

Relay

Device short name

RE22

Nominal output current

8 A

Complementary

1 C/O timed or instantaneous contact, cadmium free

Contacts type and composition

2 C/O timed contact, cadmium free

Time delay type

Off-delay

Time delay range

10...100 s 3...30 h 1...10 s 3...30 s 30...300 h 0.3...3 s 0.05...1 s 30...300 min 30...300 s 3...30 min

Control type

Rotary knob Diagnostic button

[Us] rated supply voltage

24...240 V AC/DC 50/60 Hz

Release input voltage

<= 2.4 V

Voltage range

0.85...1.1 Us

Supply frequency

50...60 Hz +/- 5 % Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end

Connections - terminals

Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end

\* Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021

Page 2

Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end 5.31…8.85 lbf.in (0.6…1 N.m) IEC 60947-1

Tightening torque Housing material

Self-extinguishing

Repeat accuracy

+/- 0.5 % IEC 61812-1

Temperature Drift

+/- 0.05 %/°C

Voltage drift

+/- 0.2 %/V +/- 10 % of full scale 25 °C IEC 61812-1

Setting accuracy of time delay Control signal pulse width

100 ms with load in parallel 30 ms

Insulation resistance

100 MOhm 500 V DC IEC 60664-1

Recovery time

120 ms on de-energisation

Immunity to microbreaks

10 ms

Power consumption in VA

3 VA 240 V AC

Power consumption in W

1.5 W 240 V DC

Switching capacity in VA

2000 VA

Minimum switching current

10 mA 5 V DC

Maximum switching current

8 A

Maximum switching voltage

250 V AC

Electrical durability

100000 cycles, 8 A at 250 V, AC-1 100000 cycles, 2 A at 24 V, DC-1

Mechanical durability

10000000 cycles

Rated impulse withstand voltage

5 kV 1.2…50 µs IEC 60664-1

Power on delay

100 ms

Creepage distance

4 kV/3 IEC 60664-1

Overvoltage category

III IEC 60664-1

Safety reliability data

MTTFd = 251.1 years B10d = 230000

Mounting position

Any position 35 mm DIN rail conforming to EN/IEC 60715

Mounting support

Green LED backlight steady)dial pointer indication

Status LED

Yellow LED steady)output relay energised Yellow LED fast flashing)timing in progress and output relay de-energised Yellow LED slow flashing)timing in progress and output relay energised

Maximum Width

0.89 in (22.5 mm)

Net Weight

0.23 lb(US) (0.105 kg)

Environment

2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1

Dielectric strength Standards

UL 508 IEC 61812-1

Directives

2006/95/EC - low voltage directive 2004/108/EC - electromagnetic compatibility

Product Certifications

CSA CCC RCM CE GL UL EAC

Ambient Air Temperature for

-4…140 °F (-20…60 °C)

Operation Ambient Air Temperature for Storage

-40…158 °F (-40…70 °C)

IP degree of protection

Housing IP40 IEC 60529 Terminals IP20 IEC 60529 Front panel IP50 IEC 60529

Pollution degree

3 IEC 60664-1

Vibration resistance

20 m/s² 10…150 Hz)IEC 60068-2-6 15 gn not operating 11 ms IEC 60068-2-27

Shock resistance

Page 3

5 gn in operation 11 ms IEC 60068-2-27

Relative humidity

95 % 77…131 °F (25…55 °C) Fast transients immunity test 1 kV capacitive connecting clip)level 3 IEC 61000-4-4

Electromagnetic compatibility

Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 Electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2 Electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test 10 V/m 80 MHz...1 GHz)level 3 IEC 61000-4-3 Conducted RF disturbances 10 V 0.15...80 MHz)level 3 IEC 61000-4-6 Fast transient bursts 2 kV direct contact)level 3 IEC 61000-4-4 Immunity to microbreaks and voltage drops 30 % 500 ms) IEC 61000-4-11 Immunity to microbreaks and voltage drops 100 % 20 ms) IEC 61000-4-11

Ordering and shipping details

22376 - RELAYS-MEASUREMENT(RM4)

Category Discount Schedule

CP2

GTIN

03606480792502

Nbr. of units in pkg.

1

Package weight(Lbs)

3.81 oz (108 g)

Returnability

Yes

Country of origin

ID

Packing Units

Unit Type of Package 1

PCE

Package 1 Height

3.23 in (8.2 cm)

Package 1 width

3.74 in (9.5 cm)

Package 1 Length

1.02 in (2.6 cm)

Offer Sustainability

Sustainable offer status

Green Premium product WARNING: This product can expose you to chemicals including: Lead and lead compounds, which

California proposition 65

is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

REACh Regulation

REACh Declaration Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Directive

EU RoHS Declaration

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

China RoHS declaration

Environmental Disclosure

Product Environmental Profile

Circularity Profile

End of Life Information

Page 4

PDF page 4 diagram

Page 5

Connections and Schema

Wiring Diagram

PDF page 5 diagram

Page 6

Technical Description

Function C: Off-Delay Relay with Control Signal

Description

After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST").

Function: 1 Output

PDF page 6 diagram

Function: 2 Outputs

PDF page 6 diagram

Legend

Relay de-energised Relay energised Output open Output closed

U - Supply
T - Timing period
R1/R2 - 2 timed outputs
R2 inst. - The second output is instantaneous if the right position is selected
Y1 - Retrigger / Restart control