R9454 HAMAMATSU
Document overview
- PDF pages: 4
Technical content
Page 1

Quick Detection of Flame from Distance,
Compact UV Sensor with High Sensitivity and Wide Directivity,
Suitable for Flame Detectors and Fire Alarms.

The UV TRON R9533 and R9454 are UV sensors that utilize the photoelectric effect from metal and gas multiplication. These devices are sensitive only to UV light in a spectral range of 185 nm to 260 nm. This makes them easy to use since they do not require optical visible-cut filters. Their electrodes are optimized for ruggedness to resist mechanical shocks up to 10 times (10000 m/s2) greater than the conventional UV TRONs. The R9533 is a head-on type (UV light enters through the top of the bulb) that easily installs into equipment. The R9454 is a side-on type (UV light enters through the side of the bulb) whose outer appearance resembles the conventional flame sensor R2868. Both these types util-
ize a plate cathode and feature high sensitivity and a wide field of view (directivity).
APPLICATIONS
G Flame detectors for gas/oil lighters and matches
G Fire alarms
G Arson watch monitors
G Combustion monitors for burners
G Inspection of ultraviolet leakage
G Detection of discharge
G Ultraviolet switching
SPECIFICATIONS
GENERAL
| Parameter | R9454 | R9533 | Unit | |
|---|---|---|---|---|
| Spectral Response | 185 to 260 | nm | ||
| Window Material | UV glass | — | ||
| Weight | Approx. 1.5 | Approx. 2.5 | g | |
| MAXIMUM RATINGS | ||||
| Parameter | R9454 | R9533 | Unit | |
| Supply Voltage (DC) | 500 | 400 | V | |
| Peak Current 1 | 30 | mA | ||
| Average Discharge Current 2 | 1 | mA | ||
| Operating Ambient Temperature | -20 to +60 | -20 to +125 | °C | |
| CHARACTERISTICS (at 25 °C) | ||||
| Parameter | R9454 | R9533 | Unit | |
| Discharge Starting Voltage (with UV radiation) (DC) | Max. | 360 | 280 | V |
| Recommended Operating Voltage (DC) | 400 ± 25 | 350 ± 25 | V | |
| Background 3 | Max. | 10 | min-1 | |
| Sensitivity 4 | Typ. | 4000 | 10000 | min-1 |
NOTE: 1This is the maximum momentary current that can be handled if its full width at half maximum is less than 10 µs. 2If the tube is operated near this or higher, the service life is noticeably reduced. Use the tube within the recommended current values. 3Measured under room illuminations (approximately 500 lux) and recommended operating conditions. Note that these values may increase if the following environmental factors are present. 1. Mercury lamps, sterilization lamps, or halogen lamps are located nearby. 2. Direct or reflected sunlight is incident on the tube. 3. Electrical sparks such as welding sparks are present. 4. Radiation sources are present. 5. High electric field (including static field) generates across the tube.
4These are representative values for a wavelength of 200 nm and a light input of 10 pW/cm2. In actual use, the sensitivity will vary with the wavelength of the ultraviolet radiation and the drive circuitry employed.
Subject to local technical requirements and regulations, availability of products included in this promotional material may vary. Please consult with our sales office. Information furnished by HAMAMATSU is believed to be reliable. However, no responsibility is assumed for possible inaccuracies or omissions. Specifications are subject to change without notice. No patent rights are granted to any of the circuits described herein. ©2007 Hamamatsu Photonics K.K.
Page 2
FLAME SENSOR UV TRON ® R9454, R9533
Figure 1: UV TRON’s Spectral Response and Various Light Sources

WAVELENGTH (nm)
ULTRAVIOLET
VISIBLE
INFRARED
Figure 2: Angular Sensitivity (Directivity)
R9454

0° 100 %

HORIZONTAL
(Right figure)
ANODE CATHODE
TPT B0033EA
R9533
0°
VERTICAL VIEWING

TPT B0032EA
Page 3
Figure 3: Dimensional Outline (Unit: mm)
R9454


TOP VIEW
A–A'
SIDE VIEW
TPT A0036EB
R9533
UV GLASS BULB
CATHODE

TOP VIEW
SIDE VIEW
BOTTOM VIEW
TPT A0035EA
Figure 4: Recommended Operating Circuit
10 MΩ
4.7 kΩ\*

PULSE OUTPIT
\* This 4.7 kΩ resistor must be connected within 2.5 cm from the tip of the UVtron anode lead.
TPT C0016EA
Page 4
FLAME SENSOR UV TRON ® R9454, R9533

RELATED PRODUCTS

WEB SITE www.hamamatsu.com
HAMAMATSU PHOTONICS K.K., Electron Tube Division 314-5, Shimokanzo, Iwata City, Shizuoka Pref., 438-0193, Japan, Telephone: (81)539/62-5248, Fax: (81)539/62-2205 U.S.A.: Hamamatsu Corporation: 360 Foothill Road, P. O. Box 6910, Bridgewater. N.J. 08807-0910, U.S.A., Telephone: (1)908-231-0960, Fax: (1)908-231-1218 E-mail: usa@hamamatsu.com Germany: Hamamatsu Photonics Deutschland GmbH: Arzbergerstr. 10, D-82211 Herrsching am Ammersee, Germany, Telephone: (49)8152-375-0, Fax: (49)8152-2658 E-mail: info@hamamatsu.de France: Hamamatsu Photonics France S.A.R.L.: 19, Rue du Saule Trapu, Parc du Moulin de Massy, 91882 Massy Cedex, France, Telephone: (33)1 69 53 71 00, Fax: (33)1 69 53 71 10 E-mail: infos@hamamatsu.fr
United Kingdom: Hamamatsu Photonics UK Limited: 2 Howard Court, 10 Tewin Road Welwyn Garden City Hertfordshire AL7 1BW, United Kingdom, Telephone: 44-(0)1707-294888, Fax: 44(0)1707-325777 E-mail: info@hamamatsu.co.uk North Europe: Hamamatsu Photonics Norden AB: Smidesvägen 12, SE-171-41 SOLNA, Sweden, Telephone: (46)8-509-031-00, Fax: (46)8-509-031-01 E-mail: info@hamamatsu.se Italy: Hamamatsu Photonics Italia: S.R.L.: Strada della Moia, 1/E, 20020 Arese, (Milano), Italy, Telephone: (39)02-935 81 733, Fax: (39)02-935 81 741 E-mail: info@hamamatsu.it
TPT 1019E03 MAY 2007 IP